Initial Inspection
-
Follow-Up Inspection
Description of Location
Safety/Housekeeping
-
Scrap material picked up
-
Proper PPE being worn
Materials
-
All inaccessible control wiring shall be run in rigid conduit with grey fittings
-
Wiring exposed to view shall be in rigid conduit or EMT
-
Wiring in accessible locations shall be plenum rated cable
-
Bridal rings shall be used in ceiling plenums
-
All conduit is larger than 1/2"
-
Insulated T-Stats at exterior walls
-
Rough in boxes in lieu of mud in
Installation
-
Sound and fire caulking in place
-
All wiring shall be supported adequately and routed neatly parallel/perpendicular to building grid lines
-
All open ends of conduit are capped with tape or plugs
-
Verify all conduits entering a j-box, electrical panel or pull box have insulated bushings
-
Conduit and cable tray has no visible damage (crimpings, improper bends, etc)
-
All j-boxes are closed
-
Unused KO's in J-boxes are plugged
-
Verify that control wiring is not in the same conduit as power wiring
-
Boxes should not be installed back to back. Provide no less than 12" of separation
-
Sensors and T-stats should be aligned to align horizontally with light switches at 48"(Exception at Retail)
-
Device shall align vertically if installed in same stud space as another device
Identification
-
Label conduits at all underground stub ups with where the conduit is routed to
-
Verify colored conduit fittings used as follows:<br>Black-normal<br>Blue-standby<br>Orange-mechanical<br>Yellow-life safety<br>Green-grounding<br>Red-fire alarm<br>White-security<br>No paint-comm<br>Grey-Mechanical Controls
-
Exposed devices shall be identified with engraved labels on the body of the device. Do not put identification on removable covers.
Low Voltage Raceways
-
Verify that all raceways installed for low voltage cabling have pull strings installed. Leave no less than 12" of slack at each end.
-
Verify bushings are installed on the ends of all raceways installed for low voltage cabling
Misc.
-
Contractor drawings are current set with applicable changes posted
-
Photos attached
-
BIM drawings attached
-
Details attached
-
Incomplete items moved to QUIT log?
-