Information
Select Campus.
-
Campus
Enter building code. E.g. 170, FMB,101, etc
-
Building Code
Enter equipment room code. E.g. 4046,4004,3036 etc
-
Equipment Room Code
Enter building name. E.g. Animal House 1, Glass House 1
-
Building Name
Enter File Name - 170.PAC1.Jan2013 (Building Code. Asset ID.MonthYYYY)
-
File Name
-
Conducted on
-
Prepared by
Audit
-
First Audit (FA) or On Going Maintenance (OGM)?
Outdoor Unit / (Entire Unit in regards to Evap, PAC's, Etc)
-
Equipment Description
- RAC
- Wall Mounted Split System
- Cassette Split System
- Under Ceiling Split System
- Floor Standing Console Split System
- Ducted Split System
- Package Unit
- Evaporative Cooler
- Evaporative Pre-Cooler
-
Equipment Manufacturer
- Acson
- Airwell
- Apac
- Acson
- Braemer
- Brivis
- Buffalo Trident
- Carrier
- Country Air
- Daikin
- Email Air
- Fan Coil Inc
- Fujitsu
- Hitachi
- Kelvinator
- Kirby
- LG
- Mitsubishi
- Muller
- Panasonic
- Stork Air
- Teco
- Temperzone
- Toshiba
- Trane
- Walker
- York
- Other
-
Enter Manufacturer
-
Equipment Model No.. E.g:MSZGE50VA
-
Equipment Serial No.. E.g:S0001234
-
My Parent Barcode. E.g:651739, Etc (if applicable)
-
My Parent Asset Description. (if applicable)
-
Year of installation
- 1985 or earlier
- 1986
- 1987
- 1988
- 1989
- 1990
- 1991
- 1992
- 1993
- 1994
- 1995
- 1996
- 1997
- 1998
- 1999
- 2000
- 2001
- 2002
- 2003
- 2004
- 2005
- 2006
- 2007
- 2008
- 2009
- 2010
- 2011
- 2012
-
Remaining equipment life (Est.)
-
Refrigerant Type
- R22
- R123
- R134a
- R409a
- R410a
- R404a
- R507
- Other
-
Enter Refrigerant
-
Equipment Location Guide E.g.: Outside catering kitchen, etc
-
Area Served. E.g:Lab 1, Admin Office, etc
-
Overall unit condition rating
-
Photo of equipment. E.g:Include as a minimum images: 1.Casing & coil, 2. Internal, 3. Indoor coil & condensate tray.
-
Are motorised dampers fitted to this equipment?
-
Note any identified OH&S issues
Indoor Units
-
Does this system include remote indoor Units?
-
Quantity of Indoor units
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
Indoor Unit
-
Asset ID (PAC#1, RAC#2, Split 29)
-
Equipment Description
- RAC
- Wall Mounted Split System
- Cassette Split System
- Under Ceiling Split System
- Floor Standing Console Split System
- Ducted Split System
- Package Unit
- Evaporative Cooler
- Evaporative Pre-Cooler
-
Equipment Manufacturer
- Acson
- Airwell
- Apac
- Acson
- Braemer
- Brivis
- Buffalo Trident
- Carrier
- Country Air
- Daikin
- Email Air
- Fan Coil Inc
- Fujitsu
- Hitachi
- Kelvinator
- Kirby
- LG
- Mitsubishi
- Muller
- Panasonic
- Stork Air
- Teco
- Temperzone
- Toshiba
- Trane
- Walker
- York
- Other
-
Enter Manufacturer
-
Equipment Model No.. E.g:MSZGE50VA
-
Equipment Serial No.. E.g:S0001234
-
Equipment Room Code. E.g:4046,4004,3036, etc
-
My Parent Barcode. E.g:651739, Etc
-
My Equipment Barcode. E.g:651750, Etc
-
Year of installation
- 1985 or earlier
- 1986
- 1987
- 1988
- 1989
- 1990
- 1991
- 1992
- 1993
- 1994
- 1995
- 1996
- 1997
- 1998
- 1999
- 2000
- 2001
- 2002
- 2003
- 2004
- 2005
- 2006
- 2007
- 2008
- 2009
- 2010
- 2011
- 2012
-
Remaining equipment life
-
Area Served. E.g:Lab 1, Admin Office, etc
-
Overall unit condition rating
-
Photo of equipment. E.g:Include as a minimum images: 1.Casing & coil, 2. Internal, 3. Indoor coil & condensate tray.
Standard Replaceable Items
-
Are replaceable filters fitted (exclude lint screens)
-
Do the filters require replacement
-
List filter type
- V-form
- Panel
- Bag
- Four Peak
- 3 Pocket
- Other
-
Enter Filter Type
-
Filter Quantity
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
-
Filter Dimensions. E.g:495x495x45, Etc
-
Filter Make & Model#
-
Are fan belts fitted
-
Do the fan belts require replacement
-
Fan belt part number. E.g:SPAX1500, Etc
-
Fan Belt Quantity
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
Maintenance Frequency
-
Select maintenance frequency and equipment type
- RAC - 6 Monthly
- RAC -12 Monthly
- Non Ducted Split - 6 Monthly
- Non Ducted Split - 12 Monthly
- Ducted Split - Monthly
- Ducted Split - 3 Monthly
- Ducted Split - 12 Monthly
- Package Unit - Monthly
- Package Unit - 6 Monthly
- Package Unit - 12 Monthly
- Evap/Pre-Cooler - 6 Monthly
- Evap/Pre-Cooler - 12 Monthly
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Inspect and brush clean the coils as required?
-
Inspect fan blades for cleanliness
-
Clean the drain pan
-
Check all electrical connections are tight and not corroded
-
Oil the fan motor as required
-
Check any linkages are free and lubricated
-
Clean the air filter, if required
-
Replace the filter as required (Filter supplied by MU)
-
Check signs of corrosion, report any rust
-
Check the operation of heating and cooling
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Check unit for undue noise, vibration and corrosion
-
Inspect and brush clean the coils as required?
-
Inspect fan blades for cleanliness
-
Clean the drain pan
-
Check all electrical connections are tight and not corroded
-
Oil the fan motor as required
-
Check any linkages are free and lubricated
-
Clean the air filter, if required
-
Replace the filter as required (Filter supplied by MU)
-
Check signs of corrosion, report any rust
-
Check the operation of heating and cooling
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
Check unit for undue noise, vibration
-
Check the liquid line sight glasses, the flow should be clear of vapour bubbles
-
Check the compressor oil sump heater is operating, the sump casing should be warm to touch
-
Check the compressor oil sump glass for correct oil level (if fitted), it should be approximately half full
-
Check for any oil leaks
-
Check all grilles and ensure they are clean and free of obstruction
-
Check condition of filters, clean as required
-
Check operation and leak test refrigeration system, report any faults, repair if authorised.
-
Check condition of indoor and outdoor coils, brush off surface dust
-
Check and record suction and discharge pressures
-
Suction Pressure (kPa)
-
Discharge pressure (kPa)
-
Check expansion device for the correct operation
-
Check the electrical system, tighten connections. Seek authorisation for any remedial work
-
Check the compressor, pressure safety touts, adjust if necessary
-
Check heat pump defrost system operation (during cool weather only)
-
Check all fans and motor bearing, grease as required
-
Ensure all guards and safety features are correctly fitted
-
Ensure that the drip trays and drains are clean and allow condensate to drain away. Clean condensate trays as required
-
Check operation of condensate pumps if installed
-
Check condition of condenser fan blades and mounts
-
Ensure all access panels are secured correctly, note any faulty clips/ screws
-
Check signs of corrosion, report any rust
-
Check wall/ remote controller for correct settings and current time as applicable
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
Check unit for undue noise, vibration
-
Check the liquid line sight glasses, the flow should be clear of vapour bubbles
-
Check the compressor oil sump heater is operating, the sump casing should be warm to touch.
-
Check the compressor oil sump glass for correct oil level (if fitted) it should be approximately half full
-
Check for any oil leaks
-
Check condition of filters, clean as required
-
Check operation and leak test refrigeration system, report any faults, repair if authorised.
-
Check condition of indoor and outdoor coils, brush off surface dust
-
Check and record suction and discharge pressures
-
Suction Pressure (kPa)
-
Discharge pressure (kPa)
-
Check expansion device for the correct operation
-
Check the electrical system, tighten connections. Seek authorisation for any remedial work
-
Check the compressor, pressure safety touts, adjust if necessary
-
Check heat pump defrost system operation (during cool weather only)
-
Check all fans and motor bearing, grease as required
-
Ensure all guards and safety features are correctly fitted
-
Ensure that the drip trays and drains are clean and allow condensate to drain away. Clean condensate trays as required
-
Check operation of condensate pumps if installed
-
Check condition of condenser fan blades and mounts
-
Ensure all access panels are secured correctly, note any faulty clips/ screws
-
Check signs of corrosion, report any rust
-
Check wall/ remote controller for correct settings and current time as applicable
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes
-
Check intake louvres for corrosion and damage
-
Check and clean insect screens, replace if damaged (authorisation required)
-
AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow
-
Check filter integrity , filter sealing, and any signs of filter deterioration
-
If disposable media, record pressure reading across filter bank if access is available
-
E.g. 150pa, etc.
-
HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>
-
COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.
-
Check for any leaks in the coils or associated pipework and controls
-
Ensure the correct operation of the controls
-
Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)
-
CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary
-
CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required
-
Check Vee belt - Tension if required
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes
-
Check intake louvres for corrosion and damage
-
Check and clean insect screens, replace if damaged (authorisation required)
-
AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow
-
Check filter integrity , filter sealing, and any signs of filter deterioration
-
If disposable media, record pressure reading across filter bank if access is available
-
E.g. 150pa, etc.
-
HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>
-
COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.
-
Check for any leaks in the coils or associated pipework and controls
-
Ensure the correct operation of the controls
-
Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)
-
CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary
-
CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required
-
Check the unit for unusual noise and vibration.
-
Check the fan belts, adjust or replace if authorised.
-
Check the liquid line sight glasses, the flow should be clear of vapour bubbles.
-
Check the compressor oil sump heater is operating, the sump casing should be warm to touch.
-
Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.
-
Check for any oil leaks.
-
Check the cabinet and flexible duct connections, for air leaks.
-
Check condition of filters, clean if authorised or report condition.
-
Check operation of and leak test refrigeration system, report any faults, repair if authorised.
-
Check evaporator coil is clean.
-
Check and record suction and discharge pressures
-
Suction Pressure (kPa)
-
Discharge pressure (kPa)
-
Check the expansion Devices for the correct operation.
-
Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.
-
Check the compressor, pressure safety cutouts, adjust if necessary.
-
Check heat pump defrost system operation (during cool weather only)
-
Check all fan and motor bearings, grease as required.
-
Ensure all guards and safety features are correctly fitted.
-
Check operation of condensate pumps if installed.
-
Check condition of condenser fan blades and mounts.
-
Check all electric motor and fan bearings for noise and overheating.
-
Check return air and spill air damper operation via enthalpy/temperature control (if fitted).
-
Lubricate damper bearings with a silicone lubricant spray as required.
-
Ensure all access panels are secured correctly, note any faulty clips/screws.
-
Check signs of corrosion, report any rust
-
Check operation of temperature and associated controls
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes
-
Check intake louvres for corrosion and damage
-
Check and clean insect screens, replace if damaged (authorisation required)
-
Air outlets and terminal units (cushion boxes) - components inspected annually, and cleaned where necessary. Cleaning at the Client's cost.
-
Return and exhaust grilles - - - inspected annually, and cleaned where necessary. Cleaning at the Client's cost.
-
Record the number of Supply Air Diffusers inspected.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
-
Record the number of Return Air Diffusers inspected.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
-
Record the number of Exhaust Air Diffusers inspected.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
-
State the condition of Grilles etc. and make recommendations.
-
AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow
-
Check filter integrity , filter sealing, and any signs of filter deterioration
-
If disposable media, record pressure reading across filter bank if access is available
-
E.g. 150pa, etc.
-
HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>
-
COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.
-
Check for any leaks in the coils or associated pipework and controls
-
Ensure the correct operation of the controls
-
Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)
-
CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary
-
CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required
-
Check the unit for unusual noise and vibration.
-
Check the fan belts, adjust or replace if authorised.
-
Check the liquid line sight glasses, the flow should be clear of vapour bubbles.
-
Check the compressor oil sump heater is operating, the sump casing should be warm to touch.
-
Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.
-
Check for any oil leaks.
-
Check the cabinet and flexible duct connections, for air leaks.
-
Check supply and return air duct for loose internal insulation
-
Check operation of and leak test refrigeration system, report any faults, repair if authorised.
-
Check and record suction and discharge pressures
-
Suction Pressure (kPa)
-
Discharge pressure (kPa)
-
Check the expansion Devices for the correct operation.
-
Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.
-
Check the compressor, pressure safety cutouts, adjust if necessary.
-
Check heat pump defrost system operation (during cool weather only)
-
Check all fan and motor bearings, grease as required.
-
Ensure all guards and safety features are correctly fitted.
-
Check operation of condensate pumps if installed.
-
Check condition of condenser fan blades and mounts.
-
Check all electric motor and fan bearings for noise and overheating.
-
Check return air and spill air damper operation via enthalpy/temperature control (if fitted).
-
Lubricate damper bearings with a silicone lubricant spray as required.
-
Check barometric dampers open freely
-
Ensure all access panels are secured correctly, note any faulty clips/screws.
-
Check signs of corrosion, report any rust
-
Check operation of temperature and associated controls
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes
-
Check intake louvres for corrosion and damage
-
Check and clean insect screens, replace if damaged (authorisation required)
-
AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow
-
Check filter integrity , filter sealing, and any signs of filter deterioration
-
If disposable media, record pressure reading across filter bank if access is available
-
E.g. 150pa, etc.
-
HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>
-
COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.
-
Check for any leaks in the coils or associated pipework and controls
-
Ensure the correct operation of the controls
-
Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)
-
CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary
-
CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required
-
Check Vee belt - Tension if required
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes
-
Check intake louvres for corrosion and damage
-
Check and clean insect screens, replace if damaged (authorisation required)
-
AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow
-
Check filter integrity , filter sealing, and any signs of filter deterioration
-
If disposable media, record pressure reading across filter bank if access is available
-
E.g. 150pa, etc.
-
HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>
-
COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.
-
Check for any leaks in the coils or associated pipework and controls
-
Ensure the correct operation of the controls
-
Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)
-
CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary
-
CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required
-
Check the unit for unusual noise and vibration.
-
Check the fan belts, adjust or replace if authorised.
-
Check the liquid line sight glasses, the flow should be clear of vapour bubbles.
-
Check the compressor oil sump heater is operating, the sump casing should be warm to touch.
-
Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.
-
Check for any oil leaks.
-
Check the cabinet and flexible duct connections, for air leaks.
-
Check operation of and leak test refrigeration system, report any faults, repair if authorised.
-
Check and record suction and discharge pressures
-
Suction Pressure (kPa)
-
Discharge pressure (kPa)
-
Check the expansion Devices for the correct operation.
-
Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.
-
Check the compressor, pressure safety cutouts, adjust if necessary.
-
Check heat pump defrost system operation (during cool weather only)
-
Check all fan and motor bearings, grease as required.
-
Ensure all guards and safety features are correctly fitted.
-
Check operation of condensate pumps if installed.
-
Check condition of condenser fan blades and mounts.
-
Check all electric motor and fan bearings for noise and overheating.
-
Check return air and spill air damper operation via enthalpy/temperature control (if fitted).
-
Lubricate damper bearings with a silicone lubricant spray as required.
-
Ensure all access panels are secured correctly, note any faulty clips/screws.
-
Check signs of corrosion, report any rust
-
Check operation of temperature and associated controls
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes
-
Check intake louvres for corrosion and damage
-
Check and clean insect screens, replace if damaged (authorisation required)
-
Air outlets and terminal units (cushion boxes) - components inspected annually, and cleaned where necessary. Cleaning at the Client's cost.
-
Return and exhaust grilles - - - inspected annually, and cleaned where necessary. Cleaning at the Client's cost.
-
Record the number of Supply Air Diffusers inspected.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
-
Record the number of Return Air Diffusers inspected.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
-
Record the number of Exhaust Air Diffusers inspected.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
-
State the condition of Grilles etc. and make recommendations.
-
AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow
-
Check filter integrity , filter sealing, and any signs of filter deterioration
-
If disposable media, record pressure reading across filter bank if access is available
-
E.g. 150pa, etc.
-
HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>
-
COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.
-
Check for any leaks in the coils or associated pipework and controls
-
Ensure the correct operation of the controls
-
Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)
-
CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary
-
CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required
-
Check the unit for unusual noise and vibration.
-
Check the fan belts, adjust or replace if authorised.
-
Check the liquid line sight glasses, the flow should be clear of vapour bubbles.
-
Check the compressor oil sump heater is operating, the sump casing should be warm to touch.
-
Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.
-
Check for any oil leaks.
-
Check the cabinet and flexible duct connections, for air leaks.
-
Check supply and return air duct for loose internal insulation
-
Check operation of and leak test refrigeration system, report any faults, repair if authorised.
-
Check and record suction and discharge pressures
-
Suction Pressure (kPa)
-
Discharge pressure (kPa)
-
Check the expansion Devices for the correct operation.
-
Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.
-
Check the compressor, pressure safety cutouts, adjust if necessary.
-
Check heat pump defrost system operation (during cool weather only)
-
Check all fan and motor bearings, grease as required.
-
Ensure all guards and safety features are correctly fitted.
-
Check operation of condensate pumps if installed.
-
Check condition of condenser fan blades and mounts.
-
Check all electric motor and fan bearings for noise and overheating.
-
Check return air and spill air damper operation via enthalpy/temperature control (if fitted).
-
Lubricate damper bearings with a silicone lubricant spray as required.
-
Check barometric dampers open freely
-
Ensure all access panels are secured correctly, note any faulty clips/screws.
-
Check signs of corrosion, report any rust
-
Check operation of temperature and associated controls
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Clean evaporative cooler basin pan, pads, fans and housing
-
Ensure the bleedoff is operating correctly
-
If auto dump solenoid is installed, test operation
-
Report on wetted pad condition
-
Clean water strainer, replace if necessary (authorisation required)
-
Flush and clean drainage system
-
Check Fan and Motor operation, lubricate bearings as required.
-
Check fan drive and belt assembly, adjust eve belt as required
-
Test pump operation and confirm water distribution is adequate
-
Install Bromine tablet to basin to aid Microbial Control
-
Report on Evap' cooler basin pan condition
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Clean evaporative cooler basin pan, pads, fans and housing
-
Ensure the bleedoff is operating correctly
-
If auto dump solenoid is installed, test operation
-
Report on wetted pad condition
-
Clean water strainer, replace if necessary (authorisation required)
-
Flush and clean drainage system
-
Check Fan and Motor operation, lubricate bearings as required.
-
Check fan drive and belt assembly, adjust eve belt as required
-
Test pump operation and confirm water distribution is adequate
-
Install Bromine tablet to basin to aid Microbial Control
-
Report on Evap' cooler basin pan condition
-
Inspect the cabinet and repair minor corrosion
-
Check all the electrical connections are tight and free of corrosion
Info required during "On Going Maintenance"
Outdoor Units (in case of: Evap Coolers, PAC's, - this is the entire unit)
-
Equipment Description
- RAC
- Wall Mounted Split System
- Cassette Split System
- Under Ceiling Split System
- Floor Standing Console Split System
- Ducted Split System
- Package Unit
- Evaporative Cooler
- Evaporative Pre-Cooler
-
My Equipment Barcode. E.g:651739, Etc
Indoor Units
-
Does this system include remote indoor Units?
Indoor Unit
-
Equipment Description
- RAC
- Wall Mounted Split System
- Cassette Split System
- Under Ceiling Split System
- Floor Standing Console Split System
- Ducted Split System
- Package Unit
- Evaporative Cooler
- Evaporative Pre-Cooler
-
My Equipment Barcode. E.g:651739, Etc
-
Quantity of Indoor units
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
Standard Replaceable Items
-
Are replaceable filters fitted (exclude lint screens)
-
Do the filters require replacement
-
Are fan belts fitted
-
Do the fan belts require replacement
Maintenance Frequency
-
Select maintenance frequency and equipment type
- RAC - 6 Monthly
- RAC -12 Monthly
- Non Ducted Split - 6 Monthly
- Non Ducted Split - 12 Monthly
- Ducted Split - Monthly
- Ducted Split - 3 Monthly
- Ducted Split - 12 Monthly
- Package Unit - Monthly
- Package Unit - 6 Monthly
- Package Unit - 12 Monthly
- Evap/Pre-Cooler - 6 Monthly
- Evap/Pre-Cooler - 12 Monthly
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Inspect and brush clean the coils as required?
-
Inspect fan blades for cleanliness
-
Clean the drain pan
-
Check all electrical connections are tight and not corroded
-
Oil the fan motor as required
-
Check any linkages are free and lubricated
-
Clean the air filter, if required
-
Replace the filter as required (Filter supplied by MU)
-
Check signs of corrosion, report any rust
-
Check the operation of heating and cooling
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Check unit for undue noise, vibration and corrosion
-
Inspect and brush clean the coils as required?
-
Inspect fan blades for cleanliness
-
Clean the drain pan
-
Check all electrical connections are tight and not corroded
-
Oil the fan motor as required
-
Check any linkages are free and lubricated
-
Clean the air filter, if required
-
Replace the filter as required (Filter supplied by MU)
-
Check signs of corrosion, report any rust
-
Check the operation of heating and cooling
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
Check unit for undue noise, vibration
-
Check the liquid line sight glasses, the flow should be clear of vapour bubbles
-
Check the compressor oil sump heater is operating, the sump casing should be warm to touch
-
Check the compressor oil sump glass for correct oil level (if fitted), it should be approximately half full
-
Check for any oil leaks
-
Check all grilles and ensure they are clean and free of obstruction
-
Check condition of filters, clean as required
-
Check operation and leak test refrigeration system, report any faults, repair if authorised.
-
Check condition of indoor and outdoor coils, brush off surface dust
-
Check and record suction and discharge pressures
-
Suction Pressure (kPa)
-
Discharge pressure (kPa)
-
Check expansion device for the correct operation
-
Check the electrical system, tighten connections. Seek authorisation for any remedial work
-
Check the compressor, pressure safety touts, adjust if necessary
-
Check heat pump defrost system operation (during cool weather only)
-
Check all fans and motor bearing, grease as required
-
Ensure all guards and safety features are correctly fitted
-
Ensure that the drip trays and drains are clean and allow condensate to drain away. Clean condensate trays as required
-
Check operation of condensate pumps if installed
-
Check condition of condenser fan blades and mounts
-
Ensure all access panels are secured correctly, note any faulty clips/ screws
-
Check signs of corrosion, report any rust
-
Check wall/ remote controller for correct settings and current time as applicable
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
Check unit for undue noise, vibration
-
Check the liquid line sight glasses, the flow should be clear of vapour bubbles
-
Check the compressor oil sump heater is operating, the sump casing should be warm to touch.
-
Check the compressor oil sump glass for correct oil level (if fitted) it should be approximately half full
-
Check for any oil leaks
-
Check condition of filters, clean as required
-
Check operation and leak test refrigeration system, report any faults, repair if authorised.
-
Check condition of indoor and outdoor coils, brush off surface dust
-
Check and record suction and discharge pressures
-
Suction Pressure (kPa)
-
Discharge pressure (kPa)
-
Check expansion device for the correct operation
-
Check the electrical system, tighten connections. Seek authorisation for any remedial work
-
Check the compressor, pressure safety touts, adjust if necessary
-
Check heat pump defrost system operation (during cool weather only)
-
Check all fans and motor bearing, grease as required
-
Ensure all guards and safety features are correctly fitted
-
Ensure that the drip trays and drains are clean and allow condensate to drain away. Clean condensate trays as required
-
Check operation of condensate pumps if installed
-
Check condition of condenser fan blades and mounts
-
Ensure all access panels are secured correctly, note any faulty clips/ screws
-
Check signs of corrosion, report any rust
-
Check wall/ remote controller for correct settings and current time as applicable
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes
-
Check intake louvres for corrosion and damage
-
Check and clean insect screens, replace if damaged (authorisation required)
-
AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow
-
Check filter integrity , filter sealing, and any signs of filter deterioration
-
If disposable media, record pressure reading across filter bank if access is available
-
E.g. 150pa, etc.
-
HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>
-
COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.
-
Check for any leaks in the coils or associated pipework and controls
-
Ensure the correct operation of the controls
-
Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)
-
CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary
-
CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required
-
Check Vee belt - Tension if required
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes
-
Check intake louvres for corrosion and damage
-
Check and clean insect screens, replace if damaged (authorisation required)
-
AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow
-
Check filter integrity , filter sealing, and any signs of filter deterioration
-
If disposable media, record pressure reading across filter bank if access is available
-
E.g. 150pa, etc.
-
HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>
-
COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.
-
Check for any leaks in the coils or associated pipework and controls
-
Ensure the correct operation of the controls
-
Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)
-
CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary
-
CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required
-
Check the unit for unusual noise and vibration.
-
Check the fan belts, adjust or replace if authorised.
-
Check the liquid line sight glasses, the flow should be clear of vapour bubbles.
-
Check the compressor oil sump heater is operating, the sump casing should be warm to touch.
-
Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.
-
Check for any oil leaks.
-
Check the cabinet and flexible duct connections, for air leaks.
-
Check condition of filters, clean if authorised or report condition.
-
Check operation of and leak test refrigeration system, report any faults, repair if authorised.
-
Check evaporator coil is clean.
-
Check and record suction and discharge pressures
-
Suction Pressure (kPa)
-
Discharge pressure (kPa)
-
Check the expansion Devices for the correct operation.
-
Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.
-
Check the compressor, pressure safety cutouts, adjust if necessary.
-
Check heat pump defrost system operation (during cool weather only)
-
Check all fan and motor bearings, grease as required.
-
Ensure all guards and safety features are correctly fitted.
-
Check operation of condensate pumps if installed.
-
Check condition of condenser fan blades and mounts.
-
Check all electric motor and fan bearings for noise and overheating.
-
Check return air and spill air damper operation via enthalpy/temperature control (if fitted).
-
Lubricate damper bearings with a silicone lubricant spray as required.
-
Ensure all access panels are secured correctly, note any faulty clips/screws.
-
Check signs of corrosion, report any rust
-
Check operation of temperature and associated controls
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes
-
Check intake louvres for corrosion and damage
-
Check and clean insect screens, replace if damaged (authorisation required)
-
Air outlets and terminal units (cushion boxes) - components inspected annually, and cleaned where necessary. Cleaning at the Client's cost.
-
Return and exhaust grilles - - - inspected annually, and cleaned where necessary. Cleaning at the Client's cost.
-
Record the number of Supply Air Diffusers inspected.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
-
Record the number of Return Air Diffusers inspected.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
-
Record the number of Exhaust Air Diffusers inspected.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
-
State the condition of Grilles etc. and make recommendations.
-
AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow
-
Check filter integrity , filter sealing, and any signs of filter deterioration
-
If disposable media, record pressure reading across filter bank if access is available
-
E.g. 150pa, etc.
-
HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>
-
COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.
-
Check for any leaks in the coils or associated pipework and controls
-
Ensure the correct operation of the controls
-
Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)
-
CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary
-
CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required
-
Check the unit for unusual noise and vibration.
-
Check the fan belts, adjust or replace if authorised.
-
Check the liquid line sight glasses, the flow should be clear of vapour bubbles.
-
Check the compressor oil sump heater is operating, the sump casing should be warm to touch.
-
Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.
-
Check for any oil leaks.
-
Check the cabinet and flexible duct connections, for air leaks.
-
Check supply and return air duct for loose internal insulation
-
Check operation of and leak test refrigeration system, report any faults, repair if authorised.
-
Check and record suction and discharge pressures
-
Suction Pressure (kPa)
-
Discharge pressure (kPa)
-
Check the expansion Devices for the correct operation.
-
Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.
-
Check the compressor, pressure safety cutouts, adjust if necessary.
-
Check heat pump defrost system operation (during cool weather only)
-
Check all fan and motor bearings, grease as required.
-
Ensure all guards and safety features are correctly fitted.
-
Check operation of condensate pumps if installed.
-
Check condition of condenser fan blades and mounts.
-
Check all electric motor and fan bearings for noise and overheating.
-
Check return air and spill air damper operation via enthalpy/temperature control (if fitted).
-
Lubricate damper bearings with a silicone lubricant spray as required.
-
Check barometric dampers open freely
-
Ensure all access panels are secured correctly, note any faulty clips/screws.
-
Check signs of corrosion, report any rust
-
Check operation of temperature and associated controls
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes
-
Check intake louvres for corrosion and damage
-
Check and clean insect screens, replace if damaged (authorisation required)
-
AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow
-
Check filter integrity , filter sealing, and any signs of filter deterioration
-
If disposable media, record pressure reading across filter bank if access is available
-
E.g. 150pa, etc.
-
HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>
-
COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.
-
Check for any leaks in the coils or associated pipework and controls
-
Ensure the correct operation of the controls
-
Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)
-
CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary
-
CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required
-
Check Vee belt - Tension if required
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes
-
Check intake louvres for corrosion and damage
-
Check and clean insect screens, replace if damaged (authorisation required)
-
AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow
-
Check filter integrity , filter sealing, and any signs of filter deterioration
-
If disposable media, record pressure reading across filter bank if access is available
-
E.g. 150pa, etc.
-
HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>
-
COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.
-
Check for any leaks in the coils or associated pipework and controls
-
Ensure the correct operation of the controls
-
Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)
-
CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary
-
CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required
-
Check the unit for unusual noise and vibration.
-
Check the fan belts, adjust or replace if authorised.
-
Check the liquid line sight glasses, the flow should be clear of vapour bubbles.
-
Check the compressor oil sump heater is operating, the sump casing should be warm to touch.
-
Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.
-
Check for any oil leaks.
-
Check the cabinet and flexible duct connections, for air leaks.
-
Check operation of and leak test refrigeration system, report any faults, repair if authorised.
-
Check and record suction and discharge pressures
-
Suction Pressure (kPa)
-
Discharge pressure (kPa)
-
Check the expansion Devices for the correct operation.
-
Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.
-
Check the compressor, pressure safety cutouts, adjust if necessary.
-
Check heat pump defrost system operation (during cool weather only)
-
Check all fan and motor bearings, grease as required.
-
Ensure all guards and safety features are correctly fitted.
-
Check operation of condensate pumps if installed.
-
Check condition of condenser fan blades and mounts.
-
Check all electric motor and fan bearings for noise and overheating.
-
Check return air and spill air damper operation via enthalpy/temperature control (if fitted).
-
Lubricate damper bearings with a silicone lubricant spray as required.
-
Ensure all access panels are secured correctly, note any faulty clips/screws.
-
Check signs of corrosion, report any rust
-
Check operation of temperature and associated controls
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Confirm outdoor unit has local isolation switch
-
AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes
-
Check intake louvres for corrosion and damage
-
Check and clean insect screens, replace if damaged (authorisation required)
-
Air outlets and terminal units (cushion boxes) - components inspected annually, and cleaned where necessary. Cleaning at the Client's cost.
-
Return and exhaust grilles - - - inspected annually, and cleaned where necessary. Cleaning at the Client's cost.
-
Record the number of Supply Air Diffusers inspected.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
-
Record the number of Return Air Diffusers inspected.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
-
Record the number of Exhaust Air Diffusers inspected.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- 13
- 14
- 15
- 16
-
State the condition of Grilles etc. and make recommendations.
-
AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow
-
Check filter integrity , filter sealing, and any signs of filter deterioration
-
If disposable media, record pressure reading across filter bank if access is available
-
E.g. 150pa, etc.
-
HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>
-
COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.
-
Check for any leaks in the coils or associated pipework and controls
-
Ensure the correct operation of the controls
-
Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)
-
CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary
-
CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required
-
Check the unit for unusual noise and vibration.
-
Check the fan belts, adjust or replace if authorised.
-
Check the liquid line sight glasses, the flow should be clear of vapour bubbles.
-
Check the compressor oil sump heater is operating, the sump casing should be warm to touch.
-
Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.
-
Check for any oil leaks.
-
Check the cabinet and flexible duct connections, for air leaks.
-
Check supply and return air duct for loose internal insulation
-
Check operation of and leak test refrigeration system, report any faults, repair if authorised.
-
Check and record suction and discharge pressures
-
Suction Pressure (kPa)
-
Discharge pressure (kPa)
-
Check the expansion Devices for the correct operation.
-
Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.
-
Check the compressor, pressure safety cutouts, adjust if necessary.
-
Check heat pump defrost system operation (during cool weather only)
-
Check all fan and motor bearings, grease as required.
-
Ensure all guards and safety features are correctly fitted.
-
Check operation of condensate pumps if installed.
-
Check condition of condenser fan blades and mounts.
-
Check all electric motor and fan bearings for noise and overheating.
-
Check return air and spill air damper operation via enthalpy/temperature control (if fitted).
-
Lubricate damper bearings with a silicone lubricant spray as required.
-
Check barometric dampers open freely
-
Ensure all access panels are secured correctly, note any faulty clips/screws.
-
Check signs of corrosion, report any rust
-
Check operation of temperature and associated controls
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Clean evaporative cooler basin pan, pads, fans and housing
-
Ensure the bleedoff is operating correctly
-
If auto dump solenoid is installed, test operation
-
Report on wetted pad condition
-
Clean water strainer, replace if necessary (authorisation required)
-
Flush and clean drainage system
-
Check Fan and Motor operation, lubricate bearings as required.
-
Check fan drive and belt assembly, adjust eve belt as required
-
Test pump operation and confirm water distribution is adequate
-
Install Bromine tablet to basin to aid Microbial Control
-
Report on Evap' cooler basin pan condition
Maintenance Tasks
-
Inspect unit mounting is secure?
-
Clean evaporative cooler basin pan, pads, fans and housing
-
Ensure the bleedoff is operating correctly
-
If auto dump solenoid is installed, test operation
-
Report on wetted pad condition
-
Clean water strainer, replace if necessary (authorisation required)
-
Flush and clean drainage system
-
Check Fan and Motor operation, lubricate bearings as required.
-
Check fan drive and belt assembly, adjust eve belt as required
-
Test pump operation and confirm water distribution is adequate
-
Install Bromine tablet to basin to aid Microbial Control
-
Report on Evap' cooler basin pan condition
-
Inspect the cabinet and repair minor corrosion
-
Check all the electrical connections are tight and free of corrosion
Comments
-
General Comments
Sign Off
-
Audit Completed by