Information

  • Site conducted

  • Document No.

  • Audit Title

  • Client / Site

  • Conducted on

  • Prepared by

  • Location
  • Personnel

GENERATOR ROOM SAFETY AUDIT

I. GENERAL AND ADMINISTRATIVE

A. Electrical

  • 1. Are the lighting circuits properly wired and do they have adequate<br>fuses and circuit breakers?

  • 2. Is all permanent wiring in approved conduit and free of "juryrigging" such as extension cords in place of proper electrical cabling?

  • 3. Does the supervisor enforce a "Lockout/Tagout" policy for electrical<br>machinery repair?

  • 4. Is all electrical equipment effectively grounded IAW, Chapter 8 of<br>Section 1?

  • 5. Is the transfer switch tested monthly and are the tests properly<br>documented?

B. Chemical

1. General

  • a. Do the employees understand the hazards of and protective<br>measures required by any chemicals which are used in the<br>generator room, particularly solvents?

  • b. Are employees handling solvents and acids equipped with and<br>do they use the necessary protective equipment such as gloves,<br>eye protection, respirators etc?

  • c. Are solvents limited to non-flammable solvents (such as<br>"Simple Green") as much as possible?

2. Flammables

  • a. Is the battery charging and maintenance area properly<br>ventilated to preclude the buildup of hydrogen gas generated<br>during battery charging operations?

  • b. Is the generator room free of flammables/combustibles except<br>for the fuel for the generator's prime mover?

  • c. If not, are flammables and combustibles limited to small<br>amounts needed in the immediate area and are they stored in<br>approved UL/FM flammable liquids storage containers?

3. Asphyxiate

  • a. Is the exhaust system gas tight to minimize the exhaust gases in<br>the generator room?

  • b. Is the exhaust stack so terminated that it is clear of vents, air<br>intakes, or other openings which would allow the exhaust gases<br>to reenter the generator room, or enter another building?

C. Ignition Sources

  • 1. Does the supervisor enforce "No Smoking" requirements?

  • 2. Is the exhaust piping properly insulated where it goes through the<br>wall. If it is a rated wall the fire stopping material must carry the<br>same rating as the wall.

  • 3. Are there other ignition sources such as portable heaters, dryers,<br>coffee pots, hot plates, etc. and are they properly controlled?

D. Mass

  • 1. Is the foundation and the skid which supports the engine-generator<br>set inspected regularly and is this documented?

E. Rotating Equipment

  • 1. Are fans or any other moving/rotating equipment less than 2.13<br>meters (7 feet) above the floor properly guarded?

  • 2. Are all drive belts and other exposed rotating equipment properly<br>guarded?

F. Noise

  • 1. Is the steady state noise level in the generator room below the limits<br>in Table 1.1.1 (85 decibels).

  • 2. If not, is the space properly placarded to indicate the need for<br>hearing protection?

  • 3. Is hearing protection and the training in its proper use available and<br>used by the employees when necessary?

  • 4. Has the exhaust piping, beyond the flexible pipe section been<br>wrapped and insulated to reduce the noise level in the room?

G. Static Electricity (Lightning)

  • 1. If the location is subject to lightning, is the building properly<br>protected against lightning strikes or secondary ground surges?

  • 2. Is the lightning protection system inspected regularly in accordance<br>with Appendix B of NFPA 78 (Lightning Protection Code)? (As<br>follows:)<br>B-2.2 Maintenance Procedures.<br>B-2.2. 1 Periodic maintenance programs should be established for all<br>lightning protection systems. The frequency of maintenance<br>procedures is dependent on the following:<br>(a) Weather related degradation.<br>(b) Frequency of stroke damage.<br>(c) Protection level required.<br>(d) Exposure to stroke damage.<br>B-2.2.2 Lightning protection system maintenance procedures should<br>be established for each system and should become a part of the<br>overall maintenance program for the structure which it protects. A maintenance program should contain a list of more or less<br>routine items that may serve as a check list so that a definite<br>maintenance procedure can be followed regularly. It is the<br>repeatability of the procedures that enhance the effectiveness of<br>a good maintenance program.<br> A good maintenance program should contain provisions for the<br>following:<br>(a) Inspection of all conductors and system components<br>(b) Tightening of all clamps and splicers.<br>(c) Measurement of lightning protection system resistance.<br>(d) Measurement of resistance of ground terminals .<br>(e) Inspection of and/or testing of surface protection devices<br>to determine their effectiveness compared with similar<br>new devices<br>(f) Refastening and tightening of components and conductors<br>as required.<br>(g) Inspection and testing as required to determine if the<br>effectiveness of the lightning protection system has been<br>altered due to additions to or changes in the structure.<br>B-2.3 Maintenance Records. Complete records shall be kept of all<br>maintenance procedures and routines and shall include<br>corrective actions that have been or will be taken. Such records<br>provide a means of evaluating system components and their<br>installation. They also serve as a basis for reviewing<br>maintenance procedures as well as updating preventive<br>maintenance programs

H. Personnel

  • 1. Does the supervisor ensure that all employees know and adhere to<br>safety requirements in the generator room operation?

  • 2. Does the supervisor have a qualification and training outline to<br>identify initial and any follow-up training?

  • 3. Does the supervisor ensure that PPE, to include hearing protection, is<br>used properly?

  • 4. Are the proper warning/caution signs in a language which the work<br>force can understands?

  • 5. Are they posted where the employees can see them?

  • 6. Is the lighting adequate in all the work areas?

  • 7. Are maintenance/operational testing procedures established and<br>documented?

  • 8. Does the supervisor enforce a "Lockout/Tagout" policy for<br>machinery repair?

  • 9. Does the room have a current/system chart posted for quick<br>reference in emergencies?

J. Fire Protection

  • 1. Is good housekeeping practiced at all times? Is the trash, taken out<br>every night?

  • 2. Are oil or fuel contaminated rags placed into a covered metal<br>container, or are they removed from the generator room?

  • 3. Does the supervisor have a current emergency and evacuation plan?<br>Has it been communicated to the employees?

  • 4. Does the generator room have a working fire detection or auto-matic<br>fire suppression system? Are they regularly maintained and tested?

  • 5. Does the generator room have the required number and types of fire<br>extinguishers and are they properly located in accordance with<br>FBO/OPS/FIR's requirements? Have the employees been trained in<br>the proper use of the fire extinguishers?

  • 6. Have there been any changes in operations, or procedures which<br>would require re-positioning of the present fire extinguishers?

  • 7 Are bilingual "NO SMOKING" signs posted and is the policy<br>enforced?

  • 8. Are the rated walls properly sealed to preclude the passage of gases,<br>smoke, other products of combustion and flame?

  • I certify that all the information in the above report are correct and true.

  • Ariel Mariano, A/POSHO

  • Gus Kosmas, POSHO

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.