Title Page
-
Project number
-
Location
-
Conducted on
-
Prepared by
-
Today's solar power generation
-
This month's power generation so far
-
Total generation so far
-
Inverter Front Photo
-
Meter/Switch Board Photo
On the Ground
-
Label - PV DP / PV SW / PV AC - Round Green Label
-
Label - PV (Solar) Site Information - Diagram
-
Label - Main Switch - Grid Supply
-
Label - Main Switch - Inverter Supply
-
Label - Shutdown Procedure
-
Label - 'Solar' on solar conduit every 2 meters
-
Other Labels
-
Voltage @MPPT1
-
Voltage @MPPT2
-
Voltage @MPPT3
-
Voltage@MPPT4
-
Any LV Cables have been found to be damaged?
-
Are Isc and Voc ratings calculated correctly as per AS/NZS5033:2021 Clause 4.2.?
-
Has double insulation been maintained on all cables as per the AS/NZS 3000:2018?
-
Does the clearance around the inverter meet the manufacturer’s minimum requirements?
-
Is the inverter securely and safely installed with all fixing/locking screws present?
-
Are MC4 connections tight and secure?
-
Has correct size AC cable been used?
-
Has the correct size CB been used?
-
Has ECD been installed correctly?
-
Has the unprotected DC cabel kept less than 300mm at the inverter?
-
If the isolator enclosure is mounted outdoors, are cables entering from the bottom?
-
Has neutral cable been terminated independently and marked correctly?
Roof Cavity
-
Label - Manhole DC Voltage Warning
-
Label - 'Solar' on solar conduit every 2 meters
-
Are all cables/wiring securely fixed in place to minimise <br>any movement of the cable?
-
Are all DC cable(s) enclosed in heavy-duty conduit or equivalent?
-
Is solar conduit fixed 600mm above the roof ceiling?
On the Roof
-
Label - PV String Disconnection Point - on Panel Frame
-
Label - PV String warning - on +ve and -ve cable of string
-
Are all cables/wiring securely fixed in place to minimise any movement of the cable?
-
Stainless Steel cable ties are used as necessary?
-
Are the roof/wall penetrations/holes suitably installed, sealed and waterproof?
-
Is the array wiring protected from UV/mechanical damage? <br>
-
Is the compliant DC cable has been used as per the AS/NZS 5033:2021?
-
Are all rails earthed and earth connections are zinc sprayed?
-
Have panels exclusion zones been maintained?
-
Are all DC cable(s) enclosed in heavy-duty conduit or equivalent?
-
Any DC cable touching the roof?
-
Are DC connectors (MC4) mated with those of the same type from the same manufacturer as required?
-
Are MC4 connections tight and secure?