Project Information

  • Document No.

  • Part No.

  • Revision No.

  • Client Name

  • Project Name

  • Inspection Started

  • Prepared by

  • Location

Test Details

  • Drawings Supplied

  • Drawing Number

  • Drawing Revision

  • Drawing Date

  • Drawing Approval RPEQ

  • Specifications Required

  • Vacuum test not fewer than the number of manholes as shown in Table 22.5. Where projects contain both precast and cast in-situ manholes, view each type as a separate population. If any of the sample manholes fail the initial test, test all remaining manholes in that population.

  • Structure Construction Type

  • Test Method FNQROC Operational Work Specification Sewerage Reticulation S6, Clause S6.26

    Vacuum Pressure = -33.50kPa
    Hold Time = As per Table S6.1
    Allowable Loss in Nominated Timeframe = 3.50kPa

  • Structures to be Tested

  • Structure
  • Structure Identification Details

  • Structure Diameter

  • Structure Depth (mm)

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 17 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 21 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 28 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 35 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 42 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 49 SECONDS

  • Please refer to WSA 02-2002-2.3 Table 22.6 and calculate to suit actual manhole sizing or contact TestX Supervisor

  • Calculated HOLD Time?

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in Calculated hold time

  • Structure Depth (mm)

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 20 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 25 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 33 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 41 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 49 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 57 SECONDS

  • Please refer to WSA 02-2002-2.3 Table 22.6 and calculate to suit actual manhole sizing or contact TestX Supervisor

  • Calculated HOLD Time?

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in Calculated hold time

  • Please refer to WSA 02-2002-2.3 Table 22.6 and calculate to suit actual manhole sizing or contact TestX Supervisor

  • Structure Depth (mm)

  • Structure Size

  • Calculated HOLD Time?

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in Calculated hold time

  • RESULT

  • Test Method Northern Rivers Local Government Development Construction Specification, Clause C402.41

    Initial Vacuum Pressure = -33.50kPa
    Settle Time = 3 Minutes
    Test Vacuum Pressure = -33.50kPa
    Hold Time = As per Table C402.6
    Allowable Loss in Nominated Timeframe = 3.50kPa

  • Structures to be Tested

  • Structure
  • Structure Identification Details

  • Structure Diameter

  • Structure Depth (mm)

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 17 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 21 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 28 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 35 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 42 SECONDS

  • Please refer to WSA 02-2002-2.3 Table 22.6 and calculate to suit actual manhole sizing or contact TestX Supervisor

  • Calculated HOLD Time?

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in Calculated hold time

  • Please refer to WSA 02-2002-2.3 Table 22.6 and calculate to suit actual manhole sizing or contact TestX Supervisor

  • Structure Depth (mm)

  • Structure Size

  • Calculated HOLD Time?

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in Calculated hold time

  • RESULT

  • Structure Construction Type

  • Test Method Tweed Shire Council Development Construction Specification, Clause C402.41

    Initial Vacuum Pressure = -33.50kPa
    Settle Time = 3 Minutes
    Test Vacuum Pressure = -33.50kPa
    Hold Time = As per Table C402.8
    Allowable Loss in Nominated Timeframe = 3.50kPa

  • Structures to be Tested

  • Structure
  • Structure Identification Details

  • Structure Diameter

  • Structure Depth (mm)

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 17 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 21 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 28 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 35 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in 42 SECONDS

  • Please refer to WSA 02-2002-2.3 Table 22.6 and calculate to suit actual manhole sizing or contact TestX Supervisor

  • Calculated HOLD Time?

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in Calculated hold time

  • Please refer to WSA 02-2002-2.3 Table 22.6 and calculate to suit actual manhole sizing or contact TestX Supervisor

  • Structure Depth (mm)

  • Structure Size

  • Calculated HOLD Time?

  • Accept the structure under test if the test vacuum loss is =/<3.50kPa in Calculated hold time

  • RESULT

  • Structure Construction Type

  • Test Method SEQ Code Amendment to WSA02-2002-2.3, Clause 22.4.4

    Initial Vacuum Pressure = -37kPa
    Settle Time = 3 Minutes
    Test Vacuum Pressure = -33.80kPa
    Hold Time = As per Table 22.6
    Allowable Loss in Nominated Timeframe = 3.40kPa

  • Structures to be Tested

  • Structure
  • Structure Identification Details

  • Structure Diameter

  • Structure Depth (mm)

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 14 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 18 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 21 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 25 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 29 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 32 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 35 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 39 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 42 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 46 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 49 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 53 SECONDS

  • Please refer to WSA 02-2002-2.3 Table 22.6 and calculate to suit actual manhole sizing or contact TestX Supervisor

  • Calculated HOLD Time?

  • Structure Depth (mm)

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 17 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 21 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 25 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 30 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 34 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 38 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 42 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 46 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 51 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 55 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 59 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 63 SECONDS

  • Please refer to WSA 02-2002-2.3 Table 22.6 and calculate to suit actual manhole sizing or contact TestX Supervisor

  • Calculated HOLD Time?

  • Structure Depth (mm)

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 20 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 25 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 30 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 35 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 40 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 45 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 50 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 55 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 59 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 64 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 69 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 74 SECONDS

  • Please refer to WSA 02-2002-2.3 Table 22.6 and calculate to suit actual manhole sizing or contact TestX Supervisor

  • Calculated HOLD Time?

  • Structure Depth (mm)

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 26 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 33 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 39 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 46 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 52 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 59 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 65 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 72 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 78 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 85 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 91 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 98 SECONDS

  • Please refer to WSA 02-2002-2.3 Table 22.6 and calculate to suit actual manhole sizing or contact TestX Supervisor

  • Calculated HOLD Time?

  • Structure Depth (mm)

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 33 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 41 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 49 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 57 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 65 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 73 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 81 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 89 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 97 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 105 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 113 SECONDS

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in 121 SECONDS

  • Please refer to WSA 02-2002-2.3 Table 22.6 and calculate to suit actual manhole sizing or contact TestX Supervisor

  • Calculated HOLD Time?

  • Please refer to WSA 02-2002-2.3 Table 22.6 and calculate to suit actual manhole sizing or contact TestX Supervisor

  • Structure Depth (mm)

  • Structure Size

  • Calculated HOLD Time?

  • Accept the structure under test if the test vacuum loss is =/<3.40kPa in Calculated hold time

  • RESULT

Test Procedure

Confirm Project Information

  • Structures to be inspected and their details

  • Testing specification requirements

Initial Work Area Inspection

  • Is test area barricaded off or sufficiently delineated?

  • Is traffic control established?

  • Has a Safe Work Method Statement been completed and all control measures followed?

  • Has a Confined Space Risk Assessment & Entry Permit been completed?

  • Is the confined space equipment and procedures set up as per the Risk Assessment & Entry Permit conditions followed?

  • Structure lid removed and placed at a safe distance from the entry point

  • Environmental controls installed as and if required

Inspection Steps

  • Equipment checked and in good working order

  • Insert test plugs into structure inlets with extendable pole if possible so confined space risks are avoided

  • Inflate plugs and add support as per manufacturer's specifications

  • Place test plate, attach to vacuum pump and vacuum down manhole to test pressure

  • Allow for vacuum to stabilise for an amount of time as per specifications

  • Hold vacuum for time specified in specifications and record result

Disassemble Steps

  • Disconnect hose from vacuum pump and release pressure from structure

  • Remove test plate, release pressure from plugs and carefully retrieve plugs out of structure

  • Replace structure lid, remove barricading and return all items to test unit

Final Demobilisation

  • Notify client of result and to contact TestX office to arrange further testing or reports

  • Calibrated gauge numbers used

  • Inspector's remarks

  • Photo of work area and inspected structures

  • I declare that the inspection procedure was followed in accordance with the nominated specifications

  • Inspection Completed

  • Report Issue Date

Report Approval - Cam Reid

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.