Information
-
Site
-
Conducted on
-
Prepared by
-
Location
-
Fire Door Inspection
Fire Door
Door Location
-
Location
-
BM TRADA Q-Mark
- FD30
- FD60
- FD90
- FD120
- Not Fitted
-
Fire Door Signage
-
Comments
About the Door
-
Does the door leaf sit against the door stop and is it free from distortion?
-
Describe the issues present
-
If the door is veneered or lipped, is the glue still holding these products firmly in place?
Door Frame
-
Is the frame in a good state of repair?
-
Is the door frame securely attached to the wall?
-
If a planted door stop is present, is it firmly attached?
-
Is the frame to door leaf gap consistently 4mm maximum?
Door Seals
-
Are intumescent seals in place?
-
What Size and Type are they
- 10mm Flat
- 10mm Combined
- 15mm Flat
- 15mm Combined
- More than 15mm
- Surface mounted
-
Are the seals well attached inside the groove in the door leaf or frame?
-
Are brush or fin type seals free from damage?
-
Are the smoke seals continuous around the door leaf or door frame?
Hinges
-
Are there a minimum of 3 hinges with all the screws fitted?
-
Are all the screws the correct size?
-
Are the hinges free from non-combustible packaging?
-
Are the hinges CE marked
-
Comment on the hinges fitted
Door Closers
-
Open the door to 75mm or 5 degrees. Does it close and engage with the latch?
-
Is the closer securely attached to the door and the frame?
-
Is the closer free from damage?
-
If unlatched does the closer hold the door in line with the frame and intumescent seal?
-
If hung in pairs, do they close in line if both are opened and released together?
-
If hold open devices is used, is it electronically or sound opperated
- Electronic Magnet type (floor or wall)
- Electronic Closer type
- Sound activated type
-
Does the hold open device release the door when required?
Lock & Latch
-
Does the latch hold the door firmly in the frame without rattling
Glazing & Glass
-
Is the intumescent seal continuous and attached to the glass and bead?
-
Are the glazing beads well attached to the frame and free from damage?
-
Is the glass free from cracking or damage
-
If the glass has been replaced is it fire rated glass?
Threshold Gap
-
Is there a consistent gap under the door that allows it to swing without touching the floor covering?
-
Is the door to floor covering gap consistently 8mm (3mm for smoke control) or less when the door is closed?
-
If the door leaf is fitted with a threshold seal, does the seal make contact with the floor covering when the door is closed?
Compliance
-
Compliance Rating
Comments
-
Add Comments to this report