Title Page

  • Conducted on

  • Prepared by

  • Location

INSPECTOR

  • Add signature

VCR'S & OCR's AND OIL SWITCHES

  • APPEARANCE OK

  • BUSHINGS CLEAN, GOOD CONDITION

  • FREE FROM OIL LEAKS

  • COUNTER READINGS RECORDED

AIR-BREAK AND DISCONNECT SWITCHES

  • APPEARANCE OK

  • INSULATORS OK

  • GROUND CONNECTION TO HANDLE OK

BYPASS SWITCHES

  • APPEARANCE OK

  • INSULATORS OK

MISCELLANEOUS ELECTRICAL EQUIPMENT

  • ARRESTER APPEARANCE OK

  • ARRESTER CORRECTLY CONNECTED

  • SWITCH STICKS OK, PROPERLY STORED

  • PHASES PROPERLY IDENTIFIED

  • CIRCUITS PROPERLY IDENTIFIED

  • BUSES AND CONNECTIONS OK

  • BURNED OUT LAMPS REPLACED

  • OVERHEAD GROUND WIRE OK

  • CABINETS AND CUBICLES OK

SAFETY

  • EQUIPMENT GROUNDS OK

  • FENCES AND GATES GROUNDED

  • EXITS, WALKWAYS AND DRIVEWAYS CLEAR

  • SUB ENCLOSURES FREE OF STORED MATERIAL & EQUIPMENT

  • NESC CLEARANCES COMPLIED WITH

  • SUBSTATION AREA PROPERLY LIGHTED

  • YARD CLEAN AND FREE OF WEEDS

  • GATES PROPERLY LOCKED

  • SUITABLE WARNING SIGNS ON FENCES

YARD AND STRUCTURES

  • FENCES AND GATES ADEQUATE

  • YARD PROPERLY SURFACED

  • STRUCTURE PAINT OK

  • FENCE AND GATE PAINT OK

POWER TRANSORMERS

  • APPEARANCE OK

  • BUSHINGS CLEAN, GOOD CONDITION

  • OIL LEVELS AND GAUGES OK

  • FREE FROM OIL LEAKS

  • THERMOMETERS OK, MAXIMUMS RESET

  • AUX. COOLING EQUIPMENT OK

  • GAS PRESSURE OK

REGULATORS

  • APPEARANCE OK

  • BUSHINGS CLEAN, GOOD CONDITION

  • OIL LEVELS AND GAUGES OK

  • FREE FROM OIL LEAKS

  • THERMOMETERS OK, MAXIMUMS RESET

  • MECHANISMS OK

  • INDICATING LIGHTS OK

  • INDICATING GLASS COVERS INTACT

  • CABINET GASKETS WEATHER TIGHT

  • COUNTER READINGS RECORDED

ADDITIONAL COMMENTS

TRANSFORMER

UNIT 69/12.47kv

MANUFACTURE = (T&R VT )

SERIAL# ( 131031-13 )

TAP SETTING ( 67,275 )

OIL LEVEL

  • OIL TEMP

  • TANK PRESSURE

BUSHING CONDITION

  • BUSHING CONDITION

REGULATORS

DRAG HAND POSITIONS

A-PHASE

  • CURRENT POSITION

  • MINIMUM POSITION

  • MAXIMUM POSITION

  • NUMBER OF OPERATIONS

  • RESET DRAG HANDS

  • MAXIMUM CURRENT

  • POWER FACTOR MAX / MIN

  • KVA MAX

  • OUTPUT VOLTAGE

B-PHASE

  • CURRENT POSITION

  • MINIMUM POSITION

  • MAXIMUM POSITION

  • NUMBER OF OPERATIONS

  • RESET DRAG HANDS

  • MAXIMUM CURRENT

  • POWER FACTOR MAX / MIN

  • KVA MAX

  • OUTPUT VOLTAGE

C-PHASE

  • CURRENT POSITION

  • MINIMUM POSITION

  • MAXIMUM POSITION

  • NUMBER OF OPERATIONS

  • RESET DRAG HANDS

  • MAX CURRENT

  • POWER FACTOR MAX / MIN

  • KVA MAX

  • OUTPUT VOLTAGE

REGULATOR SETTINGS

A-PHASE

  • MANUFACTURE (COOPER) SERIAL # ( 0750015281 ) TYPE / AMPS ( VR32 B / 100 ) SET VOLTAGE ( 123 ) BAND WIDTH 2 TIME DELAY ( 30 ) LDC R / X ( 2.8 / 2.1 ) CONTROL TYPE ( CL6 )

B-PHASE

  • MANUFACTURE (GE ) SERIAL # ( M045951PLN ) TYPE / AMPS ( VR32 B / 50 ) SET VOLTAGE ( 122 ) BAND WIDTH 2 TIME DELAY ( 30 ) LDC R / X ( 0 / 0 ) CONTROL TYPE ( CL 6B )

C-PHASE

  • MANUFACTURE (COOPER) SERIAL # ( 979105481 ) TYPE / AMPS ( VR32 B / 50 ) SET VOLTAGE ( 122 ) BAND WIDTH 2 TIME DELAY ( 30 ) LDC R / X ( 0 / 0 ) CONTROL TYPE ( CL 5C )

OIL CIRCUIT RECLOSERS

To find Demand metering amps. 1. Press METERING button, press down arrow to "Demand Metering", arrow down to "Reset Demand Phase Amps", press ENTER, record max demand an d peak amps below. To Reset Demand and Peak Amps 1. Press METERING button, press down arrow to "Demand Metering", arrow down to "Reset Demand Peaks", press F4. "METER ARE RESET" should appear for 2 seconds.

ROUTE No. 1- NOVA TS

  • A- COUNTER READINGS

  • B- COUNTER READINGS

  • C- COUNTER READINGS

  • GRD

  • A-MAX AMPS DEMAND/PEAK

  • B- MAX AMPS DEMAND/PEAK

  • C-MAX AMPS DEMAND/PEAK

ROUTE No. 3 - NOVA TS

  • A- COUNTER READINGS

  • B- COUNTER READINGS

  • C- COUNTER READINGS

  • GRD

  • A-MAX AMPS DEMAND/PEAK

  • B-MAX AMPS DEMAND/PEAK

  • C-MAX AMPS DEMAND/PEAK

ROUT No. 4

  • A- COUNTER READINGS

  • B- COUNTER READINGS

  • C- COUNTER READINGS

  • GRD

  • A-INSTANT AMPS

  • B-INSTANT AMPS

  • C-INSTANT AMPS

69 KV BAY

PCB GILDFORD #1152 (WH)

  • SPRING CHARGED

  • SF6 PRESSURE

  • OPERATION COUNTER

  • CABINET HEATER

  • BUSHING CONDITION

  • TRIP COIL AMBER LED CONTROL BUILDING

OCB GILDFORD #1252 (NH)

  • SPRING CHARGED

  • OIL PRESSURE

  • OPERATION COUNTER

  • CABINET HEATER

  • BUSHING CONDITION

  • TRIP COIL AMBER LED CONTROL BUILDING

FORM 6 BATTERY TEST

RT # 1 FORM 6

  • BATTERY TEST

TR #3 FORM 6

  • BATTERY TEST

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.