Information

  • Document No.

  • Client

  • Building

  • Conducted on

  • Prepared by

  • Location

Table 6.4.1.2 - Monthly Tests

  • All previous defects and non-conformance's attended to and recorded.

  • 1.1 - Inspect audible and visual external alarms.

  • 1.2 - Inspect condition of Control and Indicating Equipment.

  • 1.3 - Inspect the battery enclosure.

  • 1.2 - Check replacement element and tool for MCP's

  • 1.4 - Simulate an alarm condition and confirm indications and alarms function correctly.

  • 1.5 - Simulate an alarm and confirm the occupant warning system functions correctly.

  • 1.6 Confirm isolate / disable condition functions correctly.

  • 1.7 Test filament type visual indicators.

  • 1.8 - Inspect zone block plan.

  • 1.9 Baseline Data Documentation - CHECK that baseline data is available and legible.

  • Six Monthly Service Activities (Required for Special Hazards Systems ONLY)

Actions required by Table 6.4.1.3

  • All previous defects and non-conformance's attended to and recorded.

  • 2.1 - Complete monthly service.

  • 2.2 - Check local control station (LCS).

  • 2.3 - Inspect visual warning devices.

  • 2.4 - Test all discharge inhibit devices and confirm

  • 2.4a - Automatic discharge prevented.

  • 2.4b - Stops and resets discharge sequence.

  • 2.4c - Activated visual indicator at LCS and FIP.

  • 2.4d - Audible indication activated.

  • 2.4e - Manual discharge switch continues to function.

  • 2.5 - Test manual initiate function.

  • 2.6 - Confirm system inoperative visual warning devices activate as a result of:

  • 2.6a - Operation of service switch.

  • 2.6b - Fault in the discharge actuator circuit.

  • 2.6c - Operation of lock off valve.

  • 2.6d - Operation of manual inhibit switch.

  • 2.6e - Isolation or fault in the fire detection system.

  • 2.7 - Test and verify the system operation and logic.

  • 2.8 - Test actuator circuit fault indication.

  • 2.9 - Test actuators operate correctly.

  • Annual Service Activities

Table 6.4.1.4 - Annual Tests

  • All previous defects and non-conformance's attended to and recorded.

  • 3.1 - Complete all monthly and six monthly services.

  • 3.2 - Check manual call points.

  • 3.3 Manual Call Points - TEST the operation of each MCP

  • 3.4 - Inspect 'other' alarm indicating devices.

  • 3.5 - Test panel switches and keypads.

  • 3.6 - Test visual indicators and alphanumeric displays.

  • 3.7 - Measure and verify battery capacity, Record details below.

  • Standby Current (mA)

  • Alarm Mode Current (Ia) A

  • Required Quiescent Standby Time (hrs)

  • Required Alarm Mode Standby Time (hrs)

  • Calculated 20h rate Capacity (Ah)

  • Age factor (calculated capacity x1.25) (Ah)

  • Required Capacity (Ah)

  • Required Capacity (Ah)

  • 3.8 - TEST detectors as specified in Appendix G and confirm correct alarm zone indication. Where the detectors are used as part of special hazards systems 100% of the detectors SHALL be tested yearly.

  • 3.9 - Test audibility of Occupant Warning System (OWS).

  • 3.10 - Measure OWS sound pressure level (one point per amplifier) Record below.

  • Amplifier
  • Sound level (dBA)

  • 3.11 - Test at least 20% of installed alarm acknowledgement facilities.

  • 3.12 - Test alarm investigation facility.

  • 3.13 - Verify Battery Condition.

  • Date last replaced.

  • Final test voltage (V)

  • Battery Capacity (AH)

  • 3.15 - Investigate and report on component service life.

  • 3.16 - Confirm baseline data.

  • 3.17 - SURVEY all areas of the building from floor level.
    Note: the purpose of the annual survey is to identify component degradation and building changes that may impact on the system or equipment performance. It is a visual inspection, typically conducted from floor level. it is designed to identify the potential for further investigation to assess any changes to the occupancy, environment or building that may affect the performance of the fire safety system or equipment.
    Where the outcome of the survey identifies the need for further investigation, it is recommended that a Fire Safety Audit in accordance with AS 4655 be undertaken by an appropriately qualified professional. An audit will support a responsible entity in satisfying themselves that nay changes made to the fire safety system, building or occupancy are fully compliant with any applicable legislative requirements.

  • Has the occupant been in the building for the previous 12 months?

  • Have there been any additions or alterations (minor or major) made to the building in the last 12 months?

  • Have there been any changes made to the occupancy of the building?

  • Have any of the fire safety systems or equipment in the building been altered or undergone major repairs in the last 12 months?

  • 3.17a - Check fire detection system for non-approved alterations.

  • 3.17b - Check detection devices and remote indicators.

  • 3.17c - Check for false alarm triggers.

  • 3.17d - Check cabling installation.

  • 3.17e - Check mounting of CIE components.

  • Further action or investigation recommended.

  • 3.18 - Simulate and verify interfaced system initiation.

  • Door release

  • Roof vents

  • Warning system / intercom

  • Plant shutdown

  • Fuel Isolation

  • Elevator override

  • Stair pressurisation

  • Smoke control / exhaust

  • HVAC controls

  • Special Hazards

  • Notification and alert systems

  • Additional interfaced systems.

  • Interfaced System
  • 3.18 Interfaced System Initiation - Simulate alarms to verify that each interface transmission path initiates the corresponding interfaced system in accordance with the approved design.

  • Smoke Hazard Management Systems (where fitted).

  • 3.19 - Check the FFCP latches until reset.

  • 3.20 - Check manual override controls.

  • 3.21 - Check airflow fault indicator operation.

  • 3.22 - Check open-circuit fault indicator operation.

  • 3.23 - Check closed-circuit fault indicator operation.

  • 3.24 - Check electrical phase fail fault indicator.

  • 3.25 - Check fan running indicator operation.

  • 3.26 - Check fan stopped indicator operation.

  • 3.27 - Check fan fault indicator operation.

  • Special Hazard Systems (where fitted).

  • 3.28 - Test operation of status monitoring devices.

  • 3.29 - Confirm operation of suppression system directional valves.

  • 3.30 - Test and verify the discharge time delay.

  • 3.31 - Test agent release indication operation.

  • Five Yearly Service

Table 6.4.1.5 - Five Yearly Tests

  • All previous defects and non-conformance's attended to and recorded.

  • 4.1 - Complete all monthly, six monthly and yearly service items.

  • 4.2 - Test supervised circuits.

  • 4.3 - Test fault condition throughout system.

  • 4.4 - Verify operation of addressable short circuit isolators.

  • 4.5 - Test power supply supervision fault functions.

  • 4.6 - Test collective detection circuits fault indication.

  • 4.7 - Test and verify system interfaces.

  • 4.8 - Measure and verify OWS speaker circuit impedance.

  • Speaker Circuit
  • Baseline impedance (ohms)

  • Measured impedance (ohms)

  • 4.9 - Test monitoring links.

  • 4.10 - Test alarm verification facility.

Completion

  • Technician

  • Client

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.