Portable Electrical Tools and Equipment (PETE)
-
Are all items of PETE within inspection & test date? (i.e. within the last 3 months) and fitted with a current test tag.<br>Include details of items checked and the test and tag number for each.
-
Are all RCD’s within inspection and test date? (i.e. within the last month) and fitted with a current test tag.<br>Include details of items checked and the test and tag number for each.
-
Are all items of PETE been used supplied via an RCD?
-
Is there an up to date PETE register? And is required information documented?
-
Is there an up to date RCD register? And is all required information documented?
-
Are there danger tags available? (i.e for tagging of defective equipment)
-
Have all double adaptors & piggy back plugs been excluded from site?
-
Are all portable GPO outlets weatherproof?
-
Are all flexible cords/leads positioned or protected to avoid damage?
-
Are all flexible cords/leads of a length less than or equal to those shown in the attached table?
-
Are all flexible cords/leads installed off the ground? (Note: cords/leads only to be placed on ground within switchyard areas)
-
Are all portable generators clearly labelled with earthing requirements?
AS/NZS 3012 – Construction Wiring Temporary Switchboards
-
Are all switchboards of robust construction and have a minimum <br>IP23 rating?<br>
-
Are all live parts of the switchboard effectively protected from direct contact?
-
Where GPO outlets are fitted, is there an insulated tie bar to prevent strain on cords/leads?
-
Is the switchboard securely fixed in position or on a design stable free standing structure?
-
Are all main switches and isolating switches accessible clearly marked (min of 6mm text) and capable of being locked in an open position?
-
Are all switchboards and sub circuits clearly marked via unique identifications marks?
-
Is the switchboard fitted with a lockable door? <br>The door shall;<br>• Fitted with a means to retain in the open position<br>• Fitted with a sign indicating “KEEP CLOSED - RUN ALL LEADS THROUGH BOTTOM”<br>• Not damage cords/leads when closed.<br>
-
Are all RCD’s and MCB’s covered and locked to prevent unauthorised access?
-
Are all sub-circuits protected by an RCD?
-
Is the construction wiring marked every 5 metres with yellow tape & the words “construction wiring”?
-
Is any aerial wiring across vehicle access points flagged 6m either side at 0.6m below the cable?
-
Is there a copy of the certificate of electrical safety for the temporary construction wiring?
-
Has the temporary construction wiring been visually inspected and tested by a qualified electrician within the last 6 months? (earth continuity and insulation resistance)
-
Are the roofs of all temporary buildings clear of temporary wiring?