What document is this?
-
Equipment No. (Item being tested)
-
Equipment Type<br>(Item being tested)
-
Conducted on
-
Prepared by
-
EDL - Asset No.
-
PAT Tester - Uni-T UT528
Serial No. 816002795 -
What is equipment type, and serial no?
-
Is the Test device in Calibration?
-
Confirm Date
-
Record date **/**/****
-
Stop Test and report device out of calibration.
Pat Test
-
Visually Check all equipment for damage and defects
-
Stop test - fit "Do not use" label to equipment and isolate.
-
What Class is this?
-
Is there a separate PSU?<br>(Brick PSU or similar)
-
The device will be Class 3
Remember the separate PSU is Class 1 or 2 (Plastic cased), this & the AC lead will need identifying and testing -
Is there a double box symbol on ratings label?
-
It is a Class 2 device
-
It is a Class 1 device.
Full Pat test if metal cased
Just insulation resistance test if plastic cased -
Does it have metal case?
-
Earth Bond (Ω)<br>Limit 0.1Ω
-
Insulation Resistance (> 2MΩ) <br>Greater than 2MΩ
-
Earth Leakage Current(mA)<br>Limits (< = Less than)<br>IT, Movable, stationary, fixed = <3.5mA<br>Heating and cooking = <0.75mA<br>Other = <0.25mA
-
Insulation Resistance (> 2MΩ) <br>Greater than 2MΩ
-
Where is equipment located?
-
Next re-test date is one year from today
-
Next re-test date is 2 years from today
-
Insulation Resistance (> 2MΩ) <br>Greater than 2MΩ
-
Run Power cable test.
-
What Fuse is fitted?
-
Record value (**A) or brief reason why unable to see Fuse
-
Where is equipment located?
-
Next Re-test date is 2 years from today
-
Next Re-test date is 4 years from today
-
Next Re-test date is 3 years from today.
-
Where is equipment located?
-
Next Re-test is due two years from today
-
Next Re-test date is three years from today
-
Next Re-test is four years from today
-
Write next inspection date on to label and fit to the equipment
-
This is a low voltage device, so a visual inspection is all that can be done.
-
Pat Test (Pass or Fail)?<br>Any fails above this point create a fail here.
-
Stop test - fit "Do not use" label to equipment and isolate.
DO NOT COMPLETE INSPECTION -
Signature