Above Ground Tanks

Above Ground Tanks

  • Are above ground tanks positioned with a minimum safety distance of:<br><br>- 3.0 Meters from the edge of the tank to a boundary ,buildings ,drains or any combustible materials<br>- For tanks with a capacity greater than 45 000 liters and less than 80 000 liters ,the safety distance becomes 6 meters

  • Select signages on tanks

  • Are there fixed ladders on the tanks & are they in good condition?

  • All ladders been galvanized?

  • Is the filler position safe?

  • Is a 32mm kamlock fitted?

  • Is a 2 1/2 inch dry break coupling (HFO only)fitted?"

  • Are remote fillers fitted?

  • Do remote fillers have spill containment fitted?

  • Are the Dip & Filler caps in place ,sealed and locked?

  • Is there any evidence of spills or overfills at the tank or filler point?

  • Report into IHSE🚨

  • Are the tanks in good condition ,free of rust and painted?

  • Pressure on gauge (HFO only) between 150-250kpa?

  • Tempature (HFO only) on gauge between 55 - 70 degrees?

  • Comments:

  • Pictures

Under Ground Tanks

Under Ground Tanks

  • Are tanks identified with: Tank number,capacity,product?

  • Are the correct delivery couplings installed?

  • Is the filler manholes sealed to prevent spills leaking out?

  • Are the filler point manholes clean & free of product?

  • Report into IHSE🚨

  • Are the filler & dip caps securely fitted and locked at all times?

  • Is there any evidence of spills or overfills at the filler points?

  • Report into IHSE🚨

  • Are vent pipes at least 3.5m above ground level and at least 600mm above a building roof if positioned against a building?

  • Is there any signs of fuel running out of the vents?

  • Report into IHSE🚨

  • Tanker earth point fitted at tanks?

  • Comments:

  • Pictures

BTF Tanks

BTF Tanks

  • Are there more than 2 btf's used at the commercial site?

  • Are there fixed ladders on the btf's & are they in good condition?

  • Are the tanks in good condition : free of rust and painted?

  • Are tanks identified with: Tank Number;capacity;Product?

  • Is there any evidence of spills or overfills at the tank or filler point?

  • Report into IHSE🚨

  • Comments:

  • Pictures

Bunds

Bunds

  • Are all above ground installations bunded?

  • Are all bund walls constructed of brickwork: plastered & in good condition?

  • Does the site have a concreted bund floor?

  • Bund wall valve operational: kept closed and locked?

  • Close valve and advise supervisor of the importance to keep valve closed and lock at all times

  • Correct safety signage visible at the tank area?

  • Are the inside of the bunded areas clean with no rags: debris or other flammable material?

  • Comments:

  • Pictures

Pumps & Pipelines

Pumps & Pipelines

  • Are the correct decals displayed on the pumps?

  • Any signs of leaks on pumps or piping?

  • Is the correct safety signage displayed(No smoking,Cell Phones,Naked Flames)?

  • Are aboveground pipelines painted and colour-coded?

  • Is the Emergency STOP identified & accessible?

  • Is the pump secured to a concrete base?

  • Is there spill retention at the pump/fuel dispensing area?

  • Are non return valves fitted to all tanks?

  • Is the isolating valve (HFO only)on the filler line at tank open?

  • Is the isolating valve(HFO only) at coupling closed?

  • Comments:

  • Pictures

Environmental

Environmental

  • Has the site experienced spills or leaks?

  • If Engen's responsibility ,have they been entered in IHSE?

  • EINC # .....

  • Is there a seperator on site & is it maintained?

  • Does the site have a good stock control system, with records available?

  • Comments:

  • Pictures

Electrical

Electrical

  • Any loose wires visible at pump/dispenser?

  • Is the electrical distribution board correctly marked?

  • Is the emergency Stop clearly identified & tested regularly?

  • Comments:

  • Pictures

Emergency Response

Emergency Response

  • Does the site have emergency response plans in place,including spill contingency plans?

  • Are portable fire extinguishers provided for use at the bunded areas?

  • Are there fire extinguishers available at the pump/dispenser areas?

  • Are the fire extinguishers serviced and well maintained?

  • Has all staff been trained how to handle a fuel spill?

  • Is sand or spill absorbent (spill kits) available on site?

  • Are copies of MSDS for each product available on the site?

  • Obtain MSDS from www.engen.co.za
    http://www.engen.co.za

  • Comments:

  • Pictures

General

General

  • Does the site have a Valid Flammable Substance Storage License avalable?

  • Inform customer that they need to obtain a certificate on a yearly cycle and if do not have a certificate Engen can stop supply.

  • Doc No:

  • Add media

  • Does the site manager understand Engen's work permit system?

  • Are there any signs of leaks and/or spills on the site?

  • Does the operator check regularly for water in the tanks&have records of results?

  • Are the areas around the tanks ; bunds or dispensing areas free from weeds; grass or flammable material?

  • Are the signs that the ug tanks are filled from the dip pipe instead of the correct filler point?

  • Do you have recent photos of the complete installation & surrounding areas?

  • Is the customer using wooden dipsticks - (Aluminum dipsticks to be removed)

  • Comments:

  • Pictures

Follow up by Regional Sales Manager

  • Signature by Salesperson:

  • Signature by customer confirming items discussed:

  • Signature by Regional Sales Manager:

  • Picture of site:

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.