Title Page
-
Location:
-
Conducted on:
-
Council reference number:
-
Pool/Spa construction date:
-
Prepared by:
-
Supervisor & registration number:
-
Owners name & contact info:
Type of pool/spa
-
Type
-
Type of pool/spa
-
Inground or above ground
2.1 General
-
Barrier & gate must be a permanent structure, made from durable material.
2.3.1 fencing height
-
Barrier height not less than 1.2m.
-
NCZ 1.2m radius down from the top of the barrier (outside).
-
Reg147C(C) - If paling fence must be minimum 1.5m high.
2.3.2 Perforated material or mesh
-
Openings in fence not greater than 13mm shall have fence height min 1.2m.
-
(a) Openings in fence greater than 13mm but less than 100mm shall have fence height min 2.4m. OR
-
(b) Openings in fence greater than 13mm but less than 100mm with a cranked top shall have a height not less than 1.8m.
2.4 Retaining wall or other such barrier (on high side of pool)
-
(a) Minimum 2.4m high (& in accordance with Clause 2.6)
-
(b) Does NOT slope more than 15⁰
2.4 Retaining wall or other such barrier (on low side of pool)
-
(c) Minimum 1.2m high (& in accordance with Clause 2.6) OR
-
(d) Minimum 2.4m high (if not compliant with Clause 2.6)
-
Does NOT slope more than 15⁰
2.5 Ground clearance
-
Gap between ground and barrier no greater than 100mm.
2.6 Outside surface
-
If projections or indentation greater than 10mm they must be no less than 900mm spaced apart.
-
Any lower indentations or projections to be minimum 1.1m from top of barrier
-
Ignore projections/indentations if horizontal members have minimum 60⁰ splay
-
If fence specifically designed to lean towards pool - must NOT slope more than 15⁰
2.7 Horizontal climbable members [includes boundary fence. Outside of pool area]
-
(a) Horizontal members shall be no less than 900mm apart if vertical openings are greater than 10mm.
-
(b) Fences with rails - top surface of lower rail shall be no less than 1.1m below the top of the fence.
2.8 Horizontal non-climbable members
-
(a) horizontal members not complying with 2.7 have 60⁰ splay &
-
(b) Vertical members spaced no more than 10mm apart.
2.9 Horizontal surfaces inside the fencing
-
300mm deep NCZ maintained within the pool area, unless vertical openings no more than 10mm wide.
2.10 Vertical members
-
Openings no greater than 100mm.
2.11.1 & 147C (b)
-
Gate swings away from pool area.
147D - requirements for doors or gates (A.K.A. child resistant doorsets)
-
(a) self-latching device installed
-
(b) opening mechanism minimum 1.5m high
-
(c) Self-closing device fitted - self-closing device will close the gate from any open position without manual force.
147E windows in walls used as barriers
-
(a) not less than 2.4m above ground level of pool area; or
-
(b) not less than 1.5m above the floor level of the room containing the window; or
-
(c) not openable more than 125mm; or
-
(d) have securely fitted fly screen/mesh of adequate strength.
2.11.3.1 Latching device
-
Automatically operate on the closing of the gate.
-
Cannot be re-opened without manual release.
-
The latch shall not be able to:<br>• inadvertently be adjusted during operation;<br>• locked in the ‘open’ position; or<br>• adjusted without the use of tools.
2.11.3.2 Location of latch (if lower than 1.5m)
-
(a) On the inside of the barrier;
-
(b) Access to the latch must be in a position to reach over or through the barrier no lower than 1.2m above FFL OR,<br>Not less than 1.1m above the highest lower rail.
-
(c) At least 150mm below the top of barrier or hand-hole.
2.11.3.3 Shielding of latch (when latch is below 1.5m)
-
No opening greater than 10mm within 450mm of latch
Security of closure - when gate is closed and latched it can’t be:
-
lifted to release the latch OR,
-
unhinge the gate OR,
-
increase the gap underneath greater than 100mm.
2.15 Above-ground pools
-
Pool sides acting as the barrier if height is not less than 1.2m.
-
Must comply with 2.3, 2.6, 2.7 & 2.8.
2.16 Balcony balustrades where balcony floor level is less than 2.4m above NGL of pool area
-
The balcony balustrade must comply as a pool/spa barrier. OR
-
The window/s & door/s must comply with Clause 2.13 & 2.14. (child resistant window & child resistant doorset).
Reg 147ZF - circumstances in which a certificate of barrier NON-compliance must be issued immediately
-
Is the barrier incapable of being made compliant within 60 days?
-
Is the owner unlikely to bring the barrier into compliance within 60 days?
-
Does the non-compliance pose a significant risk to life or safety?
-
Can to gate/doorset be open without operating the latch?
-
Is the gate/doorset unable to be closed completely?
-
Is any part of the barrier less than 1m in height?
-
If the answer is yes to any of these questions, then a Form 24 must be issued immediately.
Compliance
-
Is Pool Safety Barrier compliant with the applicable standard to allow for a Form 23 - Certificate of Compliance to be issued. OR
-
If non-compliant, will you instead issue the owner a list setting out the non-compliant items, giving the owner maximum 60 days in which to bring the Pool Safety Barrier into compliance with the applicable standard.
-
Note. Inspector must advise owner of their intention to carry out a reinspection specifying a date not more than 60 days after the owner receives the notice.
-