Title Page

  • Audit Title

  • Conducted on

  • Personnel

Essential Plant Checks

1 - Building 1

Plant Rooms - Building 1 (Level 3) Rooftop P1

  • Cooling Towers (Level 3 North Plant Room) Check operational including Dosing Pumps & Chemical Levels.<br>- Check VSD on AUTO x9<br>- Check Cooling Towers x2<br>- Check Water

  • Air Handling Units and Car Park Extracts (Level 3 North, South West and South East Plant Rooms)<br>Check all VSD on Auto, check no leaks corrosion<br> - North VSD x3<br> - S/W VSD x1<br> - S/E VSD x1<br> - Check orange panels for fault lights<br> - Check rooms are free of waste and equipment

  • Kitchen Extracts (Level 3 Central Plant Room). 2 Seperate Entries (East & West)<br>- Check VSD on AUTO x5<br>- Check Room Free of Waste & Equipment <br>- Check Electric Panels for Faults

  • Radio Repeater (Electrical Riser outside Guest Lift Lobby)<br>Outside Lift Lobby Check Power switch is on<br>- Check Power to Cabinet<br>- Check UPS in place and working

  • Boilers (Level 3 North West Plant Room).<br>- Check VSD on Auto x3<br>- Check BOILERS x2<br>- Check for FAULTS

  • Distribution Panel (North West next to Boiler House)<br>- Check Door Panel Locked<br>- Check for tripped Circuits/Switches

Plant Rooms (Level 2)

  • Chillers (North Plant Room, Near service lifts).<br>- Check Fault lights on Chillers x2<br>- Check VSD on AUTO x3

  • Air Handling Units & Car Park Extracts (North, N/E, S/E & S/W Plant Rooms)<br>- Check all VSD on AUTO<br> - N/E VSD x3<br> - S/E VSD x5<br>- Check extraction Fan (North)<br>- Check room free of waste and equipment

  • Kitchen Extracts (Next to AHU South Plant Room, S/E Corner)

  • Distribution Panel (N/W Corner outside Maintenance Workshop to the right)<br>- Check Panel secure and door locking<br>- Check for tripped Circuits including Dynalights

Plant Rooms (Level 1)

  • Main Switch Room (North West)<br>- Check EP&T equipment powered and operational?<br>- Check Power Factor Correction (PFC) x4 Grey Boxes/Panels to the right of Orange Panels<br>- Check percentage value &/if fluctuations are present (2 small display Windows. Have % values on them.)

  • Distribution Panel (North West within Main Switch Room)<br>- Check x2 doors are locked (Lighting & Power)<br>- Check for tripped circuits including Dynalights Relays

  • Rainwater harvesting Tank Room (West, to the right of Cleaners Storeroom)<br>- Check Valves Open & Water passing through UV filter<br>- Check Life if UV Filter<br>- Check Level of Tank & No leaks<br>- Check 'Variable Speed Controller'<br>- Check Pressure in Valves x4

  • Air Handling Units (West, AHU to the left of Staff Toilets)<br>- Check VSD in AUTO x2<br>- Check Room Free of Waste & Equipment

  • Fire Control Room (Outside S/W Exit)<br>- Check for Isolations<br>- Check for Alarms<br>- 1x Photo of Panel & Time taken

  • EWIS Panel<br>- Check for Faults (Audio etc)<br>- 1x Photo of EWIS Panel & Time taken

Plant Rooms (Ground Level)

  • Tenant Metering Room including Distribution Panel & IDF (Located inside Dock 1 next to Coles Bay)<br>- Check Meters are functioning.<br>- Check DB Board for tripped circuits including Dynalight relays.<br>- Check IDF Board is secure with no loose or pulled lines.

  • Air Handling Unit (South, right side of gas room outside service lifts)<br>- Check Operational and VSD in AUTO x1<br>- Check Dist Panel for faults (Orange)<br>- Check room free of waste and equipment

  • Gas Isolation (Gas Safe) Switch & Intake/Meter Room South)<br>- Check system is functional & not tripped, external boxes x2 for green lights<br>- Check room free of waste & equipment <br>- Check no leaks (Smell)

  • Communication & MDF Room (East of Gas Room at end of corridor)<br>- Visual inspection, No issues

Plant Rooms (Lower Ground)

  • Car Park Extracts (S/W of Corridor, opposite Best N Less door BOH )<br>- Check VSD in AUTO x1 & Operational <br>- Check room free of waste & equipment

  • Air Handling Unit (LGW131, left of Coles hoist)<br>- Check VSD in AUTO x1 & Operational <br>- Check room free of waste & equipment

  • Distribution Panel (S/W of corridor, Best N Less BOH)<br>- Check door locked<br>- Check for Tripped Circuits including Dynalight Relays<br>- Check orange panel is locked

Plant Rooms (Basement)

  • Sprinkler Valve Room Diesel pumps (S/W)<br>- Check pumps on standby<br>- Check fuel in Jerry Cans <br>- Check no Fault Lights

  • Sprinkler Tank Storage Room (S/W)<br>- Check for leaks<br>- Confirm level full (Tank level indicator)<br>- Check filler valve open

  • 2x Sump Pumps (1x West near Ex Click & Collect & 1x East outside Travelator Lobby )<br>- Check for high level alarms (Stormwater Pumps) <br>- 1x Photo West near C&C 1x Photo East outside Travelator Lobby and Times Taken<br>

  • Grease Arrestor Room (West, next to ex Click & Collect)<br>- Check for flooding

  • Distribution Panel (North mid wall)<br>- Check panel door locked<br>- Check for tripped circuits including Dynalight relays <br>- Check integrity of Server

  • Air Plenums (North & South Walls)<br>- Check for no stored items & rubbish

  • Air Handling Units & Car Park Extracts (N/E AHU B1W107)<br>- Check VSD in Auto x1 and Operational <br>- Check distribution board for Faults <br>- Check room free of waste & equipment

  • DAF Room (East)<br>- Check room not flooded <br>- Check operational including air compressor <br>- Check stored level of both fluids & solids tank<br>- Check No alarms/faults etc<br>- Check no leaks<br>- 1x Photo of DAF Room & 1x Photo of Alarm Units on wall outside DAF Room & Times Taken

2 - Building 2

Plant Room (Ground)

  • Water Meter (Behind Pandora stairwell to Keira Street<br>- Check for leaks

  • Grease Arrestor Room (off lift lobby BOH, near storage cages)<br>- Check level of tank<br>- Check high level alarm<br>- Check pump in manual and working, no faults<br>- Check room free of waste and equipment

Plant Room (Level Ground A)

  • Sprinkler Tank Storage Room (behind staff toilets)<br>- Check for leaks<br>- Confirm level full (Tank level indicator)<br>- Check filler valve open

  • Auxiliary Diesel Pump<br>- Check Fuel Level in tank and jerry cans<br>- Pump showing as on duty

Plant Rooms (Level 4) - Rooftop above Security Office

  • Cooling Towers<br>- Check operational including Dosing Pumps & Chemical levels<br>- Check no leaks<br>- Check screens in place

Plant Rooms (Level 3) - Below Cooling Towers

  • Chillers and Pneumatics <br>- Check Chillers x2 standby lights on<br>- Check distribution board (Orange) for fault lights<br> - Check VSD x6

  • Boilers (N/W Plant Room)<br>- Check operational if required <br>- Check standby lights are on

  • Gas intake including metering <br>- Check for leaks (smell)

Plant Rooms (Level 2) Sprinkler Valve Room, Fire Control Room, Main Switch Room, MDF - P2 Driveway

  • Main Switch Room (Left Door P2 Entry)<br>- EP & T equipment <br> - Check powered and operational<br> - Check for Faults <br>- Power Factor Correction (PFC)<br> - Check powered and operational <br> - Check percentage value & if fluctuations are present (Same as B1)<br><br>NOTES / PHOTOS AS NECESSARY

  • Fire Control Room - Fire Panel<br>- Check for Faults and fully functioning<br> - Note Isolations<br>- 1x Photo of Fire Panel & Time taken

  • Fire Control Room - EWIS<br>- Check for Faults and fully functioning<br> - Note Isolations<br>- 1x Photo of EWIS Panel & Time taken

  • MDF<br>- Check free of rubbish

Plant Rooms (Level 1a) B2 Mezzanine level

  • Air Handling Unit / Kitchen Extracts / Toilet Extracts (East, Central & West) <br>- Access from Fire Corridor next to CSD lifts or from P2 L2 lift lobby<br>- Check VSD in AUTO & operational X 6<br>- Check Distribution Panels for faults X 2 <br>- Check room is free of waste & equipment

Tower Plant Rooms (Levels 8-12)

  • Roof Plant Room (L13 Up Fire Exit Stairs) tank and diesel booster pump.<br>- Check for leaks<br>- Check fuel for pump is full and Jerry Can full

  • Air Handling Unit and Toilet Extracts (Level 8 Terrace entry and Level 9-12 West corridor access.<br>- Check operational and VSD is in auto (if fitted) or control panels without faults/alarms.<br>- Check room is free of waste and equipment.

3 - Building 3

Plant Room Level 5 (Rooftop via plant room)

  • Cooling Towers<br>- Check operational including dosing pumps and chemical levels<br>- Check no leaks <br>- Check eyewash station x 2

Plant Room Level 4

  • Air Handling Units and Toilet Extract Fans<br>- Check operational<br>- Check for leaks

  • Compressors x4, 2 next to electrical boards/stairs and 2 in front of boiler room<br>- Check Operational<br>- No leaks

  • Boilers x 2<br>- Visual inspection, no leaks

  • Chillers x2<br>- Check Fault lights on Chillers x2

Basement Plant Rooms

  • Main Switch Room (2 doors opp cardboard compactor)<br>- EP&T equipment powered and operational<br>- Power Factor Correction equipment powered and operational <br>- Check power and % values<br>

  • Gas Intake Room, next to MDF room<br>- Visual/smell check

  • MDF<br>- Check for damage<br>- Check power etc:<br>- Check EWIS panel for faults/isolations<br>- 1x Photo of EWIS panel & Time Taken

  • Sprinkler Valve Room Fire Indicator Panel<br>- Check for faults or alarms on FIP<br>- Note all Isolations

  • Grease Arrestor Room<br>Next to fire control room <br>- Visual Inspection <br>- check pump in manual & operational <br>- check for alarms/ all ok?

5 - Remedial Action

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.