Title Page
-
Site
-
Location of Inspection
-
Prepared by
-
Conducted on
-
Personnel
Requirements
-
Are the latest revision of Jessella Details and Elevation drawings on site and being followed?
-
Are the latest revisions of Rockwool Installation Manuals on site and being followed?
-
Has the Installation Method been read and understood by all operatives?
Rockwool SP120 Vertical Cavity Barrier
-
Have the Cavity Barriers been cut to the correct cavity depth?
-
Have the Cavity Barriers been installed using the correct brackets and fixings?
-
Have the Cavity Barriers been installed fully, uninterrupted by the Horizontal Barriers?
-
Are the Cavity Barriers installed tightly abutted to each other?
-
Are their at least 2 fixings per Cavity Barrier?
-
Does the Cavity Barrier stand proud of the Vertical Rail by at least 45mm?
Rockwool OSCB44 Horizontal Fire Barrier
-
Have the Cavity Barriers been cut to the correct cavity depth?
-
Does the Cavity Barrier sit 25mm behind the Vertical Rail?
-
Have the Cavity Barriers been installed using the correct brackets and fixings?
-
Do the Cavity Barriers abut tightly to each other and to the Vertical Barriers?
-
Are their at least 2 fixings per Cavity Barrier?
-
Have Rockwool Pigtails been installed to the face of the Cavity Barrier and protrude out at least 25mm?
Rockwool 100mm Duoslab
-
Have the Insulation Slabs been installed using the correct fixings?
-
Have the Insulation Slabs been installed in a 'brick' style?
-
Have the Insulation Slabs been installed tightly abutted to each other and Cavity Barriers?
Aluminium Framing
-
Have the Aluminium C-Channels been installed using the correct fixings and following setting out drawings?
-
Have the Helping Hand Brackets been installed using the correct fixings and following setting out drawings?
-
Have the Aluminium Vertical Rails been installed using the correct fixings and following the setting out drawings?
-
Have the Aluminium Rails been installed plumb?
-
Have the Aluminium Rails been installed to allow for deflection?
-
Have the Aluminium 'Z' Carrier Rails been installed using the correct fixings and following the setting out drawings?
-
Has a section of OSCB Intumescent Strip been installed to the front of the Carrier Rail at Vertical Fire Barrier Locations?
Matrix SF Aluminium Cassettes
-
Has the Framing, Insulation and Cavity Barriers been inspected and signed off?
-
Have Anti-Rattle Clips been installed?
-
Has the gap in between the top hat sections to the rear of the panel been filled with intumescent silicone?
-
Have the Cassette Panels been fully engaged into the Carrier Rails?
-
Have the Cassette Panels been secured at the top with the correct fixings?
Site alterations
-
Are there any site alterations?
Drawings
-
Relevant drawings
Comments
-
Are there any comments?
Sign off
-
The below signatures deem all Jessella works mentioned In this report complete to drawings and handed over to Barratt London.
-
Checked on behalf of Jessella
-
Checked on behalf of Client