Information

  • Document No.

  • Audit Title

  • Client / Site

  • Conducted on

  • Prepared by

  • Location
  • Personnel

  • Inspection competed by Andrew Stanton unless stated otherwise

All Areas

  • Sprinkler clearance - Area within 500mm of the level of the sprinklers clear. That is no shelving in the zone. 1000mm if there is high piled combustible stock such as hung garments (double rung), stacked boxes, plastics (e.g. Toys and electrical appliances.

  • Dangerous Goods - No quantities of flammable gas/liquid or other dangerous goods are held which have NOT been reported to Centre Management.

  • Add photos if non compliant

Store Rooms

  • Sprinkler Configuration - Is there a sprinkler head in the storeroom

  • Add photos if non compliant

Food cooking tenancies using oil/grease

  • Fire Extinguisher - Class F extinguisher is available.

  • Class F Fire Extinguisher available mounted on wall with:<br>Base 100mm minimum from the floor<br>Top 1200mm minimum from the floor<br>2 metres minimum from risk (cooking area) <br>Sign located above extinguisher 2000mm minimum from floor

  • Fire Extinguisher Service<br>Periodical inspection tag/label current <br>Figure "1" indicates 6 monthly check<br>Figure "2" indicates monthly check<br>Figure "3" indicates a 5 yearly check

  • Kitchen Exhaust Clean<br>No excessive build up of grease on filters or surfaces.

  • Fire Blanket - available

  • Photograph compliant blanket and extinguisher

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.