Above Ground Tanks
Above Ground Tanks
-
Are above ground tanks positioned with a minimum safety distance of:<br><br>- 3.0 Meters from the edge of the tank to a boundary ,buildings ,drains or any combustible materials<br>- For tanks with a capacity greater than 45 000 liters and less than 80 000 liters ,the safety distance becomes 6 meters
-
-
Select signages on tanks
- Engen Signage
- Tank Number
- Product Description
- No lighter
- Tank Capacity
- Max Ullage
- No Cellphone
-
Are there fixed ladders on the tanks & are they in good condition?
-
All ladders been galvanized?
-
Is the filler position safe?
-
Is a 32mm kamlock fitted?
-
Is a 2 1/2 inch dry break coupling (HFO only)fitted?"
-
Are remote fillers fitted?
-
Do remote fillers have spill containment fitted?
-
Are the Dip & Filler caps in place ,sealed and locked?
-
Is there any evidence of spills or overfills at the tank or filler point?
-
Report into IHSE🚨
-
Are the tanks in good condition ,free of rust and painted?
-
Pressure on gauge (HFO only) between 150-250kpa?
-
Tempature (HFO only) on gauge between 55 - 70 degrees?
-
Comments:
-
Pictures
Under Ground Tanks
Under Ground Tanks
-
Are tanks identified with: Tank number,capacity,product?
-
Are the correct delivery couplings installed?
-
Is the filler manholes sealed to prevent spills leaking out?
-
Are the filler point manholes clean & free of product?
-
Report into IHSE🚨
-
Are the filler & dip caps securely fitted and locked at all times?
-
Is there any evidence of spills or overfills at the filler points?
-
Report into IHSE🚨
-
Are vent pipes at least 3.5m above ground level and at least 600mm above a building roof if positioned against a building?
-
Is there any signs of fuel running out of the vents?
-
Report into IHSE🚨
-
Tanker earth point fitted at tanks?
-
Comments:
-
Pictures
BTF Tanks
BTF Tanks
-
Are there more than 2 btf's used at the commercial site?
-
Are there fixed ladders on the btf's & are they in good condition?
-
Are the tanks in good condition : free of rust and painted?
-
Are tanks identified with: Tank Number;capacity;Product?
-
Is there any evidence of spills or overfills at the tank or filler point?
-
Report into IHSE🚨
-
Comments:
-
Pictures
Bunds
Bunds
-
Are all above ground installations bunded?
-
Are all bund walls constructed of brickwork: plastered & in good condition?
-
Does the site have a concreted bund floor?
-
Bund wall valve operational: kept closed and locked?
-
Close valve and advise supervisor of the importance to keep valve closed and lock at all times
-
Correct safety signage visible at the tank area?
-
Are the inside of the bunded areas clean with no rags: debris or other flammable material?
-
Comments:
-
Pictures
Pumps & Pipelines
Pumps & Pipelines
-
Are the correct decals displayed on the pumps?
-
Any signs of leaks on pumps or piping?
-
Is the correct safety signage displayed(No smoking,Cell Phones,Naked Flames)?
-
Are aboveground pipelines painted and colour-coded?
-
Is the Emergency STOP identified & accessible?
-
Is the pump secured to a concrete base?
-
Is there spill retention at the pump/fuel dispensing area?
-
Are non return valves fitted to all tanks?
-
Is the isolating valve (HFO only)on the filler line at tank open?
-
Is the isolating valve(HFO only) at coupling closed?
-
Comments:
-
Pictures
Environmental
Environmental
-
Has the site experienced spills or leaks?
-
If Engen's responsibility ,have they been entered in IHSE?
-
EINC # .....
-
Is there a seperator on site & is it maintained?
-
Does the site have a good stock control system, with records available?
-
Comments:
-
Pictures
Electrical
Electrical
-
Any loose wires visible at pump/dispenser?
-
Is the electrical distribution board correctly marked?
-
Is the emergency Stop clearly identified & tested regularly?
-
Comments:
-
Pictures
Emergency Response
Emergency Response
-
Does the site have emergency response plans in place,including spill contingency plans?
-
Are portable fire extinguishers provided for use at the bunded areas?
-
Are there fire extinguishers available at the pump/dispenser areas?
-
Are the fire extinguishers serviced and well maintained?
-
Has all staff been trained how to handle a fuel spill?
-
Is sand or spill absorbent (spill kits) available on site?
-
Are copies of MSDS for each product available on the site?
-
Obtain MSDS from www.engen.co.za
http://www.engen.co.za -
Comments:
-
Pictures
General
General
-
Does the site have a Valid Flammable Substance Storage License avalable?
-
Inform customer that they need to obtain a certificate on a yearly cycle and if do not have a certificate Engen can stop supply.
-
Doc No:
-
Add media
-
Does the site manager understand Engen's work permit system?
-
Are there any signs of leaks and/or spills on the site?
-
Does the operator check regularly for water in the tanks&have records of results?
-
Are the areas around the tanks ; bunds or dispensing areas free from weeds; grass or flammable material?
-
Are the signs that the ug tanks are filled from the dip pipe instead of the correct filler point?
-
Do you have recent photos of the complete installation & surrounding areas?
-
Is the customer using wooden dipsticks - (Aluminum dipsticks to be removed)
-
Comments:
-