Front Page
-
Site conducted
-
Conducted on
-
Prepared by
-
Location
Close Out Items
-
The pedestrian gates need to be checked for beams internally as well as externally.
-
The mag lock plates are on a metal angle plate which protrudes and is a high risk to injury, especially children due to the height, the gates should have been manufactured to incorporate the magnets and plates internally rather than being welded or bolted on the surface.
-
The vehicle gates need an external stop so they cannot be forced open by pulling from the outside.
-
Most of the doors have issues with delay in the magnets releasing, the magnet plates were adjusted whilst on site, but this is not the issue but a temporary fix, they need to be installed correctly or residents will be locked in and there will be more ECO call outs as in the past.
-
The CCTV and controls in the intake need unswitched spurs and not 3 pin plugs in sockets.
-
The PC for the PAC fob system has not been networked, this was said to be in hand and due to be completed this week.
-
All door entry button panels need to be removed and all cables connected correctly without any bare wires and sticky tape.
-
All door entry mains control panels need all cables connected correctly without any bare wires and sticky tape.
-
15-25 Carter push to exit button needs to be replaced with a correct part.
-
Fixing missing from the rear of the door entry panels on the gates
-
PTE of Ped Gate Toynbee St has bured/ sharp edges
-
Wrong fixings or missing from various drop key switches
-
Internal wiring in all door entry panels require improving
-
No silicone above PTE covers to prevent water ingress
-
Carter House – replace metal copex with steel conduit
-
Issues with doors not being able to open due to power supplying not staying off long enough for residents to open doors
-
Panels within electrical intakes – Cabling messy, needs improving
-
Brune House 70-76 no sw/isolator for door entry
-
Power cables unsupported in Brune House 70-76 electrical intake
-
Bernard Hse 14-26 Conduit to wall loose
-
Various power packs in cabinets coming away from back plate
-
It needs to be confirmed that the fire switch depowers the magnets to meet the fire regulations.