Information
-
Project Name
-
Project Number
-
Owner Name
-
Conducted on
-
Prepared by
-
Location
-
Weigand Project Supervisor(s)
-
Location / BARCODE
WALL CONSTRUCTION
-
Is wall stenciled with appropriate rating every 10' or once per wall whichever is greater?
DRYWALL / PLASTER CONSTRUCTION
-
Is the drywall / plaster continuous along the wall?
-
Are all joints between pieces tight (within 1/4")?
-
Are all drywall joints mudded and taped?
-
Is the top of wall sealed with a continuous fireproofing spray or sealant?
MASONRY CONSTRUCTION
-
Is the wall continuous?
-
Is the top of wall sealed with a continuous fireproofing spray or sealant?
FIRESTOPPING
-
Firestop material cannot be installed over any other material such as drywall joint compound or smoke sealant. The material must be removed to provide an annular space around the item to be firestopped prior to installing the firestopping.
SLEEVE / OPEN ENDED PIPE - CONDUIT PENETRATIONS
-
Is there a sticker listing the UL Assembly next to the penetration?
-
Is the space around the penetration sized properly and reasonably?
-
Is the annular space around the pipe filled with firestopping material?
-
Is the interior space of the pipe filled with firestopping material?
CONTINUOUS / CLOSED ENDED PIPE PENETRATIONS
-
Is there a sticker listing the UL Assembly next to the penetration?
-
Is the space around the penetration sized properly and reasonably?
-
Is the annular space around the pipe filled with firestopping material?
ELECTRICAL
-
Are all electrical boxes and conduit steel?
-
Are all the electrical boxes in the wall no bigger than 4" x 4"?
-
Is there a minimum of 24" of horizontal distance between electrical boxes on opposite sides of the wall?
FIRE DAMPERS
-
Firestopping is not permitted around fire dampers.
-
Is there a retaining angle between the fire-damper and the duct penetration?
-
Add signature
-
The assessors believes the information contained within this visual assessment report to be correct at the time of printing. The assessors do not accept responsibility for any consequences arising from the use of the information herein. The report is based on matters which were observed or came to the attention of the assessors during the day and time of the assessment and should not be relied upon as an exhaustive record of all possible risks or hazards that may exist or potential improvements that can be made.