Title Page
-
SON
-
Audit Title
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Personnel
-
Unit
Unit
Unit Details
-
Part Number
-
Kvar installed
-
KVar max
-
Amps Max
-
System voltage
-
Shop Order Number
-
Date of manufacture
-
Controller
-
CT Ratio
-
Protection Device
-
Unit Images
Preliminary Checks
-
Ensure all connections are tight
-
Ensure fuses installed correctly
-
Ensure contractors have free movement
-
Ensure discharge resistors have not been damaged
-
Ensure correct phase rotation to PFC
-
Ensure CT is connected to L1
-
Ensure voltage is 400V +- 10%
-
Remove CT short Links
-
Program CT Ratio
-
Check Settings and alarm functions are at default
Commissioning Details
-
Target PF
-
Switching Delay
-
CT Current Present at controller?
-
Confirmed Phase Rotation
-
Turn off Unused Steps
Step Details
-
Step Testing
Step
-
L1 Current
-
L2 Current
-
L3 Current
-
Current Test OK?
Preliminary Checks
-
Ensure all connections are tight
-
Ensure fuses installed correctly
-
Ensure contractors have free movement
-
Ensure discharge resistors have not been damaged
-
Ensure correct phase rotation to PFC
-
Ensure CT is connected to L1
-
Ensure voltage is 400V +- 10%
-
Remove CT short Links
-
Program CT Ratio
-
Check Settings and alarm functions are at default
Commissioned By
-
Technician
-
Customer