Title Page
-
Job Number
-
General Contractor
-
Conducted on
-
Project Manager
-
Floor / Area Worked
-
Tempurature
-
Confirm that all sheet metal flashing has been installed prior to paper
-
Notes
-
Add media
-
Confirm that backing is installed to trims and that true expansion joints are framed for the correct size of joint
-
Notes
-
Add media
-
Confirm primer for the flexible membrane has been installed in necessary locations
-
Notes
-
Add media
-
Confirm flexible membrane has been installed over milcor flanges
-
Notes
-
Add media
-
Confirm flexible membrane has been installed behind trims
-
Notes
-
Add media
-
Confirm flexible membrane has been lapped more than 3"
-
Notes
-
Add media
-
Insure that paper has been lapped 4" horizontally and 16" vertically
-
Notes
-
Add media
-
Confirm proper waterproofing has been installed per manufacturers recommendations if 60-minute paper is not specified
-
Notes
-
Add media
-
Confirm that two layers of 60-minute paper has been applied
-
Notes
-
Add media
-
Check and confirm correct lath laps for materials used (1" horizontally 1/2" vertically on 3.4 & 2.5 & stucco netting 2 1/2")
-
Notes
-
Add media
-
Confirm the correct fasteners have been used and are installed 6" OC
-
Notes
-
Add media
-
Confirm that lath between stud bays is tied
-
Notes
-
Add media
-
Visually check all holes, dead screws and trims have been caulked (all sill screws must be caulked to cover screw head completely)
-
Notes
-
Add media
-
Confirm that all ceilings are wire tied and that supports are 13 1/2" O.C. maximum
-
Notes
-
Add media
-
Confirm all trims are plumb and true per details
-
Notes
-
Add media
-
Confirm control joint layout are under 120/sq. ft., and that they comply with industry standards and job specifications
-
Notes
-
Add media
-
Confirm band aids or diagonal strips have been applied at heads and sills of openings
-
Notes
-
Add media
-
Confirm control joints installed prior to lath. Lath is not continuous through control joints
-
Notes
-
Add media
-
Confirm all the above have been completed per the plans and specs
-
Notes
-
Add media
-
Sign Off
-
Forman
-
Q.C. Sign Off
-
Comments