Title Page
-
Conducted on
-
Prepared by
-
Location
INSPECTOR
-
WHO IS INSPECTING THE SUB.
-
-
Add signature
OCR's AND OIL SWITCHES
-
APPEARANCE OK
-
BUSHINGS CLEAN, GOOD CONDITION
-
FREE FROM OIL LEAKS
-
COUNTER READINGS RECORDED
AIR-BREAK AND DISCONNECT SWITCHES
-
APPEARANCE OK
-
INSULATORS OK
-
GROUND CONNECTION TO HANDLE OK
BYPASS SWITCHES
-
APPEARANCE OK
-
INSULATORS OK
POWER TRANSORMERS
-
ANY POWER TRANSFORMERS
REGULATORS
-
APPEARANCE OK
-
BUSHINGS CLEAN, GOOD CONDTION
-
OIL LEVELS AND GAUGES OK
-
FREE FROM OIL LEAKS
-
THERMOMETERS OK, MAXIMUMS RESET
-
MECHANISMS OK
-
INDICATING LIGHTS OK
-
INDICATING GLASS COVERS INTACT
-
CABINET GASKETS WEATHER TIGHT
-
COUNTER READINGS RECORDED
ADDITIONAL COMMENTS
REGULATORS
DRAG HAND POSITIONS
A-PHASE
-
CURRENT POSITION
-
MINIMUM POSITION
-
MAXIMUM POSITION
-
NUMBER OF OPERATIONS
-
RESET DRAG HANDS
-
MAXIMUM CURRENT
-
POWER FACTOR MAX / MIN
-
KVA MAX
-
OUTPUT VOLTAGE
B-PHASE
-
CURRENT POSITION
-
MINIMUM POSITION
-
MAXIMUM POSITION
-
NUMBER OF OPERATIONS
-
RESET DRAG HANDS
-
MAXIMUM CURRENT
-
POWER FACTOR MAX / MIN
-
KVA MAX
-
OUTPUT VOLTAGE
C-PHASE
-
CURRENT POSITION
-
MINIMUM POSITION
-
MAXIMUM POSITION
-
NUMBER OF OPERATIONS
-
RESET DRAG HANDS
-
MAX CURRENT
-
POWER FACTOR MAX / MIN
-
OUTPUT VOLTAGE
REGULATOR SETTINGS
A-PHASE
-
MANUFACTURE (COOPER) SERIAL # ( 1050003554 ) TYPE / AMPS ( VR32 B / 100 ) SET VOLTAGE ( 123 ) BAND WIDTH 2 TIME DELAY ( 30 ) LDC R / X ( 1.9 / 1.4 ) CONTROL TYPE ( CL6 )
B-PHASE
-
MANUFACTURE (COOPER) SERIAL # ( 1050003399 ) TYPE / AMPS ( VR32 B / 100 ) SET VOLTAGE ( 123 ) BAND WIDTH 2 TIME DELAY ( 30 ) LDC R / X ( 1.9 / 1.4 ) CONTROL TYPE ( CL6 )
C-PHASE
-
MANUFACTURE (COOPER) SERIAL # ( 1050003447 ) TYPE / AMPS ( VR32 B / 100 ) SET VOLTAGE ( 123 ) BAND WIDTH 2 TIME DELAY ( 30 ) LDC R / X ( 1.9 / 1.4 ) CONTROL TYPE ( CL6 )
OIL CIRCUIT RECLOSERS
To find Demand metering amps. 1. Press METERING button, press down arrow to "Demand Metering", arrow down to "Reset Demand Phase Amps", press ENTER, record max demand an d peak amps below. To Reset Demand and Peak Amps 1. Press METERING button, press down arrow to "Demand Metering", arrow down to "Reset Demand Peaks", press F4. "METER ARE RESET" should appear for 2 seconds.
ROUTE No. 1- NOVA
-
A- COUNTER READINGS
-
B- COUNTER READINGS
-
C- COUNTER READINGS
-
GRD
-
A-MAX AMPS DEMAND/PEAK
-
B-MAX AMPS DEMAND/PEAK
-
C-MAX AMPS DEMAND/PEAK
ROUT No. 3 & 4
-
A- COUNTER READINGS
-
B-COUNTER READINGS
-
C-COUNTER READINGS
-
GRD
-
A-MAX AMPS DEMAND/PEAK
-
B-MAX AMPS DEMAND/PEAK
-
C-MAX AMPS DEMAND/PEAK
FORM 6 BATTERY TEST
RT #1 FORM 6
-
DID BATTERY TEST OK
-
DID BATTERY TEST OK