Type I hood properly installed where required.<br><br>IFC 609.2- A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors
-
Add media
-
Commercial hood and duct systems protected.<br><br>IFC 904.2.1- Each required commercial kitchen exhaust hood and duct system required by Section 609 to have a Type I hood shall be protected with an approved automatic fire-extinguishing system installed in accordance with this code.
-
Add media
-
Extinguishing system serviced every 6 months.<br><br>IFC 904.11.6.2- Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals and a certificate of inspection shall be forwarded to the fire code official upon completion.
-
Add media
-
System inspections, tests, and maintenance records maintained.<br><br>IFC 901.6.2- Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years, and shall be copied to the fire code official upon request.
-
Add media
-
Manual actuation device located 42"-48"<br><br>IFC 904.11.1- A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet and a maximum of 20 feet from the kitchen exhaust system. Installed not more than 48 inches no less than 42 inches above the floor and shall clearly identify the hazard protected.
-
Add media
-
System interconnected with utilities.<br><br>IFC 904.11.2- The actuation of the fire extinguishing system shall automatically shut down the fuel or electrical power supply to the cooking equipment. The fuel and electrical supply reset shall be manual.
-
Add media
-
Class K rated portable extinguisher available.<br><br>IFC 904.11.5- Portable fire extinguishers shall be provided within a 30-foot travel distance of commercial-type cooking equipment. Cooking equipment involving solid fuels or vegetable or animal oils and fats shall be protected with a Class K rated portable extinguisher.
-
Add media
-
Fusible links and sprinkler heads replaced annually.<br><br>IFC 904.11.6.3- Fusible links and automatic sprinkler heads shall be replaced at least annually, and other protection devices shall be serviced or replaced in accordance with the manufacturer's instructions.
-
Add media
-
Nozzle at the top of the ventilating duct in Carbon Dioxide Systems.<br><br>IFC 904.11.3- Design requirements for nozzle locations, dampers, and ducts for CO2 extinguishing systems used to protect commercial cooking systems.
-
Add media
-
Portable fire extinguishers available.<br><br>IFC 904.11.5- Portable fire extinguishers shall be provided within a 30-foot travel distance of commercial-type cooking systems.
-
Add media