Information
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Initial Date of Installation
-
PV System Size
Electrical Equipment
-
PV Inverter (PCE) Manufacturer and Model
-
PV Module, Brand and Model #
-
Quantity of PCE's Installed
-
Is the installed PCE listed on the CEC Approved Inverters list at the time of installation?
-
Describe the System Configuration ie: 2 strings of 10 Panels, paralleled to MPPT 1 of the Inverter.
-
Quantity of PV Modules Installed
-
Are the installed PV Modules listed on the CEC Approved inverters list at the time of installation?
-
Specify the Array Orientation and Array Tilt ie: Orientation = 356° North , Tilt = 22°
MAIN SWITCHBOARD
-
Describe where the Main Switchboard is Located
-
Is the switchboard arrangement compliant?
-
Record the rating of the Solar Supply Main Switch
-
Specify the size of the conductor used for the AC between the Switchboard and the PCE
-
Is the installed AC cable rated for the rated output current of the inverter, and the Solar Supply Main Switch CB rated to protect the AC cable. AS/NZS 3000 2.5.2
-
Has the Switchboard been arranged and adequately sealed to prevent the spread of fire? AS/NZS 3000 2.9.7
-
Photo showing the Switchboard Location
-
Photo showing the Switchboard Internals
-
Photo of the Solar Supply Main Switch
-
Additional comments regarding the Switchboard
PCE Location
-
Specify the rating of the PCE AC Isolator if installed
-
Is the PCE AC Isolator correct wired, rated and installed?
DC ISOLATORS at the PCE
-
Specify the DC Isolators installed at the PCE, Brand and Model
-
DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)
-
The Load Breaking Lockable DC Isolator adjacent to the inverter is correctly rated and not exceeded the DC Voltage and Current, Isc 8.7A x 1.25 = 10.9A @ Max Voc 825VDC for a Transformer type PCE
-
Have the DC Isolators been installed maintaining the manufacturers min IP Rating
-
List any Issues identified with the DC Isolator, ie: Incorrectly wired, Incorrect Rating, IP not maintained etc.
INVERTERS
-
PCE AC Current Rating
-
PCE Max Array DC Voc
-
PCE Max DC Current
-
There is adequate clearance around the inverter in accordance with the manufacturers instructions for space and ventilation
-
Is the PCE IP Rating suitable for the location of installation?
-
Has the PCE been correctly installed? Ratings, securely mounted, accessible location. etc
-
List any Issues identified with the PCE/s, ie: Incorrectly wired, Incorrect Rating, IP not maintained etc.
-
Photo showing the PCE Location, DC Isolator and AC Isolator Area
-
Photo showing the PCE Data Label
-
Photo showing any issues identified at the PCE location
DC ISOLATORS installed at the PV Array
-
Specify the DC Isolators installed at the PCE, Brand and Model
-
Specify the DC Isolator labelled location if multiple Rooftop DC Isolator installed ie: String#1, Inv #1
-
DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)
-
Are the Terminals, Connections, Configuration, and connected loads correct for the DC Isolators installed.
-
A Load Breaking Lockable DC Isolator adjacent to the inverter is correctly rated and not exceeded the DC Voltage and Current, Isc 8.7A x 1.25 = 10.9A @ Max Voc 825VDC for a Transformer type PCE
-
Has the minimum IP Rating been maintained for the DC Isolator? Installation methods, glued fittings, Sealing Glands and Grommets etc.
-
List any Issues identified with the DC Isolator, ie: Incorrectly wired, Incorrect Rating, IP not maintained etc.
-
Photos showing the DC Isolator/s Installation and location
-
Photo showing the DC Isolator/s internal connection arrangement
-
Photo of any issues identified with the DC Isolators
-
Are there Additional DC Isolators?
Additional DC ISOLATORS installed at the PV Array
-
Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)
-
Specify the DC Isolator labelled location ie: String#2, Inv #1 etc
-
DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)
-
A Load Breaking Lockable DC Isolator adjacent to the inverter is correctly rated and not exceeded the DC Voltage and Current, Isc 8.7A x 1.25 = 10.9A @ Max Voc 825VDC for a Transformer type PCE
-
Has the minimum IP Rating been maintained for the DC Isolator? Installation methods, glued fittings, Sealing Glands and Grommets etc.
-
List any Issues identified with the DC Isolator, ie: Incorrectly wired, Incorrect Rating, IP not maintained etc.
-
Photos showing the DC Isolator/s Installation and location
-
Photo showing the DC Isolator/s internal connection arrangement
-
Photo of any issues identified with the DC Isolators
-
Are there Additional DC Isolator Issues
Additional DC ISOLATORS installed at the PV Array
-
Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)
-
Specify the DC Isolator labelled location ie: String#2, Inv #1 etc
-
DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)
DC ISOLATORS
-
Specify the DC Isolator labelled location (continue the sequence from the DC Isolators above)
-
DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)
-
Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)
DC ISOLATORS
-
Specify the DC Isolator labelled location (continue the sequence from the DC Isolators above)
-
DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)
-
Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)
DC ISOLATORS
-
Specify the DC Isolator labelled location (continue the sequence from the DC Isolators above)
-
DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)
-
Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)
DC ISOLATORS
-
Specify the DC Isolator labelled location (continue the sequence from the DC Isolators above)
-
DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)
-
Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)
DC ISOLATORS
-
Specify the DC Isolator labelled location (continue the sequence from the DC Isolators above)
-
DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)
-
Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)
-
A Load Breaking Lockable DC Isolator adjacent to the inverter is correctly rated and not exceeded the DC Voltage and Current, Isc 8.7A x 1.25 = 10.9A @ Max Voc 825VDC for a Transformer type PCE
-
Has the minimum IP Rating been maintained for the DC Isolator? Installation methods, glued fittings, Sealing Glands and Grommets etc.
-
List any Issues identified with the DC Isolator, ie: Incorrectly wired, Incorrect Rating, IP not maintained etc.
-
Photos showing the DC Isolator/s Installation and location
-
Photo showing the DC Isolator/s internal connection arrangement
-
Photo of any issues identified with the DC Isolators
SOLAR PANEL MODULES
-
List the PV Module Voltage Open Circuit (Voc)
-
List the PV Module Short Circuit Current (Isc)
-
List any Issues identified with the PV Modules, ie: Incorrectly configured, Poor layout or design etc.
-
Modules of the same string are installed in the same orientation (+ or - 5 degrees)
-
Have the PV Modules been installed in accordance with AS/NZS 5033?
-
Photo/s of the PV Array, and any issues identified.
PV Array Structure and Array
-
Roof Penetrations by any of the components used in the wiring system or Array structures are suitably sealed and waterproof
-
The PV Array structure allows sufficient clearances to facilitate self cleaning of the roof to prevent any buildup of leaves and other debris
-
PV Array structure and attachment to the roof, visually inspected and appears secure
-
All Array supports, brackets, screws and other metal parts are of similar material, to minimize the corrosive and electrolysis effect of diss-similar metals.
-
Where the number of PV Array strings could result in a potential fault current higher than the module reverse current, appropriate string protection is provided.
-
List any issues identified with the PV Array Structure or Array.
-
Photos of any issues identified above
Earthing
-
The PV Array has been provided with an equipotential earthing bond connected to the earth bar in the switchboard.
-
The PV Array Frame and PV Modules have been provided with earthing connections to comply with AS/NZS 5033
-
If lightning protection has been installed, it has been installed in accordance with AS1768
-
List any issues identified with the Earthing
-
Photos of any issues identified above
GENERAL WIRING AND INSTALLATION WORK
-
There is NO exposed LV LIVE parts on any installed equipment
-
All electrical equipment for the system is installed in accordance with AS/NZS 3000
-
Connection of AC and DC components in the same enclosure have been provided with a physical separation to achieve compliant segregation
-
All DC Cables installed within the building is enclosed in Heavy Duty conduit
-
All DC connectors throughout the array are of the same type and same model.
-
All Array cables are securely fixed into place, Plastic cable ties cannot be used as the primary support
Other COMPLIANCE WITH STANDARDS AND GUIDELINES
-
Any DC Enclosures including enclosures for string protection have a min IP 54 rating, and have been installed to maintain the IP Rating. Including any connections or conduits to the enclosure
-
If the Voc of a Non-Residential system exceeds 600VDC the installation has associated wiring protection and restricted access were required.
-
Provide information relating to any non-compliance identified in the above section
-
Photos of any issues identified above
SIGNAGE
-
A 70mm circular green label "PV" is permanently fixed to the meter box or main switchboard, and is visible upon approach
-
Fire Emergency Label is permanently fixed next to the meter box and main switchboard.<br>SOLAR ARRAY ON ..(Location).. including correct Voc and Isc ratings
-
"WARNING DUAL SUPPLY ISOLATE BOTH NORMAL AND SOLAR SUPPLIES BEFORE WORKING ON THIS SWITCHBOARD" is located on the switchboard.
-
If the PV System is connected to a Distribution Board, the Main Switchboard and all other DB's are signed with "WARNING DUAL SUPPLY, ISOLATE SOLAR SUPPLY AT DISTRIBUTION BOARD ...XXX"
-
The AC Solar circuit breaker inside the switchboard is labelled "MAIN SWITCH SOLAR SUPPLY"
-
The AC Main Switch circuit breaker inside the switchboard is labelled "NORMAL SUPPLY MAIN SWITCH "
-
Shut Down procedure is correct and is permanently fixed at the inverter and/or switchboard
-
The DC Isolators are signed "PV Array DC Isolator" or similar, but must align with wording as specified on the Shut Down Procedure
-
If above 600VDC a sign shall be fixed to the restricted access areas, "WARNING HAZARDOUS VOLTAGES - AUTHORIZED ACCESS ONLY"
-
Any PV Array Junction Boxes are labelled "WARNING: HAZARDOUS DC VOLTAGE"
-
All PV cabling or conduit work clearly labelled as "SOLAR DC" every 2 mtrs, supported and secured
-
Provide any additional Information if any labels are found to be missing.
-
Photos of any issues identified above
DOCUMENTATION
-
Has the owner of the system been provided with a System Documentation folder in accordance with AS/NZS 5033 and AS/NZS 4777?
-
List any Issues identified regarding the documentation
-
Provide Information regarding any non-compliance identified in the above section
-
Photos of any issues identified above
Finalisation
-
ALL photos taken during the Inspection including an issues identified have been uploaded to the Shared DropBox folder.
-
Additional information if required.
-
If the System has been deemed to be SAFE, Re-energise and leave ON
-
Rate the Outcome of the PV System Inspection
-
Any Additional photos to support this solar inspection?