Information

  • Audit Title

  • Conducted on

  • Prepared by

  • Location

Section 1: Ground Floor

Main Entrance/Reception/M D,s Office/H R Office

  • Main Entrance

  • Do all light switches and electrical sockets appear in good condition?

  • Is the fire control panel indicating that it is operational?

  • Are the fire extinguishers (1 & 2) easily accessible?

  • Is the foam fire extinguisher (1) in a satisfactory condition?

  • Is the CO2 fire extinguisher (2) in a satisfactory condition?

  • Is the break glass call point (1) easily accessible and indicating that it is operational?

  • EMERGENCY LIGHTING KEY SWITCH 1<br>Is the illuminated final exit sign (1) next to the main exit working?

  • EMERGENCY LIGHTING KEY SWITCH 1<br>Is the external emergency light (1) above the main entrance/exit working?

  • Reception - M D's Office - H R Office

  • Is the fire exit sign above the doorway (1) present?

  • Do all light switches and plug sockets appear in good condition?

  • Do all plugs and leads appear in good condition?

  • Are extension leads run under carpets, rugs or across doorways?

  • Does the fire door (1) operate freely?

  • Is the fire door (1) free from obstruction?

  • Is the fire door (1) wedged open/shut?

  • Is the fire door (1) identified with the correct ID/notice?

  • Is the escape route from the reception area to the car park clear of obstructions?

Bottom of Stairs/Kitchen/Toilets/Boardroom

  • Bottom of Stairs

  • Is the fire exit sign (2) above the doorway to the main exit/entrance present?

  • Do all light switches and plug sockets appear in good condition?

  • Is the stairwell clear of storage and clutter?

  • Are the contents in the emergency Grab Bag correct and up to date?

  • Is the fire exit sign (3) above the doorway to the kitchen present?

  • EMERGENCY LIGHTING KEY SWITCH 2<br>Is the emergency light (2) at the bottom of the stairs working?

  • Corridor to Boardroom

  • Is the electrical circuit panel identified, locked and the surrounding 3 feet of space clear?

  • Are the panels circuit breakers identified?

  • Does the electrical socket appear in good condition?

  • Is the fire exit sign (4) above the doorway to the stairs present?

  • Are the details on the Health & Safety noticeboard up to date?

  • Is the fire extinguisher (5) easily accessible?

  • Is the CO2 fire extinguisher (5) in a satisfactory condition?

  • EMERGENCY LIGHTING KEY SWITCH 2<br>Is the emergency light (3) outside the Gents toilets working?

  • EMERGENCY LIGHTING KEY SWITCH 2<br>Is the emergency light (4) outside the Boardroom working?

  • Is the escape route from the Boardroom to the main entrance clear of obstructions?

  • Corridor to kitchen

  • Does the light switch appear in good condition?

  • Are the fire extinguishers (3 & 4) easily accessible?

  • Is the foam fire extinguisher (3) in a satisfactory condition?

  • Is the CO2 fire extinguisher (4) in a satisfactory condition?

  • EMERGENCY LIGHTING KEY SWITCH 3<br>Is the emergency light (5) in Reception working?

  • EMERGENCY LIGHTING KEY SWITCH 3<br>Is the emergency light (6) in the corridor working?

  • Kitchen

  • What is the hot water temperature of the kitchen sink (Min 50)?

  • What is the cold water temperature of the kitchen sink (Max 20)?

  • Do all light switches and electrical sockets appear in good condition?

  • Do all plugs and leads appear in good condition?

  • Does the fire door (2) operate freely?

  • Is the fire door (2) free from obstruction?

  • Is the fire door (2) wedged open/shut?

  • Is the fire door (2) identified with the correct ID/notice?

  • EMERGENCY LIGHTING KEY SWITCH 4<br>Is the emergency light (7) in the Kitchen working?

  • Is the escape route from the kitchen area to the main entrance clear of obstructions?

  • Toilets/Storeroom

  • Do all light switches and electrical sockets in the Gents toilets appear in good condition?

  • What is the hot water temperature of the Gents toilets (Min 50)?

  • What is the cold water temperature of the Gents toilets (Max 20)?

  • EMERGENCY LIGHTING KEY SWITCH 5<br>Is the emergency light (8) in the Gents toilets working?

  • Do all light switches and electrical sockets in the Storeroom appear in good condition?

  • EMERGENCY LIGHTING KEY SWITCH 5<br>Is the emergency light (9) in the Storeroom working?

  • Do all light switches and electrical sockets in the Ladies toilets appear in good condition?

  • What is the hot water temperature of the Ladies toilets (Min 50)?

  • What is the cold water temperature of the Ladies toilets (Max 20)?

  • EMERGENCY LIGHTING KEY SWITCH 6<br>Is the emergency light (10) in the Ladies toilets working?

  • Do all light switches and electrical sockets in the Disablled toilets appear in good condition?

  • EMERGENCY LIGHTING KEY SWITCH 6<br>Is the emergency light (11) in the Disabled toilet working?

  • What is the hot water temperature of the Disabled toilet (Min 50)?

  • What is the cold water temperature of the Disabled toilet (Max 20)?

  • Boardroom

  • Do all light switches and electrical sockets appear in good condition?

  • Do all plugs and leads appear in good condition?

  • Are extension leads run under carpets, rugs or across doorways?

  • Is the escape route from the Boardroom area to the main entrance clear of obstructions?

Ground Floor Office

  • Ground Floor Offices

  • Does the fire door (3) operate freely?

  • Is the fire door (3) free from obstruction?

  • Is the fire door (3) wedged open/shut?

  • Is the fire door (3) identified with the correct ID/notice?

  • Is the fire exit sign (5) above the doorway present?

  • Are the fire extinguishers (6 & 7) easily accessible?

  • Is the foam fire extinguisher (6) in a satisfactory condition?

  • Is the CO2 fire extinguisher (7) in a satisfactory condition?

  • Do all light switches and electrical sockets appear in good condition?

  • Do all plugs and leads appear in good condition?

  • Are extension leads run under carpets, rugs or across doorways?

  • Are the fire exit signs (6 & 7) on the back wall present?

  • EMERGENCY LIGHTING KEY SWITCH 7<br>Is the emergency light (12) near the First Aid Station working?

  • EMERGENCY LIGHTING KEY SWITCH 7<br>Is the emergency light (13) in the finance area working?

  • EMERGENCY LIGHTING KEY SWITCH 7<br>Is the emergency light (14) in the finance area working?

  • Are the fire extinguishers (8 & 9) easily accessible?

  • Is the foam fire extinguisher (8) in a satisfactory condition?

  • Is the CO2 fire extinguisher (9) in a satisfactory condition?

  • Is the break glass call point (2) easily accessible and indicating that it is operational?

  • EMERGENCY LIGHTING KEY SWITCH 7<br>Is the illuminated final exit sign (2) above the emergency exit working?

  • EMERGENCY LIGHTING KEY SWITCH 7<br>Is the external emergency light (15) above the emergency exit working?

  • Are the contents in the emergency Grab Bag correct and up to date?

  • Is the escape route from the Fire Door to the Emergency Exit clear of obstructions?

  • Sack Trolley

  • Is the sack trolley in a satisfactory condition?

  • Is the weight limit indicated on the sack trolley?

  • First Aid

  • Ground Floor First Aiders on Duty

  • Is the list of First Aiders up to date?

  • Are the contents of the First Aid Box correct and within the stated expiry date(s)?

Section 2: First Floor

Staircase, Landing & Server Room

  • Staircase

  • Are the threshers fixed securely?

  • Are the carpet tiles secure?

  • Is the bannister fixed and secure?

  • Server Room

  • Is the fire extinguisher (12) easily accessible?

  • Is the CO2 fire extinguisher (12) in a satisfactory condition?

  • EMERGENCY LIGHTING KEY SWITCH 8<br>Is the emergency light (16) working?

  • EMERGENCY LIGHTING KEY SWITCH 8<br>Is the emergency light (17) working?

  • Does the fire door (4) operate freely?

  • Is the fire door (4) free from obstruction?

  • Is the fire door (4) wedged open/shut?

  • Is the fire door (4) identified with the correct ID/notice?

  • Landing

  • Is the fire exit sign (8) above the Server Room doorway present?

  • Do all light switches and electrical sockets appear in good condition?

  • Are the fire extinguishers (10 & 11)) easily accessible?

  • Is the Foam fire extinguisher (10) in a satisfactory condition?

  • Is the CO2 fire extinguisher (11) in a satisfactory condition?

  • Is the break glass call point (3) easily accessible and indicating that it is operational?

  • EMERGENCY LIGHTING KEY SWITCH 9<br>Is the emergency light (19) at the top of the stairs working?

  • EMERGENCY LIGHTING KEY SWITCH 9<br>Is the emergency light (18) on the stairs working?

  • Is the escape route from the top of the stairs to the main entrance clear of obstructions?

First Floor Offices

  • Is the fire exit sign (9) above the entrance present?

  • Are the fire extinguishers (13 & 14) easily accessible?

  • Is the Foam fire extinguisher (13) in a satisfactory condition?

  • Is the CO2 fire extinguisher (14) in a satisfactory condition?

  • Is the electrical circuit panel identified, locked and the surrounding 3 feet of space clear?

  • Are the panels circuit breakers identified?

  • Are the fire exit signs (10 & 11) on the back wall present?

  • What is the hot water temperature of the kitchen sink (Min 50)?

  • What is the cold water temperature of the kitchen sink (Max 20)?

  • Do all light switches and electrical sockets appear in good condition?

  • Do all plugs and leads appear in good condition?

  • Are extension leads run under carpets/ rugs or across doorways?

  • EMERGENCY LIGHTING KEY SWITCH 10<br>Is the emergency light (20) in the entrance area working?

  • EMERGENCY LIGHTING KEY SWITCH 10<br>Is the emergency light (21) in the kitchen area working?

  • EMERGENCY LIGHTING KEY SWITCH 10<br>Is the emergency light (22) in the centre of the office working?

  • EMERGENCY LIGHTING KEY SWITCH 10<br>Is the emergency light (23) in the compliance area working?

  • EMERGENCY LIGHTING KEY SWITCH 10<br>Is the illuminated final exit sign (3) above to the emergency exit working?

  • EMERGENCY LIGHTING KEY SWITCH 10<br>Is the external emergency light (24) above the emergency exit working?

  • Does the emergency exit break glass unit function correctly?

  • Are the fire extinguishers (15 & 16) easily accessible?

  • Is the foam fire extinguisher (15) in a satisfactory condition?

  • Is the CO2 fire extinguisher (16) in a satisfactory condition?

  • Is the break glass call point (4) easily accessible and indicating that it is operational?

  • Is the escape route from the First Floor Office entrance to the First Floor emergency exit clear of obstructions?

  • Is the escape route from the top of the fire escape to the car park clear of obstructions?

  • Are the contents in the emergency Grab Bag correct and up to date?

  • First Aid

  • First Floor First Aiders on Duty

  • Are the contents of the First Aid Box correct and within the stated expiry date(s)?

  • Is the list of First Aiders up to date?

Section 3: General

Electrical, Hazardous Materials, Fire Safety, Emergency Plan, Smoking & Housekeeping

  • Electrical

  • Are circuit breakers regularly tripping?

  • Are all electrical appliances and extension leads PAT tested annually

  • Hazardous Materials

  • Are Material Safety Data Sheets available on all hazardous materials ulitised within the site?

  • Are Material Safety Data Sheets readily available for staff where chemicals are used or stored?

  • Is Personal Protective Equipment available for staff using chemicals?

  • Fire Safety

  • Fire Wardens On Duty

  • Has an annual inspection of all fire extinguishers taken place in the last twelve months?

  • Do all members of staff know where fire extinguishers are located?

  • Has at least one fire drill per shift been conducted in the last twelve months?

  • Do staff demonstrate quick and complete control during evacuation drills?

  • Is each room checked/cleared and a head count conducted?

  • Do fire drills simulate realistic situations/conditions?

  • Did the fire alarm function properly during the drill(s)?

  • Are drills performed at unexpected times?

  • Are staff routinely trained to dial emergency phone numbers to report alarms?

  • Are there any firewall penetrations that are not sealed?

  • Have smoke detectors been tested within the last twelve months?

  • Is an operator on duty at all times at the fire alarm monitoring centre?

  • Emergency Plan

  • Has the emergency plan been reviewed/approved within the last twelve months?

  • Is there an emergency communication back up?

  • Is the current evacuation plan posted/accessible to all members of staff?

  • Are all vehicles reverse parked in the car park?

  • Is the site smoking policy posted/accessible to all members of staff throughout the site?

  • Are designated smoking areas clean and free of potential hazards?

  • Are staff complying with the smoking policy?

  • Housekeeping

  • Are all waste containers emptied/cleaned on a daily basis

  • Does the site have regular waste collections to keep combustible materials at an acceptable level?

  • Additional Comments, Concerns or Issues

  • Completed By:

  • Position:

  • Date

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.