Title Page

  • Document No.

  • Audit Title

  • Client / Site

  • Conducted on

  • Prepared by

  • Location
  • Personnel

Design Module

  • Specify System type, addressable (A) or conventional (C).

  • What is the specified category of system?

  • Is the category specified and appropriate? Clause 5 Annex A

  • Are design battery calculations available? Clause 25.4(e) annex D

  • Is the specified standby power supply period suitable for the system category? Clause 25.4(e)

  • Does the system design proposal include all the required info? Clause 8.2

  • Have the correct quiescent and alarm currents been used? Clause 25.4(e) Annex D

  • Is any cause & effect on the system documented? Clause 40.2(a1)

  • Has the design taken into account any building regs (e.g. Part M) or equality act requirements? Clause 18.2.1(a)

  • Is the design battery capacity adequate? Clause 25.4(e) Annex D

  • Assumptions/variations drawn to customers attention at design/quotation stage? Clause 7.2(a)

Documentation

  • Has the required certification (design, installation, commissioning, acceptance) been issued? Clause 41.2(a)(b)

  • Is there a record of agreed variations? Clause 40.2(e)

  • Have suitable user instructions/manuals been supplied to the customer? Clause 40.2(e)

  • Are there satisfactory as fitted drawings? Clause 40.2(e)

  • Have the drawings been provided to the customer? Clause 40.2(e)

  • Has a log book been supplied? Clause 40.2(e)

  • Are insulation resistance test results available and satisfactory? Clause 38.2(a)

  • Are test results for circuit parameters such as loop continuity available and satisfactory? Clause 38.2(d)

  • Have 230v supply test records been supplied by electrical contractor/client? Clause 38.2(c)

Installation

  • Are cables of suitable type? Clause 26.2(b)(d)

  • Are cables with enhanced fire resistance used where required? Clause 26.2(c)(e)

  • Are cables adequately protected against mechanical damage? Clause 26.2(h)(k)

  • Are methods of cable support satisfactory? Clause 26.2(f)

  • Is there suitable segregation from other services and fire other fire alarm cables, where required? Clause 26.2(l)(m)(n)

  • Are joints in cables terminated correctly? Clause 26.2(g)

  • Are all junction boxes suitably labelled? Clause 26.2(g)

  • Are fire alarm cables a single common colour? Clause 26.2(o)

Mains Power Supplies

  • Has a suitable mains power supply been provided? Clause 25.2

  • Is the continuity of supply satisfactory? Clause 25.2(a)(b)(h)

  • Is it a dedicated circuit? Clause 25.2(b)

  • Has a suitable local isolation point (spur) been provided?

  • Is labelling satisfactory? Clause 25.2(f)(g)

  • Is the supply independent of any RCD protection? Clause 25.2(i)

  • Is the wiring of suitable type and segregated? Clause 26.2(b)

  • Do mains supplies enter the CIE separately? Clause 26.2(n)

  • Do separate mains supplies to other power supply units remote from the control panel meet the above requirements? Clause 25.2(e)

Circuit Design

  • Does the area per loop satisfy the specified standards (addressable systems only)? Clause 12.2.2(d)

  • Is there adequate short circuit isolation? Clause 12.2.2(c)

  • Is there adequate tolerance to open circuit faults? Clause 12.2.2(c)

  • Are there at least 2 sounder circuits (or a suitable loop with isolators)? Clause 12.2.2(j)

  • Confirm that sounder circuits are provided without spurs (conventional sounder systems only). Clause 12.2.1(a3)

  • Are circuits monitored adequately? (E.g. Are fault conditions indicated correctly on CIE) clause 12.2.1

Zoning

  • Is the detection/alarm zoning adequate? Clause 13/14

  • Is a zone plan displayed? Clause 23.2.2(e)

  • Does the area per detection zone comply with specified standards? Clause 13.2.3(a)

  • Does the search distance comply with specified standards? (60m maximum, but may not apply to addressable systems) clause 13.2.3(b) 13.2.4(b)

  • Are MCP's assigned to the relevant accommodation zone? Clause 13.2.1(a)

  • Are staircases and other vertical shafts zoned separately? Clause 13.2.3(c)

  • Do the boundaries of alarm zones comprise fire resisting construction (not external walls)? (Phased evacuation only) clause 14.2(a)

  • Do the boundaries of alarm zones coincide with the boundaries of detection zones? (Phased evacuation only) clause 14.2(d)

Manual Call Points

  • Is there adequate provision of call points? (Maximum travel distance 45m) clause 20.2(d)(e)(f)

  • Is call point location and siting appropriate? Clause 20.2(c)

  • Are all manual call points type A (automatic activation when frangible element is broken)operation? Clause 20.2(a)

  • Are all call points fitted with a protective cover? Clause 20.2(b)

  • Is an evacuate signal sounded within 3 seconds of operation of any MCP? Clause 20.2(c)

  • Are all call points mounted at the correct height? (1400mm above FFL +or- 300mm) clause 20.2(i)

  • Do call points remain operable when a detector is removed? Clause 12.2.2(e1)

  • Are suitable IP rated call points used in areas exposed to moisture? Clause 35.2.2(c)

  • Are call points sited to take into account the potential for malicious operation? Clause 35.2.2(d)

  • Are call points sited to take into account the potential for accidental operation? Clause 35.2.2(a)(b)

Automatic Detection

  • Are the areas in which automatic fire detection is provided, sufficient for the category of the system? Clause 8.2

  • Are the types of detectors used appropriate? Clause 21.2

  • Is the detector spacing appropriate? Clause 22.3

  • Are ceiling heights within the limits for the detector types used? Clause 22.9

  • Is detector siting appropriate? Clause 22.2

  • Is siting/spacing satisfactory in relation to enclosed landings & stairways? Clause 22.2(b)

  • Is siting/spacing satisfactory in relation to shaft/riser openings into accommodation areas (except L4, L5 & P2)? Clause 22.2(c)

  • Is siting/spacing satisfactory in relation to voids >800mm? Clause 22.2(d) 22.3(f)

  • Is siting/spacing satisfactory in relation to lantern lights >800mm? Clause 22.2(e)

  • Is siting/spacing satisfactory in relation to walls? Clause 22.3(g)

  • Is siting/spacing satisfactory in relation to ceiling obstructions? Clause 22.3(h)

  • Is siting/spacing satisfactory in relation to partitions and storage racks? Clause 22.3(i)

  • Is siting/spacing satisfactory in relation to deep beams? Clause 22.3(j)

  • Is siting/spacing satisfactory in relation to honeycomb ceilings? Clause 22.3(k)

  • Is siting/spacing satisfactory in relation to perforated ceilings? Clause 22.3(l)(m)

  • Is siting/spacing satisfactory in relation to air conditioning/ventilation outlets? Clause 22.3(n)

  • Is siting/spacing satisfactory in relation to clear space below the detector (500mm)? Clause 22.3(o)

  • Have optical beam detectors been sited/installed to the recommendations of BS5839-1: 2017? Clause 22.5

  • Are the detectors mounted within the appropriate limits below the ceiling? Clause 22.3(d)

  • Are remote indicator lamps provided where required? Clause 13.2.5

  • If BS 6266 is specified, are the specific recommendations for detector type, spacing and siting satisfied?

  • If BS 7273-1 is specified, are the specific recommendations for detector type, spacing and siting satisfied? (Interfaces for suppression systems)

Audible and Visual Alarms

  • Does the sounder layout appear to be suitable for the sound levels required? Clause 16.2.1

  • Have sound levels been measured and any shortfalls identified? Clause 39.2(c5)

  • Are the sounder of an appropriate type (e.g in relation to frequency)? Clause 16.2.1(b)(c)

  • Where music levels are >80 dB(A), is the music muted when the alarm sounds? Clause 16.2.1(d)

  • Can the fire service be summoned without interference from the fire alarm system? Clause 15.2(c)

  • Has the provision of fire alarm warnings for people with impaired hearing been considered? Clause 18.2.1

  • Have visual alarms been provided where required? Clause 17.2(a)

  • Are the visual alarms adequate in terms of colour and siting? Clause 17(b-f)

  • Is an external sounder/visual alarm provided if required? Clause 16.2.1(f)

  • If a voice alarm system has been provided, does it satisfy the recommendations of BS 5839-8?

  • Are visual alarm devices compliant with BS EN54-23 and sited accordingly? Clause 17.2(e)(f) Annex F

Control and Indicating Equipment

  • Is compliance with EN54-2 and EN54-4 claimed? Clause 11.2(k)(n)

  • Are functional requirements of EN54 satisfied? Clause 39.2(c8)

  • Is the siting of the CIE appropriate? Clause 23.2.1(a)(b)(g)

  • Is the area in which CIE is sited protected by automatic detection (if required)? Clause 23.2.1(f)

  • Is internal workmanship satisfactory?

  • Are batteries for standby power supplies of a suitable type? Clause 25.4(b)

  • Are batteries marked with date of installation? Clause 25.4(c)

  • Have the quiescent & alarm currents been verified at commissioning? Clause 39.2(c21)

  • Is the battery capacity installed adequate? Clause 25.4(e)

  • Is the wiring to any external power supplies or battery enclosures of suitable type? Clause 26.2(b)

  • Are the connections to power supply equipment in separate housings duplicated? Clause 12.2.2(m)

  • Are PSU/batteries in separate enclosures from the CIE fused at the remote end? Clause 12.2.2(m)

  • Do batteries connected in parallel give the correct fault indications? Clause 12.2.1(d)

  • Is the rating of the charger sufficient for full alarm load? Clause 25.4(d)

Remote Transmission of Alarms

  • Is the FD&A system provided with an ATS? Clause 15.2(e)(f)(g)(h)

  • Is the telephone switch room or frame room protected by AFD? Clause 25.4(e3)

  • If category P is a fault signal transmitted in addition to fire signals, where required? Clause 25.4(e3)

  • If no fault signal is transmitted is the battery backup capacity sufficient to maintain the system for at least 24hrs longer than the unoccupied area (max 72hrs)? Clause 25.4(e4)

  • Is the wiring to/from the transmitter of a satisfactory type and monitored? Clause 15.2(j)(l)

  • Do the 230v supply and the standby supply meet the requirements of clause 25? Clause 15.2(m)

  • Is the ATS PSU monitored for the required fault conditions by the CIE? Clause 12.2.1

Ancillary Services

  • Confirm that power is not supplied by the fire alarm system in the quiescent state? Clause 9.2(d)

Workmanship

  • What is the standard of workmanship?

  • Does the system conform to BS 7671 (as far as can be ascertained)? Clause 37.2(a)

  • Are cables securely fixed? Clause 37.2(b)

  • Are cable holes fire stopped? Clause 37.2(l)(m)

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.