INFORMATION

  • Document No.

  • Audit Title

  • Client / Site

  • Conducted on

  • Prepared by

  • Location
  • Personnel

FUEL RECEIPT RECORDS

  • Do fuel load receipt certification documents meet ASTM D1655 specifications? Are files retained for 12 months or more? <br>

PIPELINE

  • Are the following tests being conducted and recorded at the beginning, mid-point (if over 4 hours) and end of the fuel receipts?

  • Visual appearance in White Bucket

  • API Gravity, corrected to 60 degrees F (15 degrees C)

  • Color Membrane

  • Free Water Detection Test

  • Flash Point (Multi-Product Pipeline deliveries only)

  • Is the API Gravity between 37 degrees C and 51 degrees C? (Ensure there is not a change of less than 1 degree API as shown on the shipping document)

TRANSPORT

  • Are the following tests being conducted and recorded?

  • Visual appearance in White Bucket

  • API Gravity, corrected to 60 degrees F (15 degrees C)

  • Is the API Gravity between 37 degrees C and 51 degrees C? (Ensure there is not a change of less than 1 degree API as shown on the shipping document)

MANUAL & TRAINING RECORDS

  • Does the vendor have access to the most current copy of the Mesa Airlines, Inc. Fueling Manual #310?

  • Are employees aware of how to access the Mesa Airlines Fuel Manual through the Mesa non-employee Tech Pubs website?

  • Are training certification records for persons performing equipment and facility inspections current and available for review? <br>

  • Are there any waivers currently on file? (Make copies for reference if applicable) <br>

  • Does fuel vendor have an operations and maintenance manual? <br>

  • Does the vendor have a current copy of the ATA 103?

FUEL FACILITY CHECKS

  • Do facility records for persons performing daily, monthly, quarterly and annual inspections have legible signatures, initials or employee identification numbers? <br>

  • Are fuel facility filter change records kept on file for at least 36 months?

  • Are fuel facility tank inspection and cleaning records kept on file indefinitely?

  • Are Daily, Semi-Annual and Annual check records being retained on file for at least 12 months? <br>

DAILY CHECKS

  • Is the general condition of the tank yard being checked?

  • Are security, fire and safety deficiencies being checked?

  • Are fuel leaks being checked?

  • Are storage tank and reclamation tank sumps being performed and is the first sample being recorded? <br>

  • Are there separate sump recordings for each filter vessel?

  • Are filter differential pressures being recorded for each filter vessel and less than 15PSI? <br>

  • Are there separate differential pressure recordings for each filter vessel? <br>

  • Is the condition of hoses, swivels and nozzle covers being checked? <br>

  • Is the condition of static reels, cables and clamps being checked? <br>

  • Are Fire Extinguishers, inspection tags and seals being checked? <br>

MONTHLY CHECKS

  • Are monthly Millipore tests being performed on each filter vessel and are they available? <br>

  • Do Millipore membrane test results ratings meet (ASTM D2276) a 2A (3A wet) or less? <br>

  • Are free water tests being performed? <br>

  • Can the water kit detect 15ppm or less? <br>

  • Are the results 15ppm or less? <br>

  • Is the shelf life inspected to ensure no expired kits are used? (Aqua-Glo & Metrocator kits do not have a shelf life)

  • Are bonding cable continuity tests 25 ohms or less? <br>

  • Are nozzles removed and the screens checked? <br>

  • Are signs and placards being checked? <br>

  • Are the floating suctions checked? <br>

  • Are Fire Extinguishers, inspection tags and seals being checked? <br>

QUARTERLY CHECKS

  • Are the Emergency shutdown systems being operationally checked? <br>

  • Are the water defense systems being operationally checked on filter/separators? <br>

  • Are tank high level controls being checked? <br>

  • Are product reclamation tank interior inspections complied and cleaned as required? <br>

SEMI-ANNUAL CHECKS

  • Are loading and unloading hoses with reusable fittings pressure checked pre API 1540 requirements? <br>

ANNUAL CHECKS

  • Are the storage tank interiors inspections being checked and documents on ATA Form 103.07 or equivalent? <br>

  • Are filter differential pressure gauges being checked?<br>

  • Are filter elements being replaced every 12 months?<br>

  • Are filter separator/heaters being checked?<br>

  • Are tank vents being checked?<br>

  • Is cathodic protection being checked for underground storage tanks?<br>

  • Are line strainers, if installed, being removed and checked?<br>

  • Are filter vessel water defense systems being checked for operation?<br>

FUEL STORAGE FACILITY WALK-AROUND

  • Is the storage facility secure from public access (Mesa Airlines, Inc. Manual #310)<br>

  • Are all fences and gates in good condition?<br>

  • Are all fence openings in unsecured areas locked when not in use?<br>

  • Are NO SMOKING, FLAMMABLE and JET FUEL or other product signs displayed?<br>

  • Ensure that there are no galvanized, copper alloys, cadmium plated or other materials?<br>

  • Is product identified and color-coded per API 1542 standards?<br>

  • Are flow direction arrows and color-coded bands clearly marked and visible on all piping above ground?<br>

  • Is there an adequate supply of ladders, stands and other related support equipment and in serviceable condition?<br>

  • Is there adequate lighting in the area for night operations?<br>

  • Are filter/separators or full-flow monitors being used for fuel receiving and dispensing?<br>

  • Do filter/separators meet current API Group II Class B Specifications? (API 1581)<br>

  • Do the filter/separators have an automatic water defense system that will either stop fuel flow or alert personnel?<br>

  • Do the filtration vessels have the following:<br>

  • Provisions for eliminating air?

  • Direct reading differential pressure gauges?

  • Manual sump drains?

  • Downsteam & upstream Millipore connections?

  • Pressure relief valves?

  • Placard indicating the month and year of last filter change?

  • Do the filtration vessels nameplate contain all of the following:<br>

  • The Manufacture’s name and address?

  • The serial and unit number?

  • The API classification?

  • The rated capacity fot JET A?

  • The date of manufacture?

  • The number and model numbers of the coalescer and separator elements?

  • The manufacture’s recommended element change pressure differential?

  • Are the filter vessel sumps acceptable?<br>

  • Are tank sumps acceptable?<br>

  • Is there a placard indicating the volume of tank drain piping adjacent to the tank drain valves?<br>

  • Does the fuel storage facility have an operating dead man control for all truck loading operations?<br>

  • Does the fuel storage facility have static ground cables at all truck loading points?<br>

  • Are plumbing, valves and hoses free from leaks and damage?<br>

  • Do loading and unloading fuel hoses/couplings meet API 1529 standards and 10 year service life?<br>

  • Are dust covers installed?<br>

  • Is there a system in place to prevent accidental mixing of fuels?<br>

  • Is the emergency shutoff systems placarded with (NFPA 407):<br>

  • At least 2" letters?

  • Method of operation?

  • At least 7' above grade?

  • Can be read 25' away from rack?

  • Is there unobstructed access to the emergency shutoff valves and switches?<br>

  • Are electrical junctions, boxes and conduits intact, with no expose wiring or frayed connections?<br>

  • Are the fire extinguishers in proper place and unobstructed?<br>

  • Ensure that all inspection tags and seals are intact or the extinguisher must be taken out of service?<br>

  • Are floating suctions working properly?<br>

OUTBRIEF & SIGNATURE

  • Please sign below to acknowledge that the audit results have been reviewed with you.

  • Add signature

  • Auditor's Signature:

  • Add signature

  • Auditor Comments:

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.