Title Page
-
Site conducted
-
Location
-
Conducted on
-
Prepared by
Baseline Data/Compliance Documentation
-
Ease of access to records of Installation Baseline data
-
Notes from meeting
Scope of Audit Covers
-
Fire Detection and Alarm Systems
Panel
-
Asset description/location
-
Service records up to date
-
Evidence of last Annual Service
-
Panel is clear of faults
-
Block Plan Present
-
Image of block plan
-
Building layout correct and zoning identified
-
Locations of FDCIE, SHCIE, FFCP and EWCIE indicated
-
Location of FBP and marked "YOU ARE HERE"
-
Electrical switchboard marked
-
Year of original install and relevant revisions
-
In the event of fire statement
-
Condition of panel and associated devices is in good servicable condition
-
Is there a Special Hazards System installed in conjunction with the panel?
-
Gauges legible and in the green
-
Bottles are within in pressure test date
-
System in good serviceable condition
-
Bottles securely and adequately mounted (as per standard requirements)
-
Further Notes, Comments or Media
-
Extinguishers
-
General notes (Appropriate, fit for purpose extinguishers, providing adequate coverage for the protected areas?)
Extinguisher
-
Asset description/location
-
Extinguisher in good serviceable condition (Correct pressure, not damaged)
-
Extinguisher is correct type for protected area
-
Securely and adequately mounted (as per standard requirements)
-
Tag in place and stamped in service
-
Anti tamper seal in place
-
Extinguisher bag in place and in good condition
-
Required signage is in place and correct
-
Asset number in place and legible (as per AS 1851-2012 Clause 10.2.15.2)
-
Within pressure test date (3 or 5 yearly? refer adverse environment definition)
-
Fire Hose Reels
Fire Hose Reel
-
Asset description/location
-
Hose Reel in good serviceable condition and free moving
-
Clearly accessible and clear of extraneous materials
-
Required signage and operating instruction are in place, legible and correct
-
Asset number in place and legible (as per AS 1851-2012 Clause 9.2.8.2)
-
Pipe work feeding hose reel is fire rated and minimum 25mm ID
-
Securely and adequately mounted (as per standard requirements)
-
Centre of reel is 1400-2800mm high and isolation valve is 1m +/- 100mm
-
Tag in place and stamped in service
-
Hose undamaged with no kinks
-
Isolation valve fitted and operates correctly
-
Nozzle is retained in interlock
-
Flow rate appears to be adequate
-
No leaks present
-
Fire Depots
Fire Depot
-
Typical Mines depot fire equipment bin may include. 1 Bin c/w Signs, 1 Equip basket,
-1 PVC Branch 5 38mm F/Hose c/w fittings,
-1 G/M branch 65mm
-1 38mm G/M nozzle and spanners Made to specific mines requirements or needs.
TYPICAL CONTENTS SETUP
-5 x 30 METRE HOSE COMPLETE WITH COUPLINGS
-1 x 65mm CONTROLLED DIVIDING BREECH
-2 x 65mm PVC BRANCHPIPES
-1 x 65mm BRASS BRANCHPIPE
-1 x 38mm PVC straight jet NOZZLE
-1 x 38mm Brass jet spray fog FIRE NOZZLE
-2 x HYDRANT SPANNERS
Options available: Lid Dust Seal Lid Pin Lock Contents Labels inside lid -
Asset description/location
-
In good, serviceable condition
-
Contents list present
-
Contents match contents list
-
Further Notes, Comments or Media
-
Pumps
Pump
-
Asset description/location
-
Service records up to date
-
Evidence of last Annual Service
-
Pump and motor in good condition
-
Pump area clear and tidy with 1m clearance surrounding pump
-
No signs of rust or leaks
-
Diesel tank full and fitted with indicator
-
Panel operation and in working order
-
Automatic start pressure switches wired in
-
Isolation valves secured or monitored
-
Pressure gauges fitted to suction and discharge
-
Pump exhaust lagging fitted
-
Nominated duty, flow and pressure
-
Pressure relief system fitted to pump
-
Wiring systems and batteries secured and in good condition
-
"Danger this pump starts automatically" sign installed and clearly visible
-
All controllers labelled as per standard requirements
-
All valves are in correct Open/Closed position
-
Hydrants
-
Hydrant suction and booster facility fitted and fit for purpose
Hydrant
-
Asset description/location
-
Hydrant valve(s) in good serviceable condition
-
Hydrant stand pipe in good serviceable condition with minimal movement
-
Adequate sized pipe feeding hydrant (80mm or 100mm, relevant build standard dependent)
-
Clearly accessible and clear of extraneous materials
-
Tag in place and stamped in service
-
Presence of water
-
No leaks present
-
Landing valve height between 750-1200mm
-
Further Notes, Comments or Media
-
Sprinkler/Deluge Systems
System
-
Asset description/location
-
Service records up to date
-
Evidence of last Annual Service
-
Block plan fitted with required design information
-
Incoming water supply fire rated, supported and free of damage
-
All relevant signage installed and clearly visable
-
Main stop valve in correct position and in serviceable condition
-
Alarm valve fitted and in serviceable condition
-
Pressure switch and gong fitted
-
Annubar line fitted with 2 isolation valves
-
Distribution pipe well supported and free of rust
-
Range pipe well supported and free of rust
-
Sprinkler heads in good condition and temperature matches the block plan
-
Remote test line fitted
-
Pipework Overview
Defect
-
Details