Bulk LP-Gas Storage Annual Inspection

  • Location Name:

  • Container(s) Physical Address:
  • Inspection Date:

  • Inspected by:

Storage Container(s) Information

  • LP-Gas Storage Facility Photo(s):

  • Add A Storage Container:

  • Storage Container
  • Capacity:

  • Serial Number:

  • National Board Number:

  • Manufacturer Name:

  • Year Built:

Vaporizer Information

  • Vaporizer Photo(s):

  • Add A Vaporizer:

  • Vaporizer
  • Manufacturer Name:

  • Model Number:

  • Serial Number:

  • Year Built:

  • Maximum Vaporizing Capacity - GPH:

  • Burner Input BTU per Hour:

Bulk Storage Containers

  • Is the manufacturer's data plate secured and legible?

  • Is the data plate free of corrosion?

  • Is the pressure rating proper for the product?

  • Are above ground tanks properly painted?

  • Are containers free of excess corrosion, damage, dents, gouges, or other damage?

  • Are all container markings and decals in accordance with NFPA 58?

  • Are foundations in good condition?

  • Are containers/saddles free of corrosion at masonry contact areas?

  • Are saddle pads in good condition?

  • Are connections on containers greater than 2,000 gallon water capacity marked "vapor" or "liquid"?

  • Are all unused openings plugged or capped?

  • Are all container fittings leak-free?

  • Are pressure gauges in good condition and suitable for 250 psig service (such as 0 - 400 psig)?

  • Are thermometers in good condition?

  • Are liquid level gauges arranged and installed so that the liquid level can be accurately determined?

  • Is relief valve data legible?

  • Are the relief valves marked for use with LP-Gas and labeled by an independent testing agency?

  • Do relief valves communicate with the container vapor space and discharge upward, unobstructed to the open air?

  • Are relief valves equipped with vent stacks of proper diameter and length?

  • Are relief valve vent stacks equipped with breakaway couplings?

  • Do relief valve vent stacks have loose fitting protective caps or closures to prevent entry of foreign matter?

  • Are weep holes for moisture drainage open?

  • Are the valve body seams leak free?

  • Are ESV's in good working condition and leak free?

  • Is the pneumatic control system in good working condition?

  • Are remote emergency shutoff devices between 25 and 100 feet from the ESV and within the path of egress?

  • Is the thermal link intact and free of paint?

  • Are manual shut-off valves located so that they can be easily reached during normal operations and in an emergency?

  • Are valves in good condition and leak free?

  • Do valves have the proper service pressure rating, equal to or greater than the maximum allowable working pressure of the container?

  • Are catwalk railings provided and in good condition?

  • Are stairways well anchored and supported?

  • Does decking design offer drainage and prevent accumulation?

  • Is the area within 10 feet of the containers free of weeds, long grass, rags, paper, wood or other loose or piled combustible materials?

  • LP-Gas storage tank is underground.

  • Is protection against vehicular damage provided for the fitting housing, housing cover, tank connections and piping?

  • Is the container protected against corrosion by at least one of the following means:

  • Cathodic protection?

  • An external coating on the tank?

Piping

  • Are aboveground pipes properly painted?

  • Are pipes free of corrosion damage, dents, gouges or other damage?

  • Are pipes adequately supported?

  • Are pipes adequately protected against damage by vehicles?

  • Are pipes properly marked "vapor" or "liquid" or color coded accordingly?

  • Are all flanges and fittings properly sized for the pressure rating, equal to or greater than the maximum allowable working pressure of the system?

  • Are all stainless steel flex connectors in good working condition?

  • Are all flow indicators and sight checks in proper working condition and leak free?

  • Are all fittings and pipes leak free?

  • Are hydrostatic relief valves installed in each section of piping in which liquid can be isolated between shut-off valves?

  • Are hydrostatic relief valves approved for use with LP-Gas?

  • Do the hydrostatic relief valves have pressure settings between 400 - 500 psig?

  • Are valves located so that they can be easily reached during normal operations and in an emergency?

  • Are valves in good condition and leak free?

  • Do valves have the proper pressure rating, equal to or greater than the maximum allowable working pressure of the system?

  • Underground piping is present.

  • Is metallic underground piping protected against corrosion by at least one of the following means:

  • An external coating on piping?

  • Cathodic protection?

Pumps / Compressors

  • Liquid Pump (check if system has a liquid pump)

  • Are pump pads and/or foundations in good condition and properly supporting the pumps?

  • Are base plate bolts in place and properly securing the pump to the foundation?

  • Are pumps free of corrosion or other damage?

  • Are the pumps properly lubricated?

  • Are hydrostatic relieve valves installed in the appropriate location(s) and in good working condition?

  • Are fittings and piping associated with the pump leak free?

  • Are bypasses in good working condition and leak free?

  • Are drive belts properly aligned and in good working condition?

  • Shaft Coupling-Driven Pumps:

  • Are shaft couplings properly aligned?

  • Are spacing bushings in good working condition?

  • Gear Reduction-Driven Pumps:

  • Are universal joints and couplings properly aligned and in good working condition?

  • Vapor Compressor (check if system has a vapor compressor)

  • Are compressors free of corrosion or other damage?

  • Are compressor pads and/or foundations in good condition and properly supporting the compressors?

  • Are base plate bolts in place and securing the compressor to the foundation?

  • Are the compressors properly lubricated?

  • Is the crankcase oil properly filled?

  • Is the crankcase oil pressure properly set?

  • Has the oil filter been changed at the manufacturer's recommended interval?

  • Are strainers in good working condition and leak free?

  • Are pressure relief valves installed in the appropriate location and in good working condition?

  • Are all back check valves in proper working condition and leak free?

  • Are fittings and piping associated with the compressor leak free?

  • Are drive belts properly aligned, tension properly set, and in good working condition?

  • For direct drive compressors, are shaft couplings properly aligned and in good working condition?

  • Are drive belt / shaft coupling guards in place and secure?

  • Are strainers in good working condition and leak free?

  • Are all stainless steel flex connectors in good working condition?

  • Are pressure gauges in good condition?

  • Are valves located so that they can be easily reached during normal operations and in an emergency?

  • Are valves in good condition and leak free?

  • Do valves have the proper pressure rating, equal to or greater than the maximum allowable working pressure of the system?

Bulkheads

  • Are bulkheads properly protected against vehicular damage?

  • Are bulkheads in good condition and properly supporting the bulkhead, especially in the event of a pull-away?

  • Are pipe nipples and couplings that are attached to the bulkhead in good working condition and free of excessive wear?

  • Are all flanges and fittings properly sized for the pressure rating, equal to or greater than the maximum allowable working pressure of the system?

  • Are all stainless steel flex connectors in good working condition?

  • Are all flow indicators and sight checks in proper working condition and leak free?

  • Are hydrostatic relief valves installed in the appropriate location and in good working condition?

  • Are all fittings and pipes leak free?

  • Are ESV's in good working condition and leak free?

  • Is the pneumatic control system in good working condition?

  • Are remote emergency shutoff devices between 25 and 100 feet from the point of transfer and within the path of egress?

  • Are the hose covers free of exposed reinforcement?

  • Are hoses free of kinks and not flattened?

  • Are hoses free of soft spots when not under pressure, show no bulging under pressure, and have no loose outer coverings?

  • Are hose coupling assemblies secure and in good working condition?

  • Are the ACME threads and O-rings / gaskets in good working condition?

  • Are valves located so that they may be easily reached during normal operations and in an emergency?

  • Are valves in good condition and leak free?

  • Do the valves have the proper pressure rating, equal to or greater than the maximum allowable working pressure of the system?

Scales

  • Has the scale(s) been checked periodically using a certified / standard dead weight?

  • Has the scale(s) been certified by the appropriate authority having jurisdiction?

  • Have all loops, pivots, and bearings been periodically lubricated?

  • Are the scale pit(s) and/or platform(s) free of debris?

  • Are all actuators and control valves leak free and in good working condition?

  • Are all sensing lines leak free and in good working condition?

  • Are the hose covers free of exposed reinforcement?

  • Are hoses free of kinks and not flattened?

  • Are hoses free of soft spots when not under pressure, show no bulging under pressure, and have no loose outer coverings?

  • Are hose coupling assemblies secure and in good working condition?

  • Are the ACME threads and O-rings / gaskets in good working condition?

Meters (For Retail Sales Only)

  • Is the meter(s) properly calibrated or "proved" at the appropriate time intervals?

  • Is the seal(s) in place by the appropriate authority having jurisdiction?

  • Is the meter in good working condition and free of leaks?

  • Is the strainer in good working condition and leak free?

  • Are the hose covers free of exposed reinforcement?

  • Are hoses free of kinks and not flattened?

  • Are hoses free of soft spots when not under pressure, show no bulging under pressure, and have no loose outer coverings?

  • Are hose coupling assemblies secure and in good working condition?

  • Are the ACME threads and O-rings / gaskets in good working condition?

  • Are pull-away couplings in place and in good working condition?

Vaporizers

  • Is the vaporizer(s) leak free and in good working condition?

  • Have pilot lights been cleaned on a regular basis?

  • On a periodic basis, have all strainers been cleaned at the inlet side of the vaporizer(s)?

  • Have heavy ends been cleaned from the vaporizer(s) and/or separator tank?

  • Have the burner openings, thermostat, and flue been cleaned?

  • Is the vaporizer(s) located in accordance with NFPA 58?

Regulators

  • Is the first-stage or high-pressure regulator directly attached by flexible connectors to the vaporizer outlet or to the interconnected piping of manifolded vaporizers?

  • Are all first-stage and high-pressure regulators installed outside of buildings?

  • Are all regulators that are outside of buildings installed and protected so that their operation will not be affected by environmental elements or insects?

  • Is the point of discharge on the regulator's relief device at least 3 feet horizontally away from any building opening that is below the level of the discharge?

  • Is the point of discharge on the regulator's relief device located at least 5 feet in any direction from any source of ignition or mechanical ventilation air intakes?

Electrical Systems

  • Are electrical components and wiring contained in explosion-proof housings and conduit and in goofing working condition?

  • Are all seal-off fixtures filled with suitable putty and installed in the appropriate locations?

  • Are pump and/or compressor switches readily accessible to the operator?

  • Are electrical controls for equipment clearly marked or color-coded to indicate the on and off (stop) positions?

  • Is the electrical emergency shutdown located more than 20 feet (but less than 100 feet) from dispensing devices and prominently labeled?

Fire Extinguishers

  • Add A Fire Extinguisher:

  • Fire Extinguisher
  • Extinguisher number or location:

  • Size and rating:

  • Date of last annual inspection:

Sign Off:

  • All items, applicable to the LP-Gas storage installation, have been inspected according to the standards set forth in the Operation and Maintenance Handbook.

  • Signature:

  • Comments:

Follow-up:

  • All unsatisfactory items contained in this inspection have been corrected.

  • Signature & Date:

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.