Title Page
-
Site conducted
-
Conducted on
-
Prepared by
-
Location
-
Work Order
Untitled Page
(T)ools, (S)afety Equipment and (M)aterials
-
Mechanic's toolset
-
Flashlight
Safety Guidelines
-
Schedule work with operating personnel
-
Check with operating personnel for deficiencies
-
Follow site safety rules and your supervisor's instructions
-
Obtain and review manufacturer's instructions
-
Report any problems you find
-
Record the results in the equipment history log
-
Verify proper signal at FACP
Maintenance Procedures
-
Check pressure gauges located on the supply side and system side of the dry valve. Verify that the proper ratio of air pressure to water supply pressure is being maintained
-
Verify that the intermediate chamber of the dry valve is free of water. No water should flow from the drip check when the plunger is pushed
-
Verify that there is no air coming out of the 1/2” outlet of the PORV
-
If equipped with a Viking accelerator: Check the air pressure gauge located on the top of the accelerator. Air pressure in the upper chamber of the accelerator should equal the pneumatic pressure maintained in the system.
-
Check for signs of mechanical damage and/or corrosive activity. If detected, perform maintenance as required or, if necessary, replace the device
-
Verify that the dry valve and trim are adequately heated and protected from freezing and physical damage
-
Confirm that all valves are in their normal operating positions
-
Perform a water flow alarm test
-
Notify the authority having jurisdiction and those in the area affected by the test
-
To test the local electric alarm (if provided) and/or mechanical water motor gong (if provided); OPEN the alarm test valve in the dry valve trim. The electric alarm pressure switches should activate. Electric local alarms should be audible. The local
-
When testing is complete, close the alarm test valve
-
Verify that all local alarms stop sounding, and alarm panels (if provided) reset. Verify that all remote station alarms reset. Verify that all supply piping to water motor properly drain
-
Verify that the alarm test valve is CLOSED
-
Verify that the intermediate chamber of the dry valve is free of water. No water should flow from the drip check when the plunger is pushed.
-
Perform a main drain test
-
Notify the authority having jurisdiction and those in the area affected by the test
-
Record the pressure reading from the water supply pressure gauge
-
Verify that the intermediate chamber of the dry valve is free of water. No water should flow from the drip check when the plunger is pushed.
-
Verify that there is no air coming out of the 1/2” outlet of the PORV
-
Verify that the dry pipe system is pressurized at or above the minimum pressure recommended in Table 2 for the water supply pressure available
-
Fully OPEN the main drain valve located on the base of the dry valve
-
When a full flow develops from the main drain, record the residual pressure from the water supply pressure gauge
-
When the test is complete, SLOWLY CLOSE the main drain
-
Compare the test results with previous flow information. If deterioration of the water supply is detected, take appropriate steps to restore adequate water supply
-
Verify that normal water supply pressure and system pneumatic pressure have been restored, and that all alarm devices and valves are secured in normal operating position.
-
Perform a low air alarm test
-
Close the water supply main control valve supplying the dry valve
-
Close the priming valve
-
Open the flow test valve (located on the inlet of the dry valve)
-
If the dry valve being tested is equipped with a Viking Model E-1 Accelerator, performing step 6 of this test will cause the accelerator to operate. A burst of air from the vent in the bottom of the<br>accelerator will indicate operation of the accelerator.
-
Verify that the water supply main control valve is closed, and the flow test valve is open. Gradually and record the pressure at which the low air alarm op
-
Close the main drain valve
-
Place the valve in service in accordance with the manufacturer's instructions
-
Wipe down the unit
-
Verify that the water supply main control valve is open, and all other valves are in their normal operating position
-
Record and/or provide notification of test results
Maintenance Hours
-
Time spent on work order?