Information

Select Campus.

  • Campus

Enter building code. E.g. 170, FMB,101, etc

  • Building Code

Enter equipment room code. E.g. 4046,4004,3036 etc

  • Equipment Room Code

Enter building name. E.g. Animal House 1, Glass House 1

  • Building Name

Enter File Name - 170.PAC1.Jan2013 (Building Code. Asset ID.MonthYYYY)

  • File Name

  • Conducted on

  • Prepared by

Audit

  • First Audit (FA) or On Going Maintenance (OGM)?

Outdoor Unit / (Entire Unit in regards to Evap, PAC's, Etc)

  • Equipment Description

  • Equipment Manufacturer

  • Enter Manufacturer

  • Equipment Model No.. E.g:MSZGE50VA

  • Equipment Serial No.. E.g:S0001234

  • My Parent Barcode. E.g:651739, Etc (if applicable)

  • My Parent Asset Description. (if applicable)

  • Year of installation

  • Remaining equipment life (Est.)

  • Refrigerant Type

  • Enter Refrigerant

  • Equipment Location Guide E.g.: Outside catering kitchen, etc

  • Area Served. E.g:Lab 1, Admin Office, etc

  • Overall unit condition rating

  • Photo of equipment. E.g:Include as a minimum images: 1.Casing & coil, 2. Internal, 3. Indoor coil & condensate tray.

  • Are motorised dampers fitted to this equipment?

  • Note any identified OH&S issues

Indoor Units

  • Does this system include remote indoor Units?

  • Quantity of Indoor units

  • Indoor Unit
  • Asset ID (PAC#1, RAC#2, Split 29)

  • Equipment Description

  • Equipment Manufacturer

  • Enter Manufacturer

  • Equipment Model No.. E.g:MSZGE50VA

  • Equipment Serial No.. E.g:S0001234

  • Equipment Room Code. E.g:4046,4004,3036, etc

  • My Parent Barcode. E.g:651739, Etc

  • My Equipment Barcode. E.g:651750, Etc

  • Year of installation

  • Remaining equipment life

  • Area Served. E.g:Lab 1, Admin Office, etc

  • Overall unit condition rating

  • Photo of equipment. E.g:Include as a minimum images: 1.Casing & coil, 2. Internal, 3. Indoor coil & condensate tray.

Standard Replaceable Items

  • Are replaceable filters fitted (exclude lint screens)

  • Do the filters require replacement

  • List filter type

  • Enter Filter Type

  • Filter Quantity

  • Filter Dimensions. E.g:495x495x45, Etc

  • Filter Make & Model#

  • Are fan belts fitted

  • Do the fan belts require replacement

  • Fan belt part number. E.g:SPAX1500, Etc

  • Fan Belt Quantity

Maintenance Frequency

  • Select maintenance frequency and equipment type

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Inspect and brush clean the coils as required?

  • Inspect fan blades for cleanliness

  • Clean the drain pan

  • Check all electrical connections are tight and not corroded

  • Oil the fan motor as required

  • Check any linkages are free and lubricated

  • Clean the air filter, if required

  • Replace the filter as required (Filter supplied by MU)

  • Check signs of corrosion, report any rust

  • Check the operation of heating and cooling

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Check unit for undue noise, vibration and corrosion

  • Inspect and brush clean the coils as required?

  • Inspect fan blades for cleanliness

  • Clean the drain pan

  • Check all electrical connections are tight and not corroded

  • Oil the fan motor as required

  • Check any linkages are free and lubricated

  • Clean the air filter, if required

  • Replace the filter as required (Filter supplied by MU)

  • Check signs of corrosion, report any rust

  • Check the operation of heating and cooling

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • Check unit for undue noise, vibration

  • Check the liquid line sight glasses, the flow should be clear of vapour bubbles

  • Check the compressor oil sump heater is operating, the sump casing should be warm to touch

  • Check the compressor oil sump glass for correct oil level (if fitted), it should be approximately half full

  • Check for any oil leaks

  • Check all grilles and ensure they are clean and free of obstruction

  • Check condition of filters, clean as required

  • Check operation and leak test refrigeration system, report any faults, repair if authorised.

  • Check condition of indoor and outdoor coils, brush off surface dust

  • Check and record suction and discharge pressures

  • Suction Pressure (kPa)

  • Discharge pressure (kPa)

  • Check expansion device for the correct operation

  • Check the electrical system, tighten connections. Seek authorisation for any remedial work

  • Check the compressor, pressure safety touts, adjust if necessary

  • Check heat pump defrost system operation (during cool weather only)

  • Check all fans and motor bearing, grease as required

  • Ensure all guards and safety features are correctly fitted

  • Ensure that the drip trays and drains are clean and allow condensate to drain away. Clean condensate trays as required

  • Check operation of condensate pumps if installed

  • Check condition of condenser fan blades and mounts

  • Ensure all access panels are secured correctly, note any faulty clips/ screws

  • Check signs of corrosion, report any rust

  • Check wall/ remote controller for correct settings and current time as applicable

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • Check unit for undue noise, vibration

  • Check the liquid line sight glasses, the flow should be clear of vapour bubbles

  • Check the compressor oil sump heater is operating, the sump casing should be warm to touch.

  • Check the compressor oil sump glass for correct oil level (if fitted) it should be approximately half full

  • Check for any oil leaks

  • Check condition of filters, clean as required

  • Check operation and leak test refrigeration system, report any faults, repair if authorised.

  • Check condition of indoor and outdoor coils, brush off surface dust

  • Check and record suction and discharge pressures

  • Suction Pressure (kPa)

  • Discharge pressure (kPa)

  • Check expansion device for the correct operation

  • Check the electrical system, tighten connections. Seek authorisation for any remedial work

  • Check the compressor, pressure safety touts, adjust if necessary

  • Check heat pump defrost system operation (during cool weather only)

  • Check all fans and motor bearing, grease as required

  • Ensure all guards and safety features are correctly fitted

  • Ensure that the drip trays and drains are clean and allow condensate to drain away. Clean condensate trays as required

  • Check operation of condensate pumps if installed

  • Check condition of condenser fan blades and mounts

  • Ensure all access panels are secured correctly, note any faulty clips/ screws

  • Check signs of corrosion, report any rust

  • Check wall/ remote controller for correct settings and current time as applicable

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes

  • Check intake louvres for corrosion and damage

  • Check and clean insect screens, replace if damaged (authorisation required)

  • AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow

  • Check filter integrity , filter sealing, and any signs of filter deterioration

  • If disposable media, record pressure reading across filter bank if access is available

  • E.g. 150pa, etc.

  • HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>

  • COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.

  • Check for any leaks in the coils or associated pipework and controls

  • Ensure the correct operation of the controls

  • Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)

  • CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary

  • CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required

  • Check Vee belt - Tension if required

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes

  • Check intake louvres for corrosion and damage

  • Check and clean insect screens, replace if damaged (authorisation required)

  • AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow

  • Check filter integrity , filter sealing, and any signs of filter deterioration

  • If disposable media, record pressure reading across filter bank if access is available

  • E.g. 150pa, etc.

  • HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>

  • COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.

  • Check for any leaks in the coils or associated pipework and controls

  • Ensure the correct operation of the controls

  • Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)

  • CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary

  • CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required

  • Check the unit for unusual noise and vibration.

  • Check the fan belts, adjust or replace if authorised.

  • Check the liquid line sight glasses, the flow should be clear of vapour bubbles.

  • Check the compressor oil sump heater is operating, the sump casing should be warm to touch.

  • Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.

  • Check for any oil leaks.

  • Check the cabinet and flexible duct connections, for air leaks.

  • Check condition of filters, clean if authorised or report condition.

  • Check operation of and leak test refrigeration system, report any faults, repair if authorised.

  • Check evaporator coil is clean.

  • Check and record suction and discharge pressures

  • Suction Pressure (kPa)

  • Discharge pressure (kPa)

  • Check the expansion Devices for the correct operation.

  • Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.

  • Check the compressor, pressure safety cutouts, adjust if necessary.

  • Check heat pump defrost system operation (during cool weather only)

  • Check all fan and motor bearings, grease as required.

  • Ensure all guards and safety features are correctly fitted.

  • Check operation of condensate pumps if installed.

  • Check condition of condenser fan blades and mounts.

  • Check all electric motor and fan bearings for noise and overheating.

  • Check return air and spill air damper operation via enthalpy/temperature control (if fitted).

  • Lubricate damper bearings with a silicone lubricant spray as required.

  • Ensure all access panels are secured correctly, note any faulty clips/screws.

  • Check signs of corrosion, report any rust

  • Check operation of temperature and associated controls

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes

  • Check intake louvres for corrosion and damage

  • Check and clean insect screens, replace if damaged (authorisation required)

  • Air outlets and terminal units (cushion boxes) - components inspected annually, and cleaned where necessary. Cleaning at the Client's cost.

  • Return and exhaust grilles - - - inspected annually, and cleaned where necessary. Cleaning at the Client's cost.

  • Record the number of Supply Air Diffusers inspected.

  • Record the number of Return Air Diffusers inspected.

  • Record the number of Exhaust Air Diffusers inspected.

  • State the condition of Grilles etc. and make recommendations.

  • AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow

  • Check filter integrity , filter sealing, and any signs of filter deterioration

  • If disposable media, record pressure reading across filter bank if access is available

  • E.g. 150pa, etc.

  • HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>

  • COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.

  • Check for any leaks in the coils or associated pipework and controls

  • Ensure the correct operation of the controls

  • Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)

  • CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary

  • CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required

  • Check the unit for unusual noise and vibration.

  • Check the fan belts, adjust or replace if authorised.

  • Check the liquid line sight glasses, the flow should be clear of vapour bubbles.

  • Check the compressor oil sump heater is operating, the sump casing should be warm to touch.

  • Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.

  • Check for any oil leaks.

  • Check the cabinet and flexible duct connections, for air leaks.

  • Check supply and return air duct for loose internal insulation

  • Check operation of and leak test refrigeration system, report any faults, repair if authorised.

  • Check and record suction and discharge pressures

  • Suction Pressure (kPa)

  • Discharge pressure (kPa)

  • Check the expansion Devices for the correct operation.

  • Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.

  • Check the compressor, pressure safety cutouts, adjust if necessary.

  • Check heat pump defrost system operation (during cool weather only)

  • Check all fan and motor bearings, grease as required.

  • Ensure all guards and safety features are correctly fitted.

  • Check operation of condensate pumps if installed.

  • Check condition of condenser fan blades and mounts.

  • Check all electric motor and fan bearings for noise and overheating.

  • Check return air and spill air damper operation via enthalpy/temperature control (if fitted).

  • Lubricate damper bearings with a silicone lubricant spray as required.

  • Check barometric dampers open freely

  • Ensure all access panels are secured correctly, note any faulty clips/screws.

  • Check signs of corrosion, report any rust

  • Check operation of temperature and associated controls

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes

  • Check intake louvres for corrosion and damage

  • Check and clean insect screens, replace if damaged (authorisation required)

  • AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow

  • Check filter integrity , filter sealing, and any signs of filter deterioration

  • If disposable media, record pressure reading across filter bank if access is available

  • E.g. 150pa, etc.

  • HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>

  • COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.

  • Check for any leaks in the coils or associated pipework and controls

  • Ensure the correct operation of the controls

  • Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)

  • CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary

  • CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required

  • Check Vee belt - Tension if required

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes

  • Check intake louvres for corrosion and damage

  • Check and clean insect screens, replace if damaged (authorisation required)

  • AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow

  • Check filter integrity , filter sealing, and any signs of filter deterioration

  • If disposable media, record pressure reading across filter bank if access is available

  • E.g. 150pa, etc.

  • HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>

  • COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.

  • Check for any leaks in the coils or associated pipework and controls

  • Ensure the correct operation of the controls

  • Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)

  • CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary

  • CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required

  • Check the unit for unusual noise and vibration.

  • Check the fan belts, adjust or replace if authorised.

  • Check the liquid line sight glasses, the flow should be clear of vapour bubbles.

  • Check the compressor oil sump heater is operating, the sump casing should be warm to touch.

  • Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.

  • Check for any oil leaks.

  • Check the cabinet and flexible duct connections, for air leaks.

  • Check operation of and leak test refrigeration system, report any faults, repair if authorised.

  • Check and record suction and discharge pressures

  • Suction Pressure (kPa)

  • Discharge pressure (kPa)

  • Check the expansion Devices for the correct operation.

  • Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.

  • Check the compressor, pressure safety cutouts, adjust if necessary.

  • Check heat pump defrost system operation (during cool weather only)

  • Check all fan and motor bearings, grease as required.

  • Ensure all guards and safety features are correctly fitted.

  • Check operation of condensate pumps if installed.

  • Check condition of condenser fan blades and mounts.

  • Check all electric motor and fan bearings for noise and overheating.

  • Check return air and spill air damper operation via enthalpy/temperature control (if fitted).

  • Lubricate damper bearings with a silicone lubricant spray as required.

  • Ensure all access panels are secured correctly, note any faulty clips/screws.

  • Check signs of corrosion, report any rust

  • Check operation of temperature and associated controls

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes

  • Check intake louvres for corrosion and damage

  • Check and clean insect screens, replace if damaged (authorisation required)

  • Air outlets and terminal units (cushion boxes) - components inspected annually, and cleaned where necessary. Cleaning at the Client's cost.

  • Return and exhaust grilles - - - inspected annually, and cleaned where necessary. Cleaning at the Client's cost.

  • Record the number of Supply Air Diffusers inspected.

  • Record the number of Return Air Diffusers inspected.

  • Record the number of Exhaust Air Diffusers inspected.

  • State the condition of Grilles etc. and make recommendations.

  • AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow

  • Check filter integrity , filter sealing, and any signs of filter deterioration

  • If disposable media, record pressure reading across filter bank if access is available

  • E.g. 150pa, etc.

  • HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>

  • COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.

  • Check for any leaks in the coils or associated pipework and controls

  • Ensure the correct operation of the controls

  • Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)

  • CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary

  • CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required

  • Check the unit for unusual noise and vibration.

  • Check the fan belts, adjust or replace if authorised.

  • Check the liquid line sight glasses, the flow should be clear of vapour bubbles.

  • Check the compressor oil sump heater is operating, the sump casing should be warm to touch.

  • Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.

  • Check for any oil leaks.

  • Check the cabinet and flexible duct connections, for air leaks.

  • Check supply and return air duct for loose internal insulation

  • Check operation of and leak test refrigeration system, report any faults, repair if authorised.

  • Check and record suction and discharge pressures

  • Suction Pressure (kPa)

  • Discharge pressure (kPa)

  • Check the expansion Devices for the correct operation.

  • Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.

  • Check the compressor, pressure safety cutouts, adjust if necessary.

  • Check heat pump defrost system operation (during cool weather only)

  • Check all fan and motor bearings, grease as required.

  • Ensure all guards and safety features are correctly fitted.

  • Check operation of condensate pumps if installed.

  • Check condition of condenser fan blades and mounts.

  • Check all electric motor and fan bearings for noise and overheating.

  • Check return air and spill air damper operation via enthalpy/temperature control (if fitted).

  • Lubricate damper bearings with a silicone lubricant spray as required.

  • Check barometric dampers open freely

  • Ensure all access panels are secured correctly, note any faulty clips/screws.

  • Check signs of corrosion, report any rust

  • Check operation of temperature and associated controls

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Clean evaporative cooler basin pan, pads, fans and housing

  • Ensure the bleedoff is operating correctly

  • If auto dump solenoid is installed, test operation

  • Report on wetted pad condition

  • Clean water strainer, replace if necessary (authorisation required)

  • Flush and clean drainage system

  • Check Fan and Motor operation, lubricate bearings as required.

  • Check fan drive and belt assembly, adjust eve belt as required

  • Test pump operation and confirm water distribution is adequate

  • Install Bromine tablet to basin to aid Microbial Control

  • Report on Evap' cooler basin pan condition

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Clean evaporative cooler basin pan, pads, fans and housing

  • Ensure the bleedoff is operating correctly

  • If auto dump solenoid is installed, test operation

  • Report on wetted pad condition

  • Clean water strainer, replace if necessary (authorisation required)

  • Flush and clean drainage system

  • Check Fan and Motor operation, lubricate bearings as required.

  • Check fan drive and belt assembly, adjust eve belt as required

  • Test pump operation and confirm water distribution is adequate

  • Install Bromine tablet to basin to aid Microbial Control

  • Report on Evap' cooler basin pan condition

  • Inspect the cabinet and repair minor corrosion

  • Check all the electrical connections are tight and free of corrosion

Info required during "On Going Maintenance"

Outdoor Units (in case of: Evap Coolers, PAC's, - this is the entire unit)

  • Equipment Description

  • My Equipment Barcode. E.g:651739, Etc

Indoor Units

  • Does this system include remote indoor Units?

  • Indoor Unit
  • Equipment Description

  • My Equipment Barcode. E.g:651739, Etc

  • Quantity of Indoor units

Standard Replaceable Items

  • Are replaceable filters fitted (exclude lint screens)

  • Do the filters require replacement

  • Are fan belts fitted

  • Do the fan belts require replacement

Maintenance Frequency

  • Select maintenance frequency and equipment type

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Inspect and brush clean the coils as required?

  • Inspect fan blades for cleanliness

  • Clean the drain pan

  • Check all electrical connections are tight and not corroded

  • Oil the fan motor as required

  • Check any linkages are free and lubricated

  • Clean the air filter, if required

  • Replace the filter as required (Filter supplied by MU)

  • Check signs of corrosion, report any rust

  • Check the operation of heating and cooling

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Check unit for undue noise, vibration and corrosion

  • Inspect and brush clean the coils as required?

  • Inspect fan blades for cleanliness

  • Clean the drain pan

  • Check all electrical connections are tight and not corroded

  • Oil the fan motor as required

  • Check any linkages are free and lubricated

  • Clean the air filter, if required

  • Replace the filter as required (Filter supplied by MU)

  • Check signs of corrosion, report any rust

  • Check the operation of heating and cooling

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • Check unit for undue noise, vibration

  • Check the liquid line sight glasses, the flow should be clear of vapour bubbles

  • Check the compressor oil sump heater is operating, the sump casing should be warm to touch

  • Check the compressor oil sump glass for correct oil level (if fitted), it should be approximately half full

  • Check for any oil leaks

  • Check all grilles and ensure they are clean and free of obstruction

  • Check condition of filters, clean as required

  • Check operation and leak test refrigeration system, report any faults, repair if authorised.

  • Check condition of indoor and outdoor coils, brush off surface dust

  • Check and record suction and discharge pressures

  • Suction Pressure (kPa)

  • Discharge pressure (kPa)

  • Check expansion device for the correct operation

  • Check the electrical system, tighten connections. Seek authorisation for any remedial work

  • Check the compressor, pressure safety touts, adjust if necessary

  • Check heat pump defrost system operation (during cool weather only)

  • Check all fans and motor bearing, grease as required

  • Ensure all guards and safety features are correctly fitted

  • Ensure that the drip trays and drains are clean and allow condensate to drain away. Clean condensate trays as required

  • Check operation of condensate pumps if installed

  • Check condition of condenser fan blades and mounts

  • Ensure all access panels are secured correctly, note any faulty clips/ screws

  • Check signs of corrosion, report any rust

  • Check wall/ remote controller for correct settings and current time as applicable

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • Check unit for undue noise, vibration

  • Check the liquid line sight glasses, the flow should be clear of vapour bubbles

  • Check the compressor oil sump heater is operating, the sump casing should be warm to touch.

  • Check the compressor oil sump glass for correct oil level (if fitted) it should be approximately half full

  • Check for any oil leaks

  • Check condition of filters, clean as required

  • Check operation and leak test refrigeration system, report any faults, repair if authorised.

  • Check condition of indoor and outdoor coils, brush off surface dust

  • Check and record suction and discharge pressures

  • Suction Pressure (kPa)

  • Discharge pressure (kPa)

  • Check expansion device for the correct operation

  • Check the electrical system, tighten connections. Seek authorisation for any remedial work

  • Check the compressor, pressure safety touts, adjust if necessary

  • Check heat pump defrost system operation (during cool weather only)

  • Check all fans and motor bearing, grease as required

  • Ensure all guards and safety features are correctly fitted

  • Ensure that the drip trays and drains are clean and allow condensate to drain away. Clean condensate trays as required

  • Check operation of condensate pumps if installed

  • Check condition of condenser fan blades and mounts

  • Ensure all access panels are secured correctly, note any faulty clips/ screws

  • Check signs of corrosion, report any rust

  • Check wall/ remote controller for correct settings and current time as applicable

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes

  • Check intake louvres for corrosion and damage

  • Check and clean insect screens, replace if damaged (authorisation required)

  • AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow

  • Check filter integrity , filter sealing, and any signs of filter deterioration

  • If disposable media, record pressure reading across filter bank if access is available

  • E.g. 150pa, etc.

  • HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>

  • COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.

  • Check for any leaks in the coils or associated pipework and controls

  • Ensure the correct operation of the controls

  • Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)

  • CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary

  • CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required

  • Check Vee belt - Tension if required

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes

  • Check intake louvres for corrosion and damage

  • Check and clean insect screens, replace if damaged (authorisation required)

  • AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow

  • Check filter integrity , filter sealing, and any signs of filter deterioration

  • If disposable media, record pressure reading across filter bank if access is available

  • E.g. 150pa, etc.

  • HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>

  • COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.

  • Check for any leaks in the coils or associated pipework and controls

  • Ensure the correct operation of the controls

  • Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)

  • CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary

  • CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required

  • Check the unit for unusual noise and vibration.

  • Check the fan belts, adjust or replace if authorised.

  • Check the liquid line sight glasses, the flow should be clear of vapour bubbles.

  • Check the compressor oil sump heater is operating, the sump casing should be warm to touch.

  • Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.

  • Check for any oil leaks.

  • Check the cabinet and flexible duct connections, for air leaks.

  • Check condition of filters, clean if authorised or report condition.

  • Check operation of and leak test refrigeration system, report any faults, repair if authorised.

  • Check evaporator coil is clean.

  • Check and record suction and discharge pressures

  • Suction Pressure (kPa)

  • Discharge pressure (kPa)

  • Check the expansion Devices for the correct operation.

  • Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.

  • Check the compressor, pressure safety cutouts, adjust if necessary.

  • Check heat pump defrost system operation (during cool weather only)

  • Check all fan and motor bearings, grease as required.

  • Ensure all guards and safety features are correctly fitted.

  • Check operation of condensate pumps if installed.

  • Check condition of condenser fan blades and mounts.

  • Check all electric motor and fan bearings for noise and overheating.

  • Check return air and spill air damper operation via enthalpy/temperature control (if fitted).

  • Lubricate damper bearings with a silicone lubricant spray as required.

  • Ensure all access panels are secured correctly, note any faulty clips/screws.

  • Check signs of corrosion, report any rust

  • Check operation of temperature and associated controls

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes

  • Check intake louvres for corrosion and damage

  • Check and clean insect screens, replace if damaged (authorisation required)

  • Air outlets and terminal units (cushion boxes) - components inspected annually, and cleaned where necessary. Cleaning at the Client's cost.

  • Return and exhaust grilles - - - inspected annually, and cleaned where necessary. Cleaning at the Client's cost.

  • Record the number of Supply Air Diffusers inspected.

  • Record the number of Return Air Diffusers inspected.

  • Record the number of Exhaust Air Diffusers inspected.

  • State the condition of Grilles etc. and make recommendations.

  • AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow

  • Check filter integrity , filter sealing, and any signs of filter deterioration

  • If disposable media, record pressure reading across filter bank if access is available

  • E.g. 150pa, etc.

  • HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>

  • COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.

  • Check for any leaks in the coils or associated pipework and controls

  • Ensure the correct operation of the controls

  • Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)

  • CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary

  • CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required

  • Check the unit for unusual noise and vibration.

  • Check the fan belts, adjust or replace if authorised.

  • Check the liquid line sight glasses, the flow should be clear of vapour bubbles.

  • Check the compressor oil sump heater is operating, the sump casing should be warm to touch.

  • Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.

  • Check for any oil leaks.

  • Check the cabinet and flexible duct connections, for air leaks.

  • Check supply and return air duct for loose internal insulation

  • Check operation of and leak test refrigeration system, report any faults, repair if authorised.

  • Check and record suction and discharge pressures

  • Suction Pressure (kPa)

  • Discharge pressure (kPa)

  • Check the expansion Devices for the correct operation.

  • Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.

  • Check the compressor, pressure safety cutouts, adjust if necessary.

  • Check heat pump defrost system operation (during cool weather only)

  • Check all fan and motor bearings, grease as required.

  • Ensure all guards and safety features are correctly fitted.

  • Check operation of condensate pumps if installed.

  • Check condition of condenser fan blades and mounts.

  • Check all electric motor and fan bearings for noise and overheating.

  • Check return air and spill air damper operation via enthalpy/temperature control (if fitted).

  • Lubricate damper bearings with a silicone lubricant spray as required.

  • Check barometric dampers open freely

  • Ensure all access panels are secured correctly, note any faulty clips/screws.

  • Check signs of corrosion, report any rust

  • Check operation of temperature and associated controls

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes

  • Check intake louvres for corrosion and damage

  • Check and clean insect screens, replace if damaged (authorisation required)

  • AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow

  • Check filter integrity , filter sealing, and any signs of filter deterioration

  • If disposable media, record pressure reading across filter bank if access is available

  • E.g. 150pa, etc.

  • HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>

  • COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.

  • Check for any leaks in the coils or associated pipework and controls

  • Ensure the correct operation of the controls

  • Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)

  • CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary

  • CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required

  • Check Vee belt - Tension if required

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes

  • Check intake louvres for corrosion and damage

  • Check and clean insect screens, replace if damaged (authorisation required)

  • AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow

  • Check filter integrity , filter sealing, and any signs of filter deterioration

  • If disposable media, record pressure reading across filter bank if access is available

  • E.g. 150pa, etc.

  • HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>

  • COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.

  • Check for any leaks in the coils or associated pipework and controls

  • Ensure the correct operation of the controls

  • Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)

  • CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary

  • CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required

  • Check the unit for unusual noise and vibration.

  • Check the fan belts, adjust or replace if authorised.

  • Check the liquid line sight glasses, the flow should be clear of vapour bubbles.

  • Check the compressor oil sump heater is operating, the sump casing should be warm to touch.

  • Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.

  • Check for any oil leaks.

  • Check the cabinet and flexible duct connections, for air leaks.

  • Check operation of and leak test refrigeration system, report any faults, repair if authorised.

  • Check and record suction and discharge pressures

  • Suction Pressure (kPa)

  • Discharge pressure (kPa)

  • Check the expansion Devices for the correct operation.

  • Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.

  • Check the compressor, pressure safety cutouts, adjust if necessary.

  • Check heat pump defrost system operation (during cool weather only)

  • Check all fan and motor bearings, grease as required.

  • Ensure all guards and safety features are correctly fitted.

  • Check operation of condensate pumps if installed.

  • Check condition of condenser fan blades and mounts.

  • Check all electric motor and fan bearings for noise and overheating.

  • Check return air and spill air damper operation via enthalpy/temperature control (if fitted).

  • Lubricate damper bearings with a silicone lubricant spray as required.

  • Ensure all access panels are secured correctly, note any faulty clips/screws.

  • Check signs of corrosion, report any rust

  • Check operation of temperature and associated controls

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Confirm outdoor unit has local isolation switch

  • AIR INTAKES AND EXHAUST OUTLETS - Remove any combustible material from the vicinity of the intakes

  • Check intake louvres for corrosion and damage

  • Check and clean insect screens, replace if damaged (authorisation required)

  • Air outlets and terminal units (cushion boxes) - components inspected annually, and cleaned where necessary. Cleaning at the Client's cost.

  • Return and exhaust grilles - - - inspected annually, and cleaned where necessary. Cleaning at the Client's cost.

  • Record the number of Supply Air Diffusers inspected.

  • Record the number of Return Air Diffusers inspected.

  • Record the number of Exhaust Air Diffusers inspected.

  • State the condition of Grilles etc. and make recommendations.

  • AIR FILTERS - Inspect upstream and downstream of the filter and remove any large items obstructing the air flow

  • Check filter integrity , filter sealing, and any signs of filter deterioration

  • If disposable media, record pressure reading across filter bank if access is available

  • E.g. 150pa, etc.

  • HUMIDIFIERS - STEAM AND SPRAY - Inspect and clean where applicable: Line strainers, Valves, Drains, Sparge pipes, Spray nozzles and any components discharging moisture into the air stream<br>

  • COILS - Check the condition of both faces of the coils, please note if any access issues to the coils are present. Brush dust from coils.

  • Check for any leaks in the coils or associated pipework and controls

  • Ensure the correct operation of the controls

  • Inspect the access panels, catches, seals and any duct joints for air leakage. Repair if necessary (authorisation required)

  • CONDENSATE TRAYS AND SUMPS - Inspect trays and sumps, clean as necessary

  • CONDENSATE DRAINS - Check condensate drains, tun dishes and traps for cleanliness and correct operation, flush with liquid as required

  • Check the unit for unusual noise and vibration.

  • Check the fan belts, adjust or replace if authorised.

  • Check the liquid line sight glasses, the flow should be clear of vapour bubbles.

  • Check the compressor oil sump heater is operating, the sump casing should be warm to touch.

  • Check the compressor oil sight glass for correct oil level (if fitted), it should be approximately half full.

  • Check for any oil leaks.

  • Check the cabinet and flexible duct connections, for air leaks.

  • Check supply and return air duct for loose internal insulation

  • Check operation of and leak test refrigeration system, report any faults, repair if authorised.

  • Check and record suction and discharge pressures

  • Suction Pressure (kPa)

  • Discharge pressure (kPa)

  • Check the expansion Devices for the correct operation.

  • Check the electrical system, tighten connections, adjust, if necessary, repair or replace components, if authorised.

  • Check the compressor, pressure safety cutouts, adjust if necessary.

  • Check heat pump defrost system operation (during cool weather only)

  • Check all fan and motor bearings, grease as required.

  • Ensure all guards and safety features are correctly fitted.

  • Check operation of condensate pumps if installed.

  • Check condition of condenser fan blades and mounts.

  • Check all electric motor and fan bearings for noise and overheating.

  • Check return air and spill air damper operation via enthalpy/temperature control (if fitted).

  • Lubricate damper bearings with a silicone lubricant spray as required.

  • Check barometric dampers open freely

  • Ensure all access panels are secured correctly, note any faulty clips/screws.

  • Check signs of corrosion, report any rust

  • Check operation of temperature and associated controls

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Clean evaporative cooler basin pan, pads, fans and housing

  • Ensure the bleedoff is operating correctly

  • If auto dump solenoid is installed, test operation

  • Report on wetted pad condition

  • Clean water strainer, replace if necessary (authorisation required)

  • Flush and clean drainage system

  • Check Fan and Motor operation, lubricate bearings as required.

  • Check fan drive and belt assembly, adjust eve belt as required

  • Test pump operation and confirm water distribution is adequate

  • Install Bromine tablet to basin to aid Microbial Control

  • Report on Evap' cooler basin pan condition

Maintenance Tasks

  • Inspect unit mounting is secure?

  • Clean evaporative cooler basin pan, pads, fans and housing

  • Ensure the bleedoff is operating correctly

  • If auto dump solenoid is installed, test operation

  • Report on wetted pad condition

  • Clean water strainer, replace if necessary (authorisation required)

  • Flush and clean drainage system

  • Check Fan and Motor operation, lubricate bearings as required.

  • Check fan drive and belt assembly, adjust eve belt as required

  • Test pump operation and confirm water distribution is adequate

  • Install Bromine tablet to basin to aid Microbial Control

  • Report on Evap' cooler basin pan condition

  • Inspect the cabinet and repair minor corrosion

  • Check all the electrical connections are tight and free of corrosion

Comments

  • General Comments

Sign Off

  • Audit Completed by

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.