Information

  • Document No.

  • Audit Title

  • Client / Site

  • Conducted on

  • Prepared by

  • Location
  • Personnel

1. Previous Inspection

  • 1.1 Has the previous Life Safety Inspection been reviewed?

  • 1.2 Have previous discrepancies been resolved?

  • 1.3 Do the facility's Life Safety drawing match current conditions?

  • 1.4 Is the facility currently using any waivers provided by CMS?

A1. Fire Doors

  • A1.1. Are fire doors provided with positive latching?

  • A1.2. Is the fire door self-closing or automatic closing?

  • A1.3. Is the gap between fire doors 1/8" or less and the gap between the fire door and the floor 3/4" or less?

  • A1.4. Is the fire door free from decorations, door stops, unprotected penetrations, and non-rated hardware?

  • A1.5. Is the fire door free from damaged hardware?

  • A1.6. Does the fire door and frame each have a label indicating the rating?

  • A1.7. If the rated door has a window, does the window have fire wire and or a fire rated label?

A2. Fire rated walls, ceiling, and floors.

  • A2.1. Are penetrations in rated walls as provided on the facility's life safety drawings properly sealed with fire rated material?

  • A2.2. Are penetrations in floors and ceiling properly sealed with fire rated material?

A3. Fire alarm and sprinkler systems.

  • A3.1. Does the fire alarm panel have a smoke detector above it?

  • A3.2. Does the fire alarm panel show all systems normal?

  • A3.3. Have all discrepancies found in the annual fire alarm report been corrected and or repaired?

  • A3.4. Are there any escutcheon plates missing from existing sprinkler heads?

  • A3.5. Where quick response type sprinkler heads are being used are all heads within the compartment of the quick response type?

  • A3.6. Have all discrepancies found during the annual sprinkler inspection report been corrected and or repaired?

  • A3.7. Is sprinkler protection provided throughout the compartment?

A4. Rooms

  • A4.1. Are waiting areas open to the corridor < 600 sqft, with smoke detection, and arranged to not obstruct exit access?

  • A4.2. In all patient sleeping rooms >1000 sqft are there two remotely located exit access doors?

  • A4.3. Are exit access doors < 100 ft from any point in patient sleeping rooms?

  • A4.4. Is the travel distance from any point in a sleeping suite to an exit < 200 ft?

  • A4.5. Are all soiled linen and trash collection rooms rated at 1 hour?

A5. Corridors

  • A5.1. Is the corridor constructed as to limit the passage of smoke?

  • A5.2. Are all dead-end corridors less than 30 ft?

  • A5.3. Is there a minimum of 48" of clear width where serving as a means of egress from patient sleeping rooms?

  • A5.4. Are projections into the corridor < 6"?

  • A5.5. Where fixed furniture is located in a corridor that is a minimum of 8ft are all 8 requirements met per section 19.2.3.4(5), LSC 101, 2012 Edition?

A6. General

  • A6.1. Are exit signs properly illuminated?

  • A6.2. Is there adequate exit signage?

  • A6.3. Are pull stations, exit signs, exit doors, notification appliances, extinguishers, and any other life safety systems component obstructed?

  • A6.4. Are fire extinguishers tagged appropriately and within annual certification and with monthly checks?

  • A6.5. Are all stored materials a minimum of 18" from the sprinkler head?

  • A6.6. Is the area free from signs of smoking?

  • A6.7. Are electrical panels unobstructed and locked with a minimum storage free space of 30"?

A7. Documentation

  • A7.1. After meeting with the facility's Engineering Manager have you confirmed that all Life Safety/EC documentation is up-to-date and being recorded appropriately?

Signatures:

  • Facility Engineering Manager

  • Life Safety Compliance Specialist

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.