Safety

  • Any Hazards on site have been added to SWMS spreadsheet & SWMS completed?

80+ SERVICES

Backflow

  • Has the correct Containment Backflow Device been installed as per the specific " Conditions of Connection "?

  • High Hazard ( RPZ ) Backflow Device - Is Vent installed at a min. height of 300mm?

Magflow Meters

  • Is Magflow Meter connected to 240V GPO?

  • Are Bonding Cables attached?

  • Is dial positioned to be easily read?

Meter Assembly Status

  • Is Meter Assembly Complete?

  • Is Meter Assembly under Construction? ( All Components on Site )

  • Is Main Meter located appropriately?

  • Max. Height of Meter Assembly 1.5m.

  • Have gear operated shutoff valves been installed?

  • Are spacer pipes on Fire Service the correct length based on pipe diameter?

Meter Assembly Configuration

  • Are all components of the Water Meter Assembly WaterMark Certified?

  • Note: For Fire Service only components upstream of the " Non Return Device " must be Certified.

  • For SCDAT Assemblies, have bypass isolating valves been locked in open position using 003 Padlocks?

  • Has approved materials been on Fire Booster Assembly?<br>( GWIP not permitted upstream of the Backflow Device )

  • Has Testing Ferrule been Installed & Capped?

  • Have Meter Assembly risers been constructed in Copper?

  • Ensure min. 600mm annular clearance around pipe surround in concrete has been achieved?

  • Are Meter Assembly supports in place?

  • Are Meter Assembly supports adequate?

Check Meters

  • Are Meter Assemblies located in common access areas?

  • Is Meter Assembly within the Approved Tolerance?

  • 150mm min to bottom of proposed meters?

  • 150mm min from any walls?

  • 225mm min vertical spacing between Meters?

  • 1.5m max height of Assemblies?

  • Have Meter Assemblies been constructed in Approved Materials?

  • Where only a Meter Assembly is to be installed is Meter Spacer an Approved Material?

  • Are isolating valves installed to outlet of Check Meter Assemblies?

  • ( Required where damage may result to carpets, etc when removal/exchanging water meters )

  • Have all Check Meters assemblies been appropriately Tagged?

  • Are Check Meters assemblies adequately supported?

  • Itemise which Meter Assemblies have Failed...

Plumber Notified of Audit outcome

  • Verbally?

  • Electronically?

Contractor Agreement

  • Contractor agrees to have Meter Assemblies Items rectified by:

  • Add signature

South East Water's Representative

  • Add signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.