Information
-
Audit Title
-
Document No.
-
Client / Site
-
Conducted on
-
Next Inspection Due
-
Prepared by
-
Location
-
Fire Door Inspection
Fire Door
Door Location
-
Location
-
BM TRADA Q-Mark
- FD30
- FD60
- FD90
- FD120
-
Add media
Door Closing
-
Does the Fire Door fully close and shut tight by its own self-closing device?
-
Does the Fire Door slam shut?
-
Do the hinges or frame impede the Fire Door from closing?
Door Closers
-
Open the door to 75mm or 5 degrees. Does it close and engage with the latch?
-
Is the closer securely attached to the door and the frame?
-
Is the closer free from damage?
-
If unlatched does the closer hold the door in line with the frame and intumescent seal?
-
If hung in pairs, do they close in line if both are opened and released together?
Door Seals
-
Are intumescent seals in place? (Around all edges of door and/or frame)
-
Are the seals in good condition?
-
Are any cold smoke seals continuous around the door leaf or door frame and in good condition?
Threshold Gap
-
Is there a consistent gap under the door that allows it to swing without touching the floor covering?
-
Is the door to floor covering gap consistently 10mm (3mm if smoke seals are fitted) or less when the door is closed?
-
If the door leaf is fitted with a threshold seal, does the seal make contact with the floor covering when the door is closed?
Door Hinges
-
Is there a minimum of 3 hinges with all the screws fitted?
-
Are all the screws the correct size?
-
Are the hinges free from non-combustible packaging?
Door Handles
-
Does the door handle function correctly?
-
Is the handle fixed correctly and free from movement and all fixings in place?
Glazing & Glass
-
Is the intumescent seal continuous and attached to the glass and bead?
-
Are the glazing beads well attached to the frame and free from damage?
-
Is the glass free from cracking or damage
-
If the glass has been replaced is it fire rated glass?
Compliance
-
Compliance Rating
Comments
Confirmation
-
I the above name person confirm that I have conducted this audit in line with the relevant Operating Processes as laid out by Sodexo and Northumbria University, in order that it complies with BS:9999.