Title Page
-
NOTE: If any recorded results exceed the baseline values by more than ±5% then contact area EQS for advice
-
Account
-
Site conducted
-
Conducted on
-
Prepared by
-
Calibration Date of the Tester (from the calibration Certificate)
-
Multi-Function Tester Serial Number
-
CalCard Serial Number (enter 000 if using NICEIC card)
-
Circuit ID of dedicated socket outlet used for check
Checks using CalCard
-
Continuity Ω
-
Result from MFT using 0.25Ω on the Calcard(0.2 on NICEIC card)
-
Result from MFT using 0.5Ω on the Calcard
-
Result from MFT using 1.0Ω on the Calcard
-
Result from MFT using 2.0Ω on the Calcard
-
Result from MFT using 5.0Ω on the Calcard(enter 0.0 for not tested if using NICEIC Card)
-
Insulation Resistance MΩ
-
Result from MFT using 0.5MΩ on the Calcard
-
Result from MFT using 1.0MΩ on the Calcard
-
Result from MFT using 2.0MΩ on the Calcard
-
Result from MFT using 10.0MΩ on the Calcard
-
Result from MFT using 20.0MΩ on the Calcard(enter 0.0 for not tested if using NICEIC Card)
Checks using dedicated RCD protected socket
-
Earth Fault Loop Impedance (Zs Ω)
-
RCD Disconnection times mS
-
Measured Disconnection time on the MFT at 0º ½xIΔn in mS
-
Measured Disconnection time on the MFT at 180º ½xIΔn in mS
-
Measured Disconnection time on the MFT at 0º 1xIΔn in mS
-
Measured Disconnection time on the MFT at 180º 1xIΔn in mS
-
Measured Disconnection time on the MFT at 0º 5xIΔn in mS
-
Measured Disconnection time on the MFT at 180º 5xIΔn in mS
Confirmation
-
Are all results gained from the MFT today within the ±5% Deviation of the Baseline figures supplied at calibration?
-
Signature of Completion
-
Tick the Box to end