Information

  • Client / Site

  • Conducted on

  • Prepared by

  • Location
  • Initial Date of Installation

  • PV System Size

Electrical Equipment

  • PV Inverter (PCE) Manufacturer and Model

  • PV Module, Brand and Model #

  • Quantity of PCE's Installed

  • Is the installed PCE listed on the CEC Approved Inverters list at the time of installation?

  • Describe the System Configuration ie: 2 strings of 10 Panels, paralleled to MPPT 1 of the Inverter.

  • Quantity of PV Modules Installed

  • Are the installed PV Modules listed on the CEC Approved inverters list at the time of installation?

  • Specify the Array Orientation and Array Tilt ie: Orientation = 356° North , Tilt = 22°

MAIN SWITCHBOARD

  • Describe where the Main Switchboard is Located

  • Is the switchboard arrangement compliant?

  • Record the rating of the Solar Supply Main Switch

  • Specify the size of the conductor used for the AC between the Switchboard and the PCE

  • Is the installed AC cable rated for the rated output current of the inverter, and the Solar Supply Main Switch CB rated to protect the AC cable. AS/NZS 3000 2.5.2

  • Has the Switchboard been arranged and adequately sealed to prevent the spread of fire? AS/NZS 3000 2.9.7

  • Photo showing the Switchboard Location

  • Photo showing the Switchboard Internals

  • Photo of the Solar Supply Main Switch

  • Additional comments regarding the Switchboard

PCE Location

  • Specify the rating of the PCE AC Isolator if installed

  • Is the PCE AC Isolator correct wired, rated and installed?

DC ISOLATORS at the PCE

  • Specify the DC Isolators installed at the PCE, Brand and Model

  • DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)

  • The Load Breaking Lockable DC Isolator adjacent to the inverter is correctly rated and not exceeded the DC Voltage and Current, Isc 8.7A x 1.25 = 10.9A @ Max Voc 825VDC for a Transformer type PCE

  • Have the DC Isolators been installed maintaining the manufacturers min IP Rating

  • List any Issues identified with the DC Isolator, ie: Incorrectly wired, Incorrect Rating, IP not maintained etc.

INVERTERS

  • PCE AC Current Rating

  • PCE Max Array DC Voc

  • PCE Max DC Current

  • There is adequate clearance around the inverter in accordance with the manufacturers instructions for space and ventilation

  • Is the PCE IP Rating suitable for the location of installation?

  • Has the PCE been correctly installed? Ratings, securely mounted, accessible location. etc

  • List any Issues identified with the PCE/s, ie: Incorrectly wired, Incorrect Rating, IP not maintained etc.

  • Photo showing the PCE Location, DC Isolator and AC Isolator Area

  • Photo showing the PCE Data Label

  • Photo showing any issues identified at the PCE location

DC ISOLATORS installed at the PV Array

  • Specify the DC Isolators installed at the PCE, Brand and Model

  • Specify the DC Isolator labelled location if multiple Rooftop DC Isolator installed ie: String#1, Inv #1

  • DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)

  • Are the Terminals, Connections, Configuration, and connected loads correct for the DC Isolators installed.

  • A Load Breaking Lockable DC Isolator adjacent to the inverter is correctly rated and not exceeded the DC Voltage and Current, Isc 8.7A x 1.25 = 10.9A @ Max Voc 825VDC for a Transformer type PCE

  • Has the minimum IP Rating been maintained for the DC Isolator? Installation methods, glued fittings, Sealing Glands and Grommets etc.

  • List any Issues identified with the DC Isolator, ie: Incorrectly wired, Incorrect Rating, IP not maintained etc.

  • Photos showing the DC Isolator/s Installation and location

  • Photo showing the DC Isolator/s internal connection arrangement

  • Photo of any issues identified with the DC Isolators

  • Are there Additional DC Isolators?

Additional DC ISOLATORS installed at the PV Array

  • Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)

  • Specify the DC Isolator labelled location ie: String#2, Inv #1 etc

  • DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)

  • A Load Breaking Lockable DC Isolator adjacent to the inverter is correctly rated and not exceeded the DC Voltage and Current, Isc 8.7A x 1.25 = 10.9A @ Max Voc 825VDC for a Transformer type PCE

  • Has the minimum IP Rating been maintained for the DC Isolator? Installation methods, glued fittings, Sealing Glands and Grommets etc.

  • List any Issues identified with the DC Isolator, ie: Incorrectly wired, Incorrect Rating, IP not maintained etc.

  • Photos showing the DC Isolator/s Installation and location

  • Photo showing the DC Isolator/s internal connection arrangement

  • Photo of any issues identified with the DC Isolators

  • Are there Additional DC Isolator Issues

Additional DC ISOLATORS installed at the PV Array

  • Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)

  • Specify the DC Isolator labelled location ie: String#2, Inv #1 etc

  • DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)

DC ISOLATORS

  • Specify the DC Isolator labelled location (continue the sequence from the DC Isolators above)

  • DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)

  • Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)

DC ISOLATORS

  • Specify the DC Isolator labelled location (continue the sequence from the DC Isolators above)

  • DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)

  • Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)

DC ISOLATORS

  • Specify the DC Isolator labelled location (continue the sequence from the DC Isolators above)

  • DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)

  • Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)

DC ISOLATORS

  • Specify the DC Isolator labelled location (continue the sequence from the DC Isolators above)

  • DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)

  • Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)

DC ISOLATORS

  • Specify the DC Isolator labelled location (continue the sequence from the DC Isolators above)

  • DC Isolator rated current as per connected configuration as per the manufacturer (per pole rating if connected to a Transformerless Inverter)

  • Specify the DC Isolators installed at the PCE, Brand and Model (write "As Above" if all installed DC Isolators are the same brand)

  • A Load Breaking Lockable DC Isolator adjacent to the inverter is correctly rated and not exceeded the DC Voltage and Current, Isc 8.7A x 1.25 = 10.9A @ Max Voc 825VDC for a Transformer type PCE

  • Has the minimum IP Rating been maintained for the DC Isolator? Installation methods, glued fittings, Sealing Glands and Grommets etc.

  • List any Issues identified with the DC Isolator, ie: Incorrectly wired, Incorrect Rating, IP not maintained etc.

  • Photos showing the DC Isolator/s Installation and location

  • Photo showing the DC Isolator/s internal connection arrangement

  • Photo of any issues identified with the DC Isolators

SOLAR PANEL MODULES

  • List the PV Module Voltage Open Circuit (Voc)

  • List the PV Module Short Circuit Current (Isc)

  • List any Issues identified with the PV Modules, ie: Incorrectly configured, Poor layout or design etc.

  • Modules of the same string are installed in the same orientation (+ or - 5 degrees)

  • Have the PV Modules been installed in accordance with AS/NZS 5033?

  • Photo/s of the PV Array, and any issues identified.

PV Array Structure and Array

  • Roof Penetrations by any of the components used in the wiring system or Array structures are suitably sealed and waterproof

  • The PV Array structure allows sufficient clearances to facilitate self cleaning of the roof to prevent any buildup of leaves and other debris

  • PV Array structure and attachment to the roof, visually inspected and appears secure

  • All Array supports, brackets, screws and other metal parts are of similar material, to minimize the corrosive and electrolysis effect of diss-similar metals.

  • Where the number of PV Array strings could result in a potential fault current higher than the module reverse current, appropriate string protection is provided.

  • List any issues identified with the PV Array Structure or Array.

  • Photos of any issues identified above

Earthing

  • The PV Array has been provided with an equipotential earthing bond connected to the earth bar in the switchboard.

  • The PV Array Frame and PV Modules have been provided with earthing connections to comply with AS/NZS 5033

  • If lightning protection has been installed, it has been installed in accordance with AS1768

  • List any issues identified with the Earthing

  • Photos of any issues identified above

GENERAL WIRING AND INSTALLATION WORK

  • There is NO exposed LV LIVE parts on any installed equipment

  • All electrical equipment for the system is installed in accordance with AS/NZS 3000

  • Connection of AC and DC components in the same enclosure have been provided with a physical separation to achieve compliant segregation

  • All DC Cables installed within the building is enclosed in Heavy Duty conduit

  • All DC connectors throughout the array are of the same type and same model.

  • All Array cables are securely fixed into place, Plastic cable ties cannot be used as the primary support

Other COMPLIANCE WITH STANDARDS AND GUIDELINES

  • Any DC Enclosures including enclosures for string protection have a min IP 54 rating, and have been installed to maintain the IP Rating. Including any connections or conduits to the enclosure

  • If the Voc of a Non-Residential system exceeds 600VDC the installation has associated wiring protection and restricted access were required.

  • Provide information relating to any non-compliance identified in the above section

  • Photos of any issues identified above

SIGNAGE

  • A 70mm circular green label "PV" is permanently fixed to the meter box or main switchboard, and is visible upon approach

  • Fire Emergency Label is permanently fixed next to the meter box and main switchboard.<br>SOLAR ARRAY ON ..(Location).. including correct Voc and Isc ratings

  • "WARNING DUAL SUPPLY ISOLATE BOTH NORMAL AND SOLAR SUPPLIES BEFORE WORKING ON THIS SWITCHBOARD" is located on the switchboard.

  • If the PV System is connected to a Distribution Board, the Main Switchboard and all other DB's are signed with "WARNING DUAL SUPPLY, ISOLATE SOLAR SUPPLY AT DISTRIBUTION BOARD ...XXX"

  • The AC Solar circuit breaker inside the switchboard is labelled "MAIN SWITCH SOLAR SUPPLY"

  • The AC Main Switch circuit breaker inside the switchboard is labelled "NORMAL SUPPLY MAIN SWITCH "

  • Shut Down procedure is correct and is permanently fixed at the inverter and/or switchboard

  • The DC Isolators are signed "PV Array DC Isolator" or similar, but must align with wording as specified on the Shut Down Procedure

  • If above 600VDC a sign shall be fixed to the restricted access areas, "WARNING HAZARDOUS VOLTAGES - AUTHORIZED ACCESS ONLY"

  • Any PV Array Junction Boxes are labelled "WARNING: HAZARDOUS DC VOLTAGE"

  • All PV cabling or conduit work clearly labelled as "SOLAR DC" every 2 mtrs, supported and secured

  • Provide any additional Information if any labels are found to be missing.

  • Photos of any issues identified above

DOCUMENTATION

  • Has the owner of the system been provided with a System Documentation folder in accordance with AS/NZS 5033 and AS/NZS 4777?

  • List any Issues identified regarding the documentation

  • Provide Information regarding any non-compliance identified in the above section

  • Photos of any issues identified above

Finalisation

  • ALL photos taken during the Inspection including an issues identified have been uploaded to the Shared DropBox folder.

  • Additional information if required.

  • If the System has been deemed to be SAFE, Re-energise and leave ON

  • Rate the Outcome of the PV System Inspection

  • Any Additional photos to support this solar inspection?

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.