  • HV REMEDIAL MAINTENANCE REPORT

INSPECTION DETAILS

  • DATE OF INSPECTION

  • NAME OF PERSON CONDUCTING MAINTENANCE

  • NAME OF FACILITY

  • LOCATION OF MAINTENANCE - ROOM NUMBER

SCOPE SUMMARY

  • CHECKED AND ADJUSTED DAMPERS IN Tx PROTECTION CB

  • CLEANED AND REMOVED ALL OLD GREASE FROM MOVING PARTS IN THE ISOLATORS, EARTH SWITCHES AND PROTECTION CIRCUIT BREAKER. REGREASED ALL MOVING MECHANICAL PARTS

  • CHECKED AND CLEANED ALL LV AND HV TERMINATIONS IN THE RMU AND Tx.

  • INSTALLED EARTH COLOUR CODING ON THE DRAINS AND SHIELDS OF THE HV CABLES AT THE RMU END

  • VACUUMED AND WIPED CLEAN ALL CUBICLES OF DUST AND REINSTATED COVERS

  • NEW TEMPERATURE CONTROLLER AND PT100 THERMISTORS INSTALLED AND COMMISSIONED.

FORWARD SWITCHING

  • RECORD LOW VOLTAGE CHANGEOVER TIME

  • WERE THERE ANY ABNORMALITIES WITH THE FORWARD HV SWITCHING?

  • PLEASE PROVIDE MORE DETAIL

MAINTENANCE TASKS

RMU ISOLATORS AND EARTH SWITCHES

    RMU ISOLATOR
  • WHAT IS THE ISOLATOR DESIGNATION?

  • REMOVE ANY OLD GREASE

  • CONFIRM ALL ACCESSIBLE FASTENERS ARE FIRMLY TIGHTENED

  • GREASE MOVING PARTS/AREAS OF FRICTION WITH LITHIUM GREASE

  • CHECK ELECTRICAL CONNECTIONS (PLUGS/TERMINATIONS ETC)

  • INSPECT ALL CABLES/ELECTRICAL CONNECTORS FOR MECHANICAL DAMAGE.

  • IS THERE A SPRING CHARGE MOTOR

  • SPRING CHARGE MOTOR

SPRING CHARGE MOTOR

  • VERIFY SPRING CHARGE MOTOR IS OPERATIONAL AND MOVES FREELY - MANUALLY CHARGE SPRING, OPERATE AND CHECK FOR RESISTANCE OF MOVEMENT

  • MANUALLY OPERATE USING BREAK ARM AND CHECK FOR RESISTANCE TO MOVEMENT.

  • CHECK FUNCTION OF LIMIT SWITCHES AND VERIFY CONDITION

  • WERE THERE ANY ABNORMALITIES IDENTIFIED WHILST SERVICING THIS ISOLATOR?

  • PROVIDE FURTHER DETAILS

  • PROVIDE PHOTOS

  • RMU EARTH SWITCH
  • WHAT IS THE EARTH SWITCH DESIGNATION?

  • REMOVE ANY OLD GREASE

  • CONFIRM ALL ACCESSIBLE FASTENERS ARE FIRMLY TIGHTENED

  • GREASE MOVING PARTS/AREAS OF FRICTION WITH LITHIUM GREASE

  • INSPECT ALL CABLES/ELECTRICAL CONNECTORS FOR MECHANICAL DAMAGE.

  • CONFIRM EASE OF MOVEMENT OF ALL MECHANICAL PARTS. MANUALLY CLOSE AND OPEN HV EARTH SWITCHES UNDER AP TO CONFIRM MECHANICAL EASE.

  • WERE THERE ANY ABNORMALITIES IDENTIFIED WHILST SERVICING THIS EARTH SWITCH?

  • PROVIDE FURTHER DETAILS

  • PROVIDE PHOTOS

TRANSFORMER PROTECTION CIRCUIT BREAKER

  • WHAT IS THE CIRCUIT BREAKER DESIGNATION?

  • REMOVE ANY OLD GREASE

  • CONFIRM ALL ACCESSIBLE FASTENERS ARE FIRMLY TIGHTENED

  • GREASE MOVING PARTS/AREAS OF FRICTION WITH LITHIUM GREASE

  • CHECK ELECTRICAL CONNECTIONS (PLUGS/TERMINATIONS ETC)

  • INSPECT ALL CABLES/ELECTRICAL CONNECTORS FOR MECHANICAL DAMAGE.

  • INSPECT ALL PARTS FOR SIGNS OF UNUSUAL OR EXCESSIVE WEAR

  • CHECK DAMPER IS CORRECTLY POSITIONED AND SECURED IN PLACE, CLEANED AND GREASED.

  • RECORD CYCLE COUNTER

SPRING CHARGE MOTOR

  • VERIFY SPRING CHARGE MOTOR IS OPERATIONAL AND MOVES FREELY - MANUALLY CHARGE SPRING, OPERATE AND CHECK FOR RESISTANCE OF MOVEMENT

  • MANUALLY OPERATE USING BREAK ARM AND CHECK FOR RESISTANCE TO MOVEMENT.

  • CHECK FUNCTION OF LIMIT SWITCHES AND VERIFY CONDITION

  • WERE THERE ANY ABNORMALITIES IDENTIFIED WHILST SERVICING THIS PROTECTION CIRCUIT BREAKER?

  • PROVIDE FURTHER DETAILS

  • PROVIDE PHOTOS

LV COMPARTMENT

  • VISUALLY INSPECT ALL TERMINATIONS AND CONFIRM THEY ARE TIGHT

  • CONFIRM THAT CONTROL CABINET HAS BEEN CLEANED. VACUUMED AND WIPED.

  • TAKE PHOTO OF SF6 GAS GAUGE

  • INSPECT ALL CABLES AND ELECTRICAL CONNECTORS FOR DAMAGE

  • WERE THERE ANY ABNORMALITIES IDENTIFIED WHILST SERVICING THIS PROTECTION CIRCUIT BREAKER?

  • PROVIDE FURTHER DETAILS

  • PROVIDE PHOTOS

CABLE ZONES

  • THOROUGHLY CLEAN - VACUUM AND WIPE

  • CONFIRM THE COLOUR CODING OF THE HV CABLES SCREENS (YELLOW/GREEN)

  • CONFIRM CABLE CLAMP TIGHTNESS

  • WERE THERE ANY ABNORMALITIES IDENTIFIED WHILST SERVICING THIS PROTECTION CIRCUIT BREAKER?

  • PROVIDE FURTHER DETAILS

  • PROVIDE PHOTOS

COMPLETED FULL TEST OF TEMPERATURE CONTROLLER AND THERMISTOR CHECK, INCLUDING CALIBRATION TO ENSURE THAT FANS, ALARM AND TRIP OCCUR WITHIN TOLERANCES OF AS/NZS 60076-2:2013. REPORT WILL SHOW THAT THE TEMPERATURE CONTROLLER TOLERANCE WAS WITHIN 1%.

  • CONFIRM FANS SWITCH ON AT 50 DEG C

  • CONFIRM THAT CONTROLLER ALARMS AT 60 DEG C

  • CONFIRM TRIP AT 100 DEG C

GENERAL CHECKS

  • TIGHTNESS CHECKS ON ALL Tx HV TERMINALS

  • TIGHTNESS CHECKS ON ALL Tx LV TERMINALS

  • VISUAL INSPECTION IN Tx CAGE ENSURING ALL MATERIALS AND EQUIPMENT REMOVED AND ACCOUNTED FOR

  • MEN CHECK - CONFIRM UPGRADE OF LV MEN TO PARALLEL 120 SQMM CABLES

  • THERMISTOR CHECK - CONFIRM UPGRADE OF THERMISTORS AND CHECK TIGHTNESS OF TERMINATIONS

  • TAKE PHOTO OF UPGRADED MEN

  • TAKE PHOTO SHOWING NEW THERMISTORS

CLEANED TRANSFORMER ROOM

  • HEPA VACUUMED ALL SURFACES WITHIN THE Tx CAGE AND ROOM

  • WIPED DOWN ALL SURFACES IN THE Tx CAGE AND OUTSIDE REMOVING ALL DUST

  • RELAMPED ALL THE LIGHT FITTINGS WITH IN THE ROOM

  • TAKE PHOTO SHOWING CLEANED ROOM

GENERAL COMMENTS

    FURTHER INFORMATION
  • FURTHER INFORMATION

  • ADD FURTHER PHOTOS IF NEEDED

REVERSE SWITCHING

  • RECORD LOW VOLTAGE CHANGEOVER TIME

  • WERE THERE ANY ABNORMALITIES WITH THE REVERSE HV SWITCHING?

  • PLEASE PROVIDE MORE DETAIL

  • END OF AUDIT

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.