    CIRCUIT BREAKERS, ISOLATORS, EARTH SWITCHES, CTs, VTs, etc
  • Perform TEV Testing

  • Circuit Breaker/Switch Make, Type and Serial Number

  • Check operating handles are present and in good condition

  • Check HV neon indicators and test probes for proving dead

  • Carry out HV End Box Inspection if Isolated

  • Check for oil, gas or compound leaks`

  • Check springs charged where appropriate

  • Check bushing oil levels

  • Check correct engagement of isolators

  • Check for damage and signs of arcing or local heating to insulators, connections and contacts

  • Check pressure gauges and SF6 indicators

  • Check SF6 pressure pump running time and number of operations

  • Check surge arrester connections and diaphragm

  • Check circuit labels, phase plates and locks

  • Check main and earthing connections

  • Report on excessive rust / need for repainting

  • Check mechanism boxes, marshalling kiosks, etc. Check fit of doors and covers, operation of heaters. Check heaters

  • Record no of ops & shots in hand (if applicable)

  • Ensure warning notice fitted in switchrooms with vacuum switchgear

CONTROL AND RELAY PANELS

  • Check for flag operation; log and reset

  • Check voltmeters. ammeters all working

  • Check / replace indication lamps

  • Check healthy trip circuits

  • Check inside for verdigris or dampness

  • Check heaters

BATTERIES

  • Inspect and check operation of battery charger

  • Test Batteries

  • Number of Failed Cells and cell type

LV AC BOARDS

  • Check for local heating / discharge

NERs and NEUTRAL SWITCHGEAR

  • Check for internal debris/dirt

  • Check heater operation (if present)

  • Report missing weather shield (if present)

  • lubricate linkages/hinges

  • Check general condition, correct locks fitted, indicator glasses not cracked, crazed or discoloured, labels fitted and legible etc

  • Report on excessive rust / need for repainting

  • Check earthing

  • Check for oil and compound leaks

TRANSFORMERS, AUXILIARY TRANSFORMERS, REGULATORS, REACTORS

  • Record tapchanger counter readings, write in logbook

  • Recorded in Log book

  • Check tap position indicator indicating correctly, Check off load t/c are locked off

  • Check winding temperature indicators record maximum readings

  • Check oil temperature indicators, record maximum readings

  • Recorded in Log book?

  • Check silica Gel

  • Silica Gel Replaced?

  • Check operation of pumps and fans

  • Check for oil and compound leaks

  • Check transformer, tapchanger and bushing oil levels, transparency of site glasses

  • Check Buchholz for gas accumulation

  • Check insulators or arcing horns for damage, signs of arcing or local heating

  • Check explosion diaphragm, Qualitrols & PRV's for signs of operation

  • If necessary, lift out sump pump assembly, clean probes. Clean debris from pump inlet. Dispose of accumulated oil; investigate source. Check pump working. Check alarms

  • Check bund walls intact and generally free from water

  • Record transformer and feeder MDI & reset

  • Report on excessive rust / need for repainting

  • Check for abnormal levels of noise

CABLE SEALING ENDS

  • Check insulators, oil levels, oil leaks

  • Check general condition including cleating

  • Check earthing

  • Check labelling / phase plates

Thermography

  • Use TIC to check for hotspots on transformer cable connections

  • Use TIC to check for hotspots on Busbar connections

  • Use TIC to check for hotspots on switchgear

SITE

  • Check stored materials do not restrict access or compromise security or safety clearances

  • Complete security inspection. Check walls, fences, windows etc

  • Check for rubbish, weeds, etc.; remove or report

  • Report need for grass cutting

  • Check floodlights

  • Check ditches

BUILDINGS

  • Check operation of all doors (main and emergency). Check secure

  • Check for signs of cracking to brickwork, loose masonry etc

  • Visually check condition of pitched roofs (from ground level), missing tiles, etc

  • Check gutters, downpipes and gulleys

  • Check for water leaks internal to buildings

  • Check any windows for breakages water ingress or security

  • Check lighting (main and emergency)

  • Replace any defective bulbs or tubes

  • Check all heaters are working and the substation environment is adequate

  • Check telephone operates correctly ( if present)

  • Check trench covers and access covers are in place, complete and level. Check for water or vermin infestation

  • Check basements for ingress of water and correct operation of water pump

  • Check plumbing, toilet, wash basins, toilet paper, brush, cleaner, soap, paper towels and water heater. Replace sundries

STEPS AND LADDERS

  • Check tags. Inspect and date if out of date by next inspection

  • Check locked secure

  • Report if missing

GENERAL

  • Danger Label Emergency contact

  • SF6 Label Posted on Entrances

  • Substation Name Fitted on Entrances

  • Electricity at Work Act Sign

  • Resuscitation Poster

  • HV Line Diagram

  • Inspection recorded in site log book?

  • Sign

LV SWITCHGEAR DETAILS

  • Check ACB'S are in good condition

  • Check ACB relays for flag operation

  • Check fuse ways are in good condition with no signs of blown fuses

  • Check for signs of overheating

  • Check LV labelling is correct

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.