AS/NZS 3012:2010 requirements

Clause 1.2

  • All wiring installed according to AS 3000 Wiring rules in addition to AS3012 requirements.

Clause 2.1.2

  • All electrical equipment and lighting supplied from a 30mA RCD protected circuit

Clause 2.1.3

  • Source of supply identified

Clause 2.3.1.1

  • Switchboard readily accessible

Clause 2.3.2.1 (ab)

  • Switchboard of robust construction with a minimum IP23 rating

2.3.2.1 (c)

  • Live parts effectively protected and a warning sign attached along an electric shock Symbol

  • Danger live

    81FB86B5-2EC2-4DCB-BACA-BA563EC200A1.jpeg
  • Electric shock

    FF9CF20A-AB9A-4B82-8FB9-80CFB3BF0713.jpeg

Clause 2.3.2.1 (d)

  • Insulated tie bars for extension leads to prevent strain on socket/outlet.

Clause 2.3.2.1 (e)

  • Switchboard door is lockable, non removable without tool and fitting with a retention device to stay in open position

Clause 2.3.2.1 (e)

  • Switchboard has means of safe entry of leads and a label: KEEP CLOSED-RUN LEADS THOUGH BOTTON

Clause 2.3.3

  • Switchboard mounted on a pole, structure, wall or suitable designed free standing design

Clause 2.4.1

  • Switchboard has a Main isolation switch capable all downstream circuits.

Clause 2.4.2

  • Main switch capable of being locked or within a lockable space.

Clause 2.4.3

  • Main switch labelled appropriately: MAIN SWITCH or DISTRIBUTION BOARD ISOLATION SWITCH or similar.

Clause 2.5.3

  • Construction wiring installation in appropriate conduit to protect against mechanical damaged.

Clause 2.5.4

  • Construction wiring labelled with yellow tape with words ( construction wiring ) at distance of 5 metres.

Clause 2.6.9

  • Extension leads supported by stands or insulated hooks.

Clause 2.7.1

  • Adequate lighting provided for safe work.

Clause 2.7.2

  • Lighting is mechanically protected.

Clause 2.7.3

  • Emergency lighting adequate for safe exit of workers.

Clause 2.8.1

  • If a lift shaft is present, the final sub-circuit feeding it is locked and tagged to prevent inadvertent isolation of supply.

Clause 2.9

  • Socket outlet in site sheds and other transportation structures are a RCD protected

Clause 3.8.3

  • Portable equipment including power leads are inspected monthly intervals.

Clause 3.8.3

  • Portable RCDs trip time is tested every month.

Clause 3.8.3

  • Switchboard wiring and site sheds are inspected every month interval.

Clause 3.10

  • Register available for equipment and includes records of testing and tagging,RCD trip times result and list of repaired equipment.

Temp board picture

  • Front picture

  • Inside

CCEW

  • CCEW LODGED

CCEW

  • Picture (front )

Supervisor/Inspector

  • Name

Signature

  • Signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.