Title Page
-
Walmart Store Number
-
Conducted on
-
Location
-
Technician Name
Inspection Items
-
Are there two electrical services?
-
Take a picture of the overall layout of the Main Electrical Distribution Switchboard
-
Take a picture of the Main Breaker and the associated Relay and trip settings
-
Breaker Make/Model
-
Voltage/Amperage Value
-
Type of Protection Relay
-
Long-Time Pick Up Value (A or kA)
-
Long Time Delay (seconds)
-
Short-Time Pick Up Value (A or kA)
-
Short-Time Delay Value (seconds)
-
Instantaneous Pick Up Value (A or kA)
-
Ground Fault Pick Up Value (A or kA)
-
Ground Fault Delay Value (seconds)
-
Determine where the main electrical switchboard is fed from.
-
Is it protected by fuses?
-
What is the type, voltage, amperage, and configuration of the fuses?
-
How to you foresee disconnecting the main power from the main switchboard?
-
Take a picture of the secondary Electrical Distribution Switchboard (overall in electrical room)
-
Take a picture of the Main Breaker and the associated Relay and trip settings
-
Breaker Make/Model
-
Voltage/Amperage Value
-
Long-Time Pick Up Value (A or kA)
-
Long Time Delay Value (seconds)
-
Short-Time Pick Up Value (A or kA)
-
Short-Time Delay Value (seconds)
-
Instantaneous Pick Up Value (A or kA)
-
Ground Fault Pick Up Value (A or kA)
-
Ground Fault Delay Value (seconds)
-
Determine where the main electrical switchboard is fed from.
-
Is it protected by fuses?
-
What is the Amperage rating, fuse type and kA rating of the fuses?
-
What is the rating of the transformer (if marked)
-
How far from the main switchboard is the transformer located?
-
Please take a picture of the transformer and nameplate (if applicable)
-
What is the make/model/serial number of the transformer?
-
What are the voltage, amperage, %iz, and other ratings of the transformer?
-
Please take a picture of the location and nameplate
-
How to you foresee disconnecting the main power from the main switchboard?
Refrigeration Equipment (Coolers, etc.)
-
Is there a breaker in the main distribution panel that feeds all of the refrigeration equipment?
-
What is the Make/Model of the breaker?
-
What is the voltage/amperage?
-
How many and what size conductors are terminated on the load side of the breaker?
-
Where is the refrigeration equipment fed from?
-
What are the panel names, voltage/amps?
-
Roughly how many AMPS are required to temporarily feed the refrigeration panels during a power outage?
-
How far can the generator be parked from the refrigeration breaker in order to backfeed during the outage?
-
Can the breaker be isolated to temporarily feed the electrical panels that control the refrigeration equipment?
-
Why not?
-
How can this be accomplished?
Temporarily Feed Refrigeration Equipment for Shutdown
-
How far can the generator be parked from the refrigeration breaker in order to backfeed during the outage?
UPS (Uninterrupted Power Supply)
-
Take a picture of the nameplate of the UPS
-
What is the Make/Model of the UPS?
-
What is the AC Input
-
What is the AC Output
-
What is the Capacity
-
What is the Battery Input
-
What is the Serial Number
-
What is the size, type, conductor count, and type of cable feeding it?
-
What size is the disconnect for the UPS?
Pharmacy
-
Is there a Pharmacy?
-
Are there fridges in the pharmacy?
-
Add photos
-
How Many?
-
What panel are they fed from?
-
Where is the panel located?
-
Can an extension cord be run to feed these fridges during a power outage?
-
How do you anticipate keeping these fridges running during the outage?
Walmart Super Store (Other Stores Located Inside Walmart)
-
Is this Walmart a Super Store?
-
What other stores are located in the Super Store?