Title Page
-
Site conducted
-
Conducted on
-
Prepared by
-
Location
-
Operative being assessed
General requirements
-
Prior to commencing any work ensure that the following documentation is available and authorised where
appropriate.
1. Job instructions
2. Routine / Non-Routine operation procedures
3. Permit to work
Tools and equipment
-
4 No. Squeeze-off units
-
Bypass.
-
Pressure gauges
-
Metallic vent pipes, flame traps,<br>earthing straps and pressure points.<br>
-
Clean, damp, on-synthetic cloths, paper towelling<br>and water
-
Expanding pipe stoppers.
-
PE pipe cutters/saw.
-
Squeeze-off tape.
-
Re-rounding clamp.
Pipe & fittings preparation:
-
Thoroughly clean the main where the squeeze-off and joints are to be made
-
Check diameter, Standard Dimension Ratio (SDR). Material type – information will be printed along <br>the pipe barrel at 1m intervals on each side of the pipe. Check then pipe for ovalty and re-round as<br>required.
-
Ensure the correct distance is maintained from the existing fittings, joints, squeeze-off applied<br>locations and any proposed future joints used for connection purposes.
-
Set out the squeeze-off operation by marking the exposed pipe with all positions for pressure<br>points, by-pass connections, vent points, rider points and location of squeeze-off.
Operational material limits
-
Limits have been set for squeeze-off operations to prevent long-term damage to PE pipes during <br>squeeze-off operations.
-
The minimum distance between squeeze-off bars or beams is calculated as a percentage of twice <br>the minimum of the wall thickness. <br>> For up to 250mm pipe the limit is 80% of twice the minimum wall thickness.<br>> For 315mm-355mm pipe the limit is 90% of twice the minimum wall thickness.
-
The range of PE wall thickness are detailed in pipe specifications but should be confirmed on be <br>the use of an ultrasonic measuring devise.
Establish network pressure:
-
Install two pressure monitoring points on the PE main either side of the proposed flow stop section<br>of pipe, a PE tapping tee can achieve this
-
Attach and commission pressure gauges.
-
Confirm Network pressure expected and that it does not exceed 2bar for medium pressure and <br>75mbr for low pressure works.
Assemble by-pass & by pass vents:
-
Construct the bypass in size and material as per written procedures. Where large diameter branch<br>saddles are required refer to module 6-Specialist techniques for construction details.
-
Where the by-pass is 90mm or below, it must be pressure tested with valves A and B in the open<br>position with the vent pipes capped off above the vent valves C and D, these vent valves must be <br>left in the open position. The bypass must be pressure tested with air to 350mbr for low <br>pressure or 3bar for medium pressure for 15 minutes. No pressure loss is accepted. On <br>successful completion of the air test the vents on valves C and D must be closed and the vent<br>pipes erected, close vales A and B
-
The main can now be drilled.
-
Where larger diameter bypasses are used appropriate under pressure drilling arrangements<br>must be undertaken in accordance with Section D1 or D2, (SGN/WI/ML/2). To provide valves A<br>and B. the bypass must be tested to the same requirements as above prior to connecting on to<br>the under-pressure tees/valves. Any joint not included in a test must be checked using a leak <br>detection fluid once the bypass has been commissioned.
Commission bypass
-
It is important that the bypass is confirmed free from blockages by purging both ways. Check all <br>valves are closed, check network pressure.
-
Open vent valve C, then open bypass valve A,
-
Purge until two independent readings of 90% gas in air have been obtained from vent C, then close<br>vent valve C and bypass valve A.
-
Open vent valve D then bypass valve B.
-
Purge until two independent readings of 90% gas in air have been obtained from vent valve D. Close<br>vent valve D.
-
Open bypass valve A slowly and pressurise to network pressure.
-
Fittings not tested must be checked for soundness with approved leakage detection fluid, washing<br>off pipe and fittings with clean water afterwards
-
The bypass is now fully commissioned.
Squeeze-off preparation
-
Set the stops to the correct pipe size and SDR. If the SDR of the pipe cannot be found, then set<br>the stops to the size of pipe. For 90mm and 125mm SDR 17.6 pipe it is necessary to set the stops<br>to one size below i.e. 125mm to 90mm and 90mm to 63mm. See procedure J below. For larger <br>diameter pipes the squeeze-offs manufacturer’s operating instructions should be consulted for <br>correct use of the equipment
-
Check squeeze-off units are in good working order by closing and opening them on a scrap piece <br>of PE.
-
Place the squeeze-off units on the main
- Yes
- No
- N/A
-
Attach all vent pipes and the purge riders onto main as set out on the pipe. Vent pipes must be<br>constructed as per Section H1, (SGN/WI/ML/2) and protrude 2.5m above ground level. Metallic <br>vent pipes must be earthed using approved electrical earth rods and straps from the metallic <br>vent pipes to earth. Vent pipes must be adequately supported
-
Squeeze-off PE main:
-
Re-check Network pressure to confirm mains operating pressure.
-
Re-check bypass is fully open.
-
Slowly apply downstream squeeze-off unit 1, until it reaches its maximum position, monitoring the<br>pressures at both mains pressure points to ensure the pressure is not falling. Monitor the pressure <br>gauges for 10 minutes before proceeding. If the pressure starts to fall below that stated on the <br>written procedure release squeeze-off and inform the Operational Manager
-
Apply squeeze-off safety stops.
-
Slowly apply upstream squeeze-off 2. Continuously monitor pressure.
-
Apply squeeze-off safety stops.
-
Open vent valve F or K and check between the squeeze-off units 1&2 to establish whether there <br>is any gas passing.
-
If gas is passing, refer to Section E1, (SGN/WI/ML/2)
-
If no gas is passing continue with the operation, leave vent pipe F and/or K open.
-
Slowly apply upstream squeeze-off 3, monitoring Network pressure.
-
Apply squeeze-off safety stops.
-
Check at the vent between the squeeze-off units 2 & 3 by opening valves G and I, ensuring valve<br>H remains closed, to establish whether there is any gas passing.
-
If gas is passing, see Section E1, (SGN/WI/ML/2)
-
If no gas is passing continue with the operation, leave vent pipe between squeeze-offs 2 and 3 <br>open.
-
Slowly apply downstream squeeze-off 4, monitoring network pressure.
-
Apply squeeze-off safety stops.
-
Check at the vent E between the squeeze-off units 1 & 4 to establish whether there is any gas<br>passing.
-
If gas is passing, see Section E1, (SGN/WI/ML/2)
-
If no gas is passing continue with the operation, leave vent pipe E open.
-
At the instruction of the Operational Manager the section of main between squeeze off 1 & 2 <br>may be purged with an inert gas, introduced to the work site through K, and vented through F,<br>with care being taken to ensure that the inert gas pressure does not exceed one third of the<br>pressure in the live main
Cut out PE main:
-
Drape damp cloths around the pipe and ensure they are in contact with the ground on each side of <br>the cut to prevent a spark from static electricity.
-
Cut pipe section as specified in the work instruction, continually monitor the network pressure and<br>the atmosphere within the cut-out area. The cutting of PE mains must only be undertaken using <br>approved equipment. Should a guillotine be used a re-rounding clamp should be put on the main <br>prior to joining.
-
Install expanding stoppers whilst preparing fittings for installation.
-
Remove expanding stoppers.
-
Install new section as specified in the work instruction and in accordance with Appendix D,<br>(SGN/WI/ML/2) Electrofusion.
Re-commission main:
-
Re-commissioning of the PE main can be carried out either by using a rider or the controlled release of <br>squeeze-offs. For medium pressure mains, the preference is to use a rider to enable the pressure in the<br>newly inserted section of main to be raised in stages allowing leakage test to be undertaken using leak <br>detection fluid.
Re-commission PE main by use of a rider:
-
Connect purge rider through valve J to closed vent point H. A governed purge rider may be<br>required as detailed in the written procedure. The construction of rider’s is detailed within <br>Section E2, (SGN/WI/ML/2)
-
Close valve G, Open valve J & H and purge rider until two independent readings of 90% gas in air<br>have been obtained at vent.
-
Close valve I.
-
Remove safety stops and release downstream squeeze-off 1.
-
Remove safety stops and release upstream squeeze-off 2.
-
Close valves F & K (valve K where applicable), open valve G and purge through vent pipe E until <br>two independent readings of 90% gas in air have been obtained at vent pipe E.
-
When purge is complete turn off valve E, pressurising the section to line pressure.
-
Test installed fittings with leakage detection fluid. Wash off with clean water.
-
While carefully monitoring pressure gauges, remove safety stops and slowly release upstream<br>squeeze-off 3.
-
While carefully monitoring pressure gauges, remove safety stops and slowly release upstream<br>squeeze-off 4
-
Close valve G<br>
-
Isolate purge valves at H and J and remove rider.
Re-commission main by controlled release of a squeeze-off:
-
Close valves G and, ensuring H is in the closed position.
-
Remove safety stops and release downstream squeeze-off.
-
Remove safety stops and release upstream squeeze-off.
-
Close valve(s) F & K (K where applicable).
-
While carefully monitoring pressure gauges, remove safety stops and slowly release upstream<br>squeeze-off 3 and purge through vent E until independent reading of 90% gas in air (GIA) are<br>obtained.<br>
-
When purge is complete turn off valve E. pressurising the section to line pressure.
-
Test installed fittings with leak detection fluid.
-
While carefully monitoring pressure gauges, remove safety stops and slowly release downstream<br>squeeze-off 4.
By-pass & vent point de-commissioning:
-
Isolate vent points E, F, G and K (K where applicable)
-
Remove completion caps from top tees and re-insert pipe cutter onto the main at the vent<br>connection. Check seal using leak detection fluid.
-
Remove vents; install electrofusion caps on the outlets of the saddle fusion tees. Raise integral <br>PE cutters and fit completion caps. Test electrofusion and completion cap. Wash off with clean <br>water.<br>
-
Slowly close bypass valve B whilst monitoring network pressure for 10 minutes to ensure <br>renewed section is supplying downstream.
-
Slowly close bypass valve A and vent bypass by opening vent valve C and checking the pressure<br>reduces to zero.
-
Close vent valve C.
-
Connect air supply to valve C, open valve C and D and direct purge bypass to vent D using no <br>more than 1/3<br>rd. of the mains operating pressure.
-
Remove bypass pipe work.
-
Remove squeeze-offs 1and 4 and re-round PE main.
-
Seal bypass connections at tapping tees/saddles, cut and cap PE.
-
Test with leakage detection fluid. Wash with clean water.
-
Apply squeeze-off applied tape to the main at all squeeze-off positions.
-
Follow Section E1, (SGN/WI/ML/2) for squeeze-offs passing gas and for
other fault finding:
Sign off
-
Name of assessor
-
Pass or refer for further training