Maintenance Checks

1- Building 1

Plant Rooms Building 1 (Level 3)

  • Boilers (Level 3 North West Plant Room)<br>Check operational if required

  • Cooling Towers (Level 3 North Plant Room)<br>Check level in tower ponds<br>Check operational including Dosing Pumps & Chemical levels<br>Check Condenser pumps 4 & 5 (Coles ) western side of room operational.<br>Check Eye Wash Station Operational ( weekly)

  • Kitchen Extracts (Level 3 Central Plant Room).<br>-Check all VSD set in Auto<br>- Check room free of Waste & Equipment

  • Radio Repeater Building 1 (Electrical Cupboard outside Guest Lift Lobby)<br>- Check power to cabinet is on <br>- Check UPS in place and working.

  • Air Handling Units & Car Park Extracts (Level 3 North, South West & South East Plant Rooms)<br>-Please check operational & VSD units set in auto.<br>- Check rooms are free of waste & Equipment.

  • Distribution Panel (North West next to Boiler House)<br>- Check door locked<br>- checked for tripped Circuits

Plant Rooms (Level 2)s

  • Kitchen Extracts (Level 2 South Plant room)

  • Air Handling Units & Car Park Extracts (Level 2 North, North East ,South East & South West Plant Rooms)<br>- Please check operational & VSD units set in auto.<br>- Check room free of waste or Equipment

  • Chillers (Level 2 North plant Room).

  • Kitchen Extracts North East Plant Room (next to Ramp up to Level 3)

  • Distribution Panel (North West next to Maintenance Workshop)<br>- Check door locked<br>- checked for tripped Circuits including Dynalight Relays

Plant Rooms (Level 1)

  • Main Switch Room (North West)<br>- is the EP&T equipment powered and operational?<br><br>Is the Power Factor Correction (PFC) powered and operational?<br>- check percentage value & if fluctuations are present<br><br>

  • Distribution Panel (North West within Main Switch Room)<br>- Check door locked<br>- checked for tripped Circuits including Dynalight Relays

  • Rainwater harvesting Tank Room (West)<br>- Check valves open & water passing through UV filter<br>- Check Life of UV filter<br>- check level of tank (weekly)<br>- Check the 'Check Valve is operational and UPS is on stand By

  • Air Handling Units West & South<br>- Check operational & VSD is in Auto<br>- Check room free free of Waste & Equipment

  • Fire Control Room (Outside South West Exit).<br>- check for Isolations<br>- Check for Alarms

  • EWIS Panel<br>- Check for faults

  • Mains Water Meter Room (Outside North West Exit)<br>- Check area clean and free of Waste & Equipment.<br>-

Plant Rooms (Ground Level).

  • Tenant Metering Room including Distribution Panel & IDF<br>- Check meters are functional <br>- check DB for tripped circuits including Dynalight Relays<br>- Check IDF board is secure with no loose or pulled lines.

  • Car park extract (off entry next to Richardson St )

  • Air Handling Unit (South)<br>- Check operational & VSD in auto<br>- Check room free of waste & Equipment

  • Gas isolation (Gas Safe) Switch & Intake/ meter room (South)<br>- check system is functional & not tripped<br>- Check room free of waste & Equipment

  • Communication & MDF Room (East of Gas Room end of Corridor)

Plant Rooms ( Lower Ground)

  • Distribution Panel (South west of corridor)<br>- Check door locked<br>- checked for tripped Circuits including Dynalight Relays

  • Air Handling Unit (adjoining Distribution room)<br>- Checks VSD operational & in Auto<br>- Check room free of waste & equipment

  • Car Park Extracts (South West next to lift & North Corridor )<br>- Check VSD operational & in Auto<br>- Check room clean and free of Waste & Equipment.

Plant Rooms (Basement)

  • Air Pelhams North & South<br>- check nothing stored within these areas.

  • Distribution Panel (North)<br>- Check panel door locked<br>- checked for tripped Circuits including Dynalight Relays<br>- Check integrity of Server

  • Air Handling Units & Car Park Extracts (North East)<br>- Please check operational & VSD units set in auto.<br>- Check room free of waste or Equipment

  • DAF Room (East)<br>- Check room not flooded. Low point pit empty<br>- Check inlet Flow Switch active (lights indication if working) west end of DAF<br>- check operational including Air Compressor<br>- Check air pressure correct (sight glass between 2 & 3 - between 6.25 & 6.5 pressure gauge)<br>- Flush Sludge valve (small valves at bottom of Tank leading back to DAF)<br>- Check stored level of both solids & fluid tank.

  • Sump Pumps (East & West) <br>- Check for high level alarms<br>- Test pumps in Manual

  • Grease Arrestor Room (West)<br>- Check for flooding

  • Sprinkler Tank Storage Room (South West)<br>- Check for leaks<br>-Confirm level full ( Tank level indicator)<br>- Check filler valve open

  • Sprinkler Tank Room (Weekly on Thursdays) Confirm tank capacity

  • Sprinkler valve room including diesel pumps (South West)<br>- Check pumps on stand by<br>- check all pumps are up to pressure required

  • Valves strapped open?

2 - Building 2

Plant rooms (Level 4)

  • Cooling Towers <br>- Check operational including Dosing Pumps & Chemical levels<br>-Check Eye Wash Station Operational ( weekly)

Plant Rooms Level 3

  • Are the Chillers and Pneumatics in Buildings 2

  • Boilers (Level 3 North West Plant Room)<br>Check operational if required

  • Gas intake including Metering

Plant Rooms (Level 2) Sprinkler Valve Room/ Fire Indication Panels

  • Fire panel checked and functioning?

  • Isolations noted?

  • Alarm panel checked and functioning?

  • Valves strapped open?

  • Main Switch Room (Left Door P2 Entry)<br>- is the EP&T equipment powered and operational?<br><br>Is the Power Factor Correction (PFC) powered and operational?<br>- check percentage value & if fluctuations are present<br><br>

Plant Room (Level 2) Main Switch Room/ Fire Control Room / MDF

  • EWIS checked and functional (Middle Room P2 Entry)<br>

  • MDF (Right Door P2 Entry)<br>- Check no wiring exposed or disconnected

Plant Rooms (Level 1 a)

  • Air Handling Unit / Kitchen Extracts / Toilet Extracts (East,Central & West)<br>- Check operational and VSD is in Auto (if fitted) or control panels without faults/alarms<br>- check room is free of Waste & Equipment

Tower Centre Management Office ECO (Tone Testing Every Thursday 0700- 0730 Hrs)

  • Please note areas Tested this day.

Tower Plant rooms (Levels 8-12)

  • Air Handling Unit & Toilet Extracts (Level 8 Terrace entry & Levels 9-12 West corridor access)<br>- Check operational and VSD is in Auto (if fitted) or control panels without faults/alarms<br>- check room is free of Waste & Equipment

  • Roof plant room Tank , Diesel Booster Pump<br>- Check for leaks<br>- Check fuel for Pump full and Gerry Can full.

Plant room (Level Ground A)

  • Sprinkler Tank Storage Room (behind staff toilets)<br>- Check for leaks<br>-Confirm level full ( Tank level indicator)<br>- Check filler valve open

  • Sprinkler Tank Room (Weekly on Thursdays) Confirm tank capacity

  • Auxiliary Diesel Pump<br>- check Fuel level in tank<br>- check spare fuel cans full<br>- Pump showing as on duty

Plant Room (Ground)

  • Grease Arrestor Room (off lift lobby BOH near CML storage )<br>- Check level of tank<br>- Check high level alarm<br>- Check pump in Manual are working<br>- Check room free of waste & Equipment

  • Water Meter (Behind Pandora stairwell to Keira St)<br>- Check for leaks

3- Building 3

Plant Room Level 5 (roof via plant room)

  • Cooling Towers <br>- Check operational including Dosing Pumps & Chemical levels<br>- Check Eye Wash Station Operational ( weekly)

Plant Room Level 4

  • Air Handling Units / Toilet Extracts

  • Compressors

  • Boilers

Plant rooms Dock Level

  • Main Switch Room ( 2 x Doors opposite Cardboard Compactor)<br>- is the EP&T equipment powered and operational?<br><br>Is the Power Factor Correction (PFC) powered and operational?<br>- check percentage value & if fluctuations are present<br><br>

  • Gas intake Room

  • Sprinkler Valve Room including F.I.P<br>- Check all valves are strapped open<br>- Check Fire Indicator Panel is functional <br>- Check for alarms and note isolations

  • Grease Arrestor Room (opposite Wet compactor)<br>- Check level of tank<br>- Check high level alarm<br>- Check pump in Manual are working<br>- Check room free of waste & Equipment

  • MDF

  • Mains Water Meter<br>- Check valve are locked open<br>- Check no leaks

CCTV

  • Check operational (Security Office Dock 2)

Casual Leasing

  • Is the test and tagging up to date?

  • Are the tables and chairs in good working order?

  • Is the area surrouding all casual leases clear of hazards?

Remedial Action

  • Remedial Action Required

  • Task
  • Job Details

  • Photos

Fire Control Room Inspections

Building 1 Sprinkler Valve Room

  • Sprinkler Valve Sets

  • Sprinkler Valve Set
  • Sprinkler Valve Set in range?

  • Gauge Pressure

  • Booster Valve Sets

  • Booster Valve Set
  • Booster Valve Set in range?

  • Gauge Pressure

Building 2 Sprinkler Valve Room

  • Sprinkler Valve Sets

  • Sprinkler Valve Set
  • Sprinkler Valve Set in range?

  • Gauge Pressure

  • Booster Valve Sets

  • Booster Valve Set
  • Booster Valve Set in range?

  • Gauge Pressure

Building 3 Sprinkler Valve Room

  • Sprinkler Valve Sets

  • Sprinkler Valve Set
  • Sprinkler Valve Set in range?

  • Gauge Pressure

  • Booster Valve Sets

  • Booster Valve Set
  • Booster Valve Set in range?

  • Gauge Pressure

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.