Title Page
General Information
-
Project:
-
Contractor:
-
Conducted on:
-
Location:
-
Completed By:
-
Record Number:
Compliance Questions
1. Documents
-
1.1: Is the approved Contractor procedure present on-site?
-
Provide evidence
-
1.2: Is the approved Inspection & Test Plan (ITP) available on-site?
-
Provide a clear photo of the document cover page.
-
1.3: Is the isometric available?
-
Provide a photo of the BoM
2. Personnel
-
2.1: Are all personnel involved in flange assembly certified in bolting and flange management?
-
-
2.2: Is proof of qualification (card/certificate) available for all personnel working on flange management?
-
-
2.3: Is a Contractor QC Inspector present on-site to verify activities?
3. Equipment
-
3.1: Are all torque or tensioning tools uniquely identified with a serial number?
-
3.2: Is all bolting equipment calibrated and certified for use?
-
3.3: Is the equipment in good working order and free from damage?
4. Process
-
4.1: Are workers aware of their specific roles and responsibilities according to the flange management procedure?
-
4.2: Has a Toolbox talk been completed before work begins?
-
4.3: Is the QC Inspector familiar with ITP requirements?
-
4.4: Have bolts, gaskets, and nuts been checked and verified as correct prior to tightening?
-
4.5: Are flange faces free from rust, dirt, and contamination before assembly?
-
4.6: Is the correct bolt tightening sequence followed according to the criss-cross method?
-
4.7: Are flange gaps acceptable before tightening, ensuring no visible misalignment
-
4.8: Is Molykote 1000 lubricant applied correctly to all bolts?
-
4.9: Are stud and nut stamps visible?
-
4.10: Are the correct tightening values known?
-
-
4.11: Is the tensioning value correctly applied for each stage?
-
-
4.12: After tightening, is the joint visually inspected to ensure an even flange gap and obstruction-free bolting?
-
4.13: Has the final stage 100% tightening verification been completed?
5. Records
-
5.1: Has a Flange Management tag been applied to the joint upon completion?
-
5.2: Has the P02A (ITR) for joint integrity been completed accurately?
-
5.3: For joints not hydrotested, have these been recorded a witness joint on the joint map?