Title Page
-
Site conducted
-
Conducted on
-
Prepared by
-
Location
1. Main Entrance
-
Security personnel are available at the main entrance
-
An entry/exit log is kept up to date & visitor ID is checked
-
Ceiling in a proper condition free of any defects or moisture
-
Electrical wires and sockets are in good condition
-
Availability of fire detectors
-
Availability of inspected fire extinguisher with proper weight and height
-
Proper air quality
-
Proper housekeeping
2. Corridors
-
Emergency evacuation plans and maps are clearly posted in designated areas
-
First aid kit contents are clean and valid (no expired items)/ Monthly Checklists are available
-
Lobbies and corridors are free of waste, obstructions, slip & trip hazards
-
Floor surfaces are in good condition
-
Appropriate warning signs are provided during floor cleaning (e.g. Wet Floor)
-
Emergency exit doors are clearly marked and signed, unlocked & open freely
3. Access and Egress
-
Egress routes free of blockages (corridors, stairs, doorways & exterior routes)
-
Fire extinguishers in good condition (placed, unobstructed, no visual damage gauges up to pressure, pullpin & seal in place, periodical maintenance records, etc)
-
Emergency exits must open to outside (toward attendants flow)
-
No presence of any solid scented perfume (bokhor)
-
All corridors and stair ways must be free from storage
-
Electrical wires and sockets in a good condition
-
Availability of inspected fire extinguisher with proper weight and height
-
Proper housekeeping
-
Availability of slip resistance rubbers in all stairway steps
-
Assembly areas free of vehicles or other obstructions
-
Egress routes are free of obstructions (corridors, stairs, doorways & outdoor routes to assembly areas)
-
Emergency exits & assembly signs are in good condition & clearly visible
-
Guardrails on ramps are in proper height for special need people use
-
Non-slippery floors
-
Emergency exits are unlocked
4. Emergency Preparedness
-
Emergency lights are operational
-
Fire system is working without faults or false alarms
-
Control Panel was locked to prevent access for unauthorized persons
-
Emergency evacuation plans and maps are clearly posted in designated areas
-
Emergency evacuation drill conducted
-
Last drill was on:
5. Laboratory
-
All hazardous substances are properly labeled, including secondary containers & contain the risk and safety phrases according to MSDS
-
Induction about hazards for used substances has been given to users prior to use
-
MSDS & Hazardous Substances Register readily accessible in the area where substances are stored & used
-
Risk assessment has been conducted for substance uses is available
-
All substances are stored according to requirements of MSDS
-
Flammable chemical substances and concentrated acids (e.g. HCL) are stored in a special fire-resistant cabinet
-
Lab local exhaust ventilation / suction hood and indoor air quality ventilation system are in good condition (no observation of abnormal chemical or gas smells)
-
Appropriate PPE available (according to MSDS) & worn by all those users (user is that person who is using or handling the substance)
-
PPE is properly stored & in good condition
-
Expired chemicals and waste substances are disposed of through certified and approved service providers.
-
Records available for disposed chemicals waste
-
Chemicals properly labeled, including secondary containers
-
Presence of First Aid kit
-
Presence of emergency eye wash and emergency shower
-
No compressed gas cylinders
-
All chemical cabinets were marked and locked
-
Ceiling in proper condition free of any defects or moisture
-
Electrical wires and sockets in a good condition
-
Availability of fire detectors
-
Availability of inspected fire extinguisher with proper weight and height
-
Proper air quality
-
Proper housekeeping
-
All the student chairs in the chemical laboratory are in a circle shape without arm rests and there is no back support
6. Electrical Rooms
-
Electrical rooms are free of any storage items - no boxes, ladders and any remnants
-
All electrical plugs, sockets, leads, cords & switches are in good working order
-
Electrical rooms locked to prevent unauthorized access
-
Proper signage in place and clearly visible (e.g. Electrical Hazard or Danger High Voltage)
-
Ceiling in proper condition free of any defects or moisture
-
Availability of fire detectors
7. All School Area
-
Art works and teaching materials which displayed and posted in corridors shouldn't exceed more than 20% of a wall section without fire sprinklers system. In case of fire sprinkler availability it should not exceed 50%
-
Availability of inspected fire extinguisher with proper weight and height
-
No evidence of moisture leaks or mold around AC units
-
Ensure that the prevention procedures for pests are placed
-
No smoking policy enforced for all (students, employees, contractors, visitors)
8. Classrooms
-
Proper housekeeping
-
Work station ergonomics are in place for Chairs, desks & work layout
-
- Computer screens kept away from windows to avoid glare
-
Lighting is adequate
-
All furniture is fit for purpose & in good condition
-
Electrical cords properly secured & away from students (e.g. not across walkways/no trip hazards)
-
No evidence of moisture leaks around AC units
-
Windows are not able to open for more than 10-20cm
-
Proper air quality and appropriate temperature
-
Ceiling in proper condition free of any defects or moisture
-
Carpets should not be used unless in KG's
-
No decorations hanged from the ceiling or on the lights
-
Art works and teaching materials which displayed and posted in the classroom shouldn't exceed more than 20% of a wall section without fire sprinklers system, In case of fire sprinkler availability it should not exceed 50%
9. Clinic Checklist
-
Sharps containers in place & log available
-
Presence of First aid kits and easily accessible
-
Proper PPE is available & in use (e.g. gloves, masks)
-
MSDS available in the clinic for all hazardous substances and tools used in the school
-
Biohazard labels on all containers of regulated waste, refrigerators, freezers, etc
-
Expired and waste substances are disposed of through certified and approved service providers. Records for chemical waste and disposal program available
-
Adequate lighting
-
Presence of 3 disposal trashes
-
Local exhaust ventilation / suction hood and indoor air quality ventilation system in place, good condition, periodical maintenance records, etc. (no observation of abnormal chemical smells)
-
Ceiling in proper condition free of any defects or moisture
-
Electrical wires and sockets in a good condition
-
Availability of fire detectors
-
Availability of inspected fire extinguisher with proper weight and height
-
Proper air quality
-
Proper housekeeping
10. Cafeteria & kitchen
-
Hygiene controls are in place for food handling (gloves, hair nets, etc.)
-
Kitchens & washrooms are adequately ventilated (no bad smells)
-
Presence of hygienic control equipment and monitoring in kitchen and washrooms
-
Non-slippery floors
-
No compressed gas cylinders
-
Food Handlers certified by ADFSA (Abu Dhabi Agriculture and Food Safety Authority)
-
Exhaust hood ventilation working properly, door kept closed
-
The validity of expiry dates for all food items
-
Provide a list of approved foods category
-
The canteen must be certified by ADFSA (Abu Dhabi Agriculture and Food Safety Authority)
-
Ceiling in proper condition, free of any defects or moisture
-
Electrical wires and sockets in good condition and harmless
-
Availability of heat detectors
-
Availability of inspected fire extinguisher with proper weight and height
-
Proper air quality
-
Proper housekeeping
-
Food are certified and approved by ADEK and ADFSA
11. Playground and Gymnasium
-
No sharp edges available
-
Walls covered by absorbing fire rated pads
-
Ceiling in proper condition free of any defects or moisture and covered by safety net
-
Electrical wires and sockets in a good condition and harmless
-
Availability of inspected fire extinguisher with proper weight and height
-
Proper air quality
-
Noise levels are less than 85 db
-
No presence of moisture or mold under the washers
12. Swimming Pool
-
Water quality testing (PH, Chloride levels) is posted on the notice board with the lifeguard and coaches certificates?
-
Non-slippery area around swimming pool
-
Swimming pool depth signs presence in both sides
-
Proper Fire System
-
Chemicals stored according to MSDS in specific chemical cabinets (double-walled, with specified capacities for the type of chemicals contained, fire-rated, etc.)
-
Ceiling in proper condition free of any defects or moisture
-
Electrical wires and sockets in a good condition and harmless
-
Availability of inspected fire extinguisher with proper weight and height
-
Proper air quality
-
Proper housekeeping
-
Presence of trained guard
13. Theatre / Auditorium
-
Emergency exit doors are sufficient to the number of attendants and provided with signs
-
Emergency exit doors are fire rated and clearly marked
-
Emergency exit doors unlocked & open freely
-
Emergency exits signs and lights are adequate, posted in place, operating and in good condition
-
Non slippery floors
-
Fully adjustable chairs
-
Area behind the stage free of storage
-
Fire exit available back stage
-
Ceiling in proper condition free of any defects or moisture.
-
Proper Housekeeping
14. Storage Area
-
2 meters maximum heights of goods stored/ materials properly stacked ( No storage exceed 2 meters height)
-
No overloading of bin and shelves
-
Materials are stored appropriately & safely (e.g. heavy items are stored at waist height)
-
Materials properly stacked away at least 1 meter from the ceiling
-
Proper equipment's are used for handling materials (e.g. trolleys)
-
Ceiling in proper condition free of any defects or moisture
-
Portable ladders are in good condition
-
Electrical wires and sockets in a perfect condition and harmless
-
Availability of inspected fire extinguisher with proper weight and height
-
Proper air quality
-
Correct lifting procedures are observed
15. Toilets
-
Proper Housekeeping
-
Washrooms adequately ventilated (no bad smells)
-
No evidence of mold growth around AC units, exhausts and under the water pipes closets
-
Non-slippery floors
-
HVAC supply & exhaust vents kept clear
-
Ceiling in proper condition free of any defects or moisture
-
Electrical wires and sockets in good condition
16. Library
-
lightning suitable and sufficient
-
Fire extinguishers in place, unobstructed, no visual damage, gauges up to pressure, pullpin & seal in place, good condition, periodical maintenance records, etc
-
Electrical wires and sockets in a good condition and harmless
-
Availability of inspected fire extinguisher with proper weight and height
-
Books were arranged safely (avoid fallings or overload)
-
No evidence of mould growth around AC units & potted plants
-
Carpet clean and there is no presence of tripping hazards
-
Proper chairs at workstations
-
Availability of fire detectors
-
No decorations hanged from the ceiling or on the lights
-
Art works and teaching materials which displayed and posted in corridors shouldn't exceed more than 20% of a wall section without fire sprinkler system, In case of fire sprinkler availability it should not exceed 50%
17. Computer Laboratory I ICT LAB
-
Computer screens kept away from windows avoiding glare
-
Proper chairs at workstations
-
Electrical cords properly secured (not across walkways/no tripping hazards)
-
Emergency exit doors are sufficient to the number of attendants, fire rated, clearly marked and provided with signs, unlocked & open freely
-
Ceiling in proper condition free of any defects or moisture
-
Electrical wires and sockets in a perfect condition and harmless
-
Availability of inspected fire extinguisher with proper weight and height
-
Proper air quality
-
Proper housekeeping
18. Art Room
-
MSDS & Hazardous Substances Register readily accessible in the area where substances are stored & used
-
Chemicals properly labeled, including secondary containers
-
Availability of chemical storage cabinet
-
Ceiling in proper condition free of any defects or moisture
-
Electrical wires and sockets in a perfect condition and harmless
-
Availability of fire detectors
-
Availability of inspected fire extinguisher with proper weight and height
-
Proper air quality
-
Proper housekeeping
19. Music Room
-
Presence of visual alarms
-
Sound proof walls
-
Proper air quality
-
Electrical wires and sockets in a perfect condition and harmless
-
Availability of inspected fire extinguisher with proper weight and height
-
Proper housekeeping
20. Administration Office
-
Glass doors shadowed to be more clear and visible
-
Workstation ergonomics are in place for Chairs, desks, monitors keyboard, mouse, phone & work layout
-
No presence of any solid scented perfume (bokhor)
-
Ceiling in proper condition free of any defects or moisture
-
Electrical wires and sockets in a perfect condition and harmless
-
Availability of inspected fire extinguisher with proper weight and height
-
Proper air quality
-
Proper housekeeping
21. Server Room
-
Proper warning signage
-
Fire rated doors
-
Ceiling in proper condition free of any defects or moisture
-
Electrical wires and sockets in a perfect condition
-
Availability of fire detectors
-
Availability of inspected fire extinguisher with proper weight and height
-
Proper air quality
-
Proper housekeeping
22. School yard
-
Proper housekeeping
-
Floors are in good conditions
-
Proper safety measures for grass fertilizer
23. Pump room
-
No evidence of moisture leaks or mold
-
Ceiling in proper condition free of any defects or moisture
-
Pressure gauge reading during the inspection
-
Availability of inspected fire extinguisher with proper weight and height
-
Availability of fire detectors
-
Proper air quality
-
Proper housekeeping
-
Water sprinkler system available