Information

  • Document No.

  • Audit Title

  • Client / Site

  • Building picture from the road / access location

  • Conducted on

  • Prepared by

  • Location
  • Personnel

1. Building Details

  • Building Description

  • Add location

Asset List As Supplied By Client

  • AUTOMATIC FIRE SPRINKLER SYSTEM - AS1851 section 2

  • FIRE PUMPSETS - AS1851 section 3

  • FIRE HYDRANT SYSTEMS - AS1851 section 4

  • WATER STORAGE TANKS FOR FIRE PROTECTION SYSTEMS - AS1851 section 5

  • FIRE DETECTION AND ALARM SYSTEMS - AS1851 section 6

  • SPECIAL HAZARD SYSTEMS - AS1851 section 7

  • DELIVERY LAY FLAT FIRE HOSE - AS1851 section 8

  • FIRE HOSE REELS - AS1851 section 9

  • PORTABLE AND WHEELED FIRE EXTINGUISHERS - AS1851 section 10

  • FIRE BLANKETS - AS1851 section 11

  • PASSIVE FIRE AND SMOKE CONTAINMENT SYSTEMS - AS1851 section 12

2. AUTOMATIC FIRE SPRINKLER SYSTEM - AS1851 section 2

1.1 Fire Safety Equipment Installed

  • Automatic fire suppression (sprinkler).

  • - Automatic sprinkler systems are inspected and tested in accordance with AS 1851 section 2 on a weekly basis

  • - Additionally, a log book is required to be placed at the location of the sprinkler in order for the technician to record the results of each inspection, in accordance with AS 1851 section 2

  • Wall wetting sprinkler and drenched systems

  • - Wall wetting and drenched systems are inspected and tested in accordance with AS 1851 section 2 on a weekly basis

  • AS 1851 section 2.4.7 12 heads or less on a monthly basis

  • Location of Sprinkler System / Systems

  • Picture of valve room

  • Number of Valve Rooms

  • Number of Valve Sets

  • Year of Installation

  • Water Supply

2.6 Documentation

  • - AS 1851.6.2 PROCEDURES AND PRECAUTIONS

  • - Design and installation survey detection systems shall be surveyed on an annual basis in accordance with Clause 6.4.4

  • - C6.2.1 A detection survey is topically conducted visually from floor level and is intended to identify changes to the detection system or the building and it's environment which could impair the performance of the detection system.

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • Is there any evidence of the annual survey being conducted ?

  • Is a block plan securely mounted in the valve room ?p

  • Have any critical defects been recorded in the previous 12 months ?

  • Have any non-critical defects been reported in the previous 12 months ?

3. FIRE PUMPSETS - AS1851 section 3

  • Electric and Diesel Pumps

  • - Fire Hydrant booster pumps are inspected in accordance to AS 1851 section 3 on a weekly basis.

  • - Additionally, in the case of a hydrant booster pump being present, a log book is required in order for the technician to record the results of each weekly inspection, in accordance with maintenance code AS 1851 Section 3.

  • Location of pump room

  • Picture of all pump sets and controls

  • Number of Pumps

  • Year of Installation

  • Water supply

3.1 Six monthly test dates (Previous twelve months)

  • Has the system been tested for the last six months ?

3.2 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

3.3 Five Yearly Test date.

  • Has the system been tested in the last five years ?

  • Select date

3.4 Documentation

  • - AS 1851.6.2 PROCEDURES AND PRECAUTIONS

  • - Design and installation survey detection systems shall be surveyed on an annual basis in accordance with Clause 6.4.4

  • - C6.2.1 A detection survey is topically conducted visually from floor level and is intended to identify changes to the detection system or the building and it's environment which could impair the performance of the detection system.

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • Is a block plan securely mounted in the valve room ?

  • Is there any evidence of the annual survey being conducted ?

  • Have any non-critical defects been reported in the previous 12 months ?

4. FIRE HYDRANT SYSTEMS - AS 1851 section 4

  • Fire Hydrant System

  • - fire hydrants are inspected and tested in accordance with AS 1851 section 4 on a six monthly basis

  • - Every year unassisted flow test is required

  • - Hydrant Boosters, Every year unassisted flow test is required. Every five years an assisted flow test is required

  • Have any critical defects been recorded in the previous 12 months ?

4.1 Six monthly test dates (Previous twelve months)

  • Has the system been tested for the last six months ?

4.2 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

4.3 Five Yearly Test date.

  • Has the system been tested in the last five years ?

  • Select date

4.4 Documentation

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

5. DELIVERY LAY FLAT FIRE HOSE -AS1851 section 5

  • Delivery lay flat hoses are inspected and tested in accordance with AS1851 section 5 on a yearly basis

  • Lay Flat Hoses

5.1 Annual test dates (Previous year)

  • Has the system been tested in the last year ?

  • Select date

5.2 Documentation

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

6. FIRE DETECTION SYSTEMS -AS1851 section 6

  • Automatic fire detection and alarm system

  • Automatic fire detection and alarm systems (panels) are inspected and tested in accordance with AS1670 & AS1851 section 6 on a monthly basis

  • Additionally, a log book is required to be placed at the location of the fire indicator panel in order for the technician to record the results of each inspection, in accordance with AS 1851 section 6.

  • Location of Fire Indicator Panel

  • Picture of FIP / Sub FIP

  • Manufacturer

  • System type

  • Year of installation

  • Local System or Brigade Connected?

  • Provision to alert occupants ?

  • Are there sub indicator panels?

6.1 Monthly test dates (Previous twelve months)

  • Has the system been tested for the last twelve months ?

6.2 Six Monthly test dates (Previous twelve months)

  • Has the system been tested for the last six months ?

6.3 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

6.4 Five yearly test date

  • Has the system been tested for the last five years ?

  • Select date

6.5 Documentation

  • Documentation shall be housed in or adjacent to the FIP without interfering with the system wiring. The following documentation shall be provided upon completion of the commissioning tests: (a) 'As-installed' drawings covering the system or alterations, as applicable. Standard symbols, as given in Appendix D, shall be used. The drawings shall show the following, where applicable (see also Figures D1 and D2, appendix D)

  • - Design and installation survey detection systems shall be surveyed on an annual basis in accordance with Clause 6.4.4

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • - C6.2.1 A detection survey is typically conducted visually from floor level and is intended to identify changes to the detection system or the building and it's environment which could impair the performance of the detection system.

  • Is there any evidence of the annual survey being conducted ?

  • Have any critical defects been recorded in the previous 12 months ?

  • Have any non-critical defects been reported in the previous 12 months ?

  • Is there baseline data available ?

  • Commissioning test report available ?

  • Installers statement in accordance with appendix E of AS 1670.1 available ?

  • Aspirating system design tool calculation available ? (if applicable)

  • Is a zone block plan securely mounted adjacent to the FIP ?

  • AS-Installed drawings available ?

  • Report conclussion including any recommendations.

7. SMOKE ALARMS AND HEAT ALARMS - AS1851 section 7

  • Smoke and heat detectors

  • - Back to panel - Smoke and heat detectors are inspected and tested in accordance with AS 1851 section 7 on a yearly basis.

  • - 240 Volt - Smoke and heat detectors are inspected and tested in accordance with AS1851 section 7 on a six monthly basis.

7.2 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

7.3 Documentation

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • Report conclussion including any recommendations.

8. FIRE ALARM MONITORING SYSTEMS - AS1851 section 8

  • Alarm Monitoring

  • - Alarm Monitoring is inspected and tested in accordance with AS 1851 section 8

8.1 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

8.2 Documentation

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • Report conclussion including any recommendations.

9. SOUND SYSTEMS FOR EMERGENCY PURPOSES - AS1851 section 9

  • Audio Visual Devices

  • - Sound Systems inspected and tested in accordance with AS 1851 section 9

  • Location of Audio visual device

  • Picture of OWS / EWIS

  • Manufacturer

  • System type

  • Year of installation

9.1 Monthly test dates (Previous twelve months)

  • Has the system been tested for the last twelve months ?

9.2 Six Monthly test dates (Previous twelve months)

  • Has the system been tested for the last six months ?

9.3 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

9.4 Documentation

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • Have any critical defects been recorded in the previous 12 months ?

  • Have any non-critical defects been reported in the previous 12 months ?

10. INTERCOM SYSTEMS FOR EMERGENCY PURPOSES - AS1851 section 10

  • Emergency warning and intercommunication system

  • Emergency warning and intercommunication system (EWIS) are tested in accordance with AS 1851 section 10

  • Location of Audio visual device

  • Add media

  • Manufacturer

  • System type

  • Year of installation

10.1 Six Monthly test dates (Previous twelve months)

  • Has the system been tested for the last six months ?

10.2 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

10.3 Documentation

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • Have any critical defects been recorded in the previous 12 months ?

  • Have any non-critical defects been reported in the previous 12 months ?

11. GASEOUG FIRE EXTINGUISHING SYSTEMS - AS 1851 section 11

  • Gas Dump System

  • - Gas fire extinguishing systems are inspected & tested in accordance with AS 1851 section 11 on a monthly basis

  • Location of Gas system

  • Add media

  • Manufacturer

  • System type

  • Year of installation

  • Service Provider Details

11.1 Monthly test dates (Previous twelve months)

  • Has the system been tested for the last twelve months ?

11.2 Six Monthly test dates (Previous twelve months)

  • Has the system been tested for the last six months ?

11.3 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

11.4 Five yearly test date

  • Has the system been tested for the last five years ?

  • Select date

11.5 Documentation

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • Have any critical defects been recorded in the previous 12 months ?

  • Have any non-critical defects been reported in the previous 12 months ?

12. FIXED AEROSOL FIRE EXTINGUISHING SYSTEMS - AS 1851 section 12

  • Aerosol Dump System

  • - Aerosol fire extinguishing systems are inspected & tested in accordance with AS 1851 section 12 on a monthly basis.

  • Location of Aerosol system

  • Add media

  • Manufacturer

  • System type

  • Year of installation

  • Service Provider Details

12.1 Monthly test dates (Previous twelve months)

  • Has the system been tested for the last twelve months ?

12.2 Six Monthly test dates (Previous twelve months)

  • Has the system been tested for the last six months ?

12.3 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

12.4 Five yearly test date

  • Has the system been tested for the last five years ?

  • Select date

12.5 Documentation

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • Have any critical defects been recorded in the previous 12 months ?

  • Have any non-critical defects been reported in the previous 12 months ?

13. OPEN NOZZLE WATER FIRE EXTINGUISHING SYSTEMS - AS 1851 section 13

  • Wet Mist Extinguishing Systems

  • - Wet mist fire extinguishing systems are inspected and tested in accordance with AS 1851 section 13 on a monthly basis

  • Location of Wet Mist System

  • Add media

  • Manufacturer

  • System type

  • Year of installation

  • Service Provider Details

13.1 Monthly test dates (Previous twelve months)

  • Has the system been tested for the last twelve months ?

13.2 Six Monthly test dates (Previous twelve months)

  • Has the system been tested for the last six months ?

13.3 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

13.4 Five yearly test date

  • Has the system been tested for the last five years ?

  • Select date

13.5 Documentation

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • Have any critical defects been recorded in the previous 12 months ?

  • Have any non-critical defects been reported in the previous 12 months ?

14. FIRE HOSE REELS - AS 1851 section 14

  • Fire Hose Reels

  • - Fire Hose Reel systems are inspected and tested in accordance with AS 1851 section 14 on a six monthly basis

  • Has a record of service been completed and left onsite ?

14.1 Six Monthly test dates (Previous twelve months)

  • Has the system been tested for the last six months ?

14.2 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

14.3 Documentation

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • Have any critical defects been recorded in the previous 12 months ?

  • Have any non-critical defects been reported in the previous 12 months ?

15. PORTABLE AND WHEELED FIRE EXTIBGUISHERS - AS 1851 section 15

  • Portable Fire Extinguishers

  • - Portable fire extinguishers are inspected and tested in accordance with AS 1851 section 15 on the six monthly basis

  • - Additionally, five years pressure testing is required, plus recharging when an extinguisher is discharged

  • Has a record of service been completed and left onsite ?

15.1 Six Monthly test dates (Previous twelve months)

  • Has the system been tested for the last six months ?

15.2 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

15.3 Five yearly test date

  • Has the system been tested for the last five years ?

  • Select date

15.4 Documentation

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • Have any critical defects been recorded in the previous 12 months ?

  • Have any non-critical defects been reported in the previous 12 months ?

16. FIRE BLANKETS - AS 1851 section 16

  • Portable fire blankets

  • Has a record of service been completed and left onsite ?

16.1 Six Monthly test dates (Previous twelve months)

  • Has the system been tested for the last six months ?

16.2 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

16.3 Documentation

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • Have any critical defects been recorded in the previous 12 months ?

  • Have any non-critical defects been reported in the previous 12 months ?

17. PASSIVE FIRE AND SMOKE CONTAINMENT SYSTEMS - AS 1851 section 17

  • Fire Dampers

  • - Fire Dampers are inspected and tested in accordance with AS 1851 section 17 on a six monthly basis

  • Fire Doors

  • - Fire Doors are inspected and tested in accordance with AS 1851 section 17 on a three monthly basis

  • Fire Walls and Barriers / Separations

  • - Fire walls barriers are inspected and tested in accordance with AS1851 section 17 on a six monthly basis

17.2 Six Monthly test dates (Previous twelve months)

  • Has the system been tested for the last six months ?

17.3 Annual test dates (Previous year)

  • Has the system been tested for the last twelve months ?

  • Select date

17.4 Documentation

  • Have all tests been completed within the frequency toll arranges set out in AS 1851-2005 section 1 ?

  • Have any non-critical defects been reported in the previous 12 months ?

  • Have any critical defects been recorded in the previous 12 months ?

Notes and Comments

  • Report conclussion including any recommendations.

Sign Off

  • On site representative

  • Auditor's signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.