INTRODUCTION
-
Name of Airport?
-
What is the Airport ARFF Index?
-
What is the Airport Classification?
-
Does the proposed ARFF station provide adequate space for ARFF personnel, vehicle, equipment, and their related functions as prescribed by FAR 139.317 for certification?
-
Does the department provide EMS service?
-
Is a bay needed for over-head vehicle servicing?
ARFF APPARATUS BAYS (AC 150/5210-15)
-
Meets vehicle configuration (L/H/W) according AC 150/5210-15 Appendix A
-
Free personnel access from all interior / exterior access points.
-
Side by side parking versus tandem parking
-
Drive through bays
-
Observer's Comments:
ARFF APPARATUS BAYS STANDARD CLEARANCES (AC 150/5210-15)
-
6 feet between vehicles walls and storage areas.
-
8 feet between vehicles parked side by side.
-
5 feet between vehicle parked end to end.
-
5 feet between the vehicle and apparatus bay doors
-
7 feet between the top of vehicle platform and ceiling.
-
10 square feet of Personal Protection Equipment Storage.
-
Is 10% of space allocated for additional apparatus bay storage?
-
Observer's Comments:
ARFF APPARATUS BAYS ELECTRICAL DETAILS (AC 150/5210-15)
-
Are lighting levels provided per AC 150/5210-15, Chapter 3?
-
Are electrical outlets provided 18" - 24" above the floor and spaced at 8 feet intervals?
-
Are retractable electrical reels provided that service vehicle electrical systems?
-
Conduit should be provided to allow for future expansion
-
Observer's Comments:
ARFF APPARATUS BAYS INTERIOR ENVIRONMENT (AC 150/5210-15)
-
Is a vehicle exhaust extraction system provided and vented to the outside?
-
Are carbon monoxide detectors installed to sense CO in living quarters?
-
Are walls designed for easy cleaning and low maintenance?
-
Observer's Comments:
ARFF APPARATUS BAYS VEHICLE SUPPORT EQUIPMENT (AC 150/5210-15)
-
Is an over-head hoist provided?
-
Is the over-head hoist a minimum 1 ton rated device?
-
Has a vehicle water re-supply connection been provided (AC 150/5220-4)
-
Is a utility room provided with a deep slope sink, hot / cold water outlets, and mop wriner?
-
Is the utility room provided at least 64 - 100 square feet in size?
-
Is a compressed air supply capable of supplying a minimum of 120 psi available to maintain vehicle air supply system?
-
Is a foam agent recharging capability provided? Is it a overhead system or a transfer pumping system?
-
Observer's Comments:
ARFF APPARATUS BAY DOORS (AC 150/5210-15)
-
Are apparatus bay doors a minimum 16 X16 feet?
-
Is the maximum time to raise apparatus bay doors 16 seconds?
-
Are doors remotely operated from the alarm / watch room?
-
Is each door provided with a separate electrical operating control switch located adjacent to the door?
-
Are doors provided with a manual pull chain in the event of electrical system or switch failure?
-
Is each apparatus / bay door provided with a manual over-ride?
-
Are doors equipped with adjustable timers designed to close to prevent energy loss?
-
Are automatic door retractors provided on each door?
-
Are electrical "eye beams" installed to reverse door closing? Are they correctly mounted and do they function properly to preclude equipment or personnel injury?
-
Are doors equipped with windows? If windows are installed, are they tempered safety glass, and shatter proof?
-
Are apparatus bay doors insulated and provided with weather stripping?
-
Observer's Comments:
ARFF APPARATUS BAYS VEHICLE ROOM FLOOR (AC 150/5210-15)
-
Are floors designed to support current and future vehicle weight and footprints?
-
To prevent injury are adjacent room floors on the same level plane as the apparatus floor?
-
Are floor surfaces resilient to various liquids? Are they smooth surfaced and easy to clean?
-
Do floors have a minimum 1 inch (2.5 cm) to 10 feet (3M) slope to a center line transverse drain collection point?
-
Is the apparatus floor provided with a traverse drain heavy gauge cover, sediment / grease trap?
-
Observer's Comments:
ARFF APPARATUS BAY SLIDING POLES (NFPA 1500)
-
Meets safety requirements identified in NFPA 1500
-
Are poles located near walls and positioned away from obstructions?
-
Observer's Comments:
ARFF STATION APRON (AC 150/5210-15)
-
Does the apron / driveway have direct access to the aircraft movement area?
-
Does the apron area have exterior hose bibs with garden hose connections?
-
Are fire hydrants adjacent to the ARFF Station?
-
If wall hydrants are provided, are they corrected labeled?
-
Are pedestrian / vehicle traffic warning lights installed for location where traffic crosses the apron?
-
Observer's Comments:
ARFF STATION APRON STANDARDS (AC 150/5210-15)
-
Is the apron operating surface large enough to allow the longest vehicle access to any apparatus bay?
-
Is the apron at least 28 feet wide?
-
Is the apron length at least 1.5 times the longest vehicle lenght?
-
Are they tapered to not less that 28 feet for multi-vehicle stations?
-
Are they tapered to not less than 12 feet for single-vehicle stations?
-
Is the apron strength that same as the apparatus bay?
-
Gradient - Is the apron slope a minimum of 2 - 4 degrees and is it directed away from the apparatus bays?
-
Marking - Is the floor and apron striping provided? Is it at least 1.5 times the vehicle length for the apron?
-
Lighting - Is exterior lighting provided? Is it mounted to prevent view obstruction?
-
Apron Canopy - Is an apron canopy provided?
-
Are concrete bollards provided on each side of bay doors to prevent structural damage from backing vehicles?
-
Observer's Comments:
ARFF STATION WATCH / ALARM ROOM (AC 150/5210-15)
-
Is a watch / alarm provided for the receipt and dissemination of alarms, dispatch of equipment, and directing support resources?
-
General Design - Is the watch / alarm room provide for maximum surveillance of the airfield and apparatus bays? If deemed necessary, is the room elevated?
-
Is the room a minimum of 130 square feet? Does it have sufficient storage space and wall space for maps, reference material, and dispatch equipment?
-
Is the room equipped with a CCTV for security purpose?
-
Alternate emergency back-up power?
-
Accessibility to controls for electronic or electrical servicing / maintenance personnel?
-
Computer system with LAN access?
-
Radio equipment - ARFF and tunable radio capability?
-
Room dimmer switch and non-glare lighting?
-
Tinted glass?
-
A lavatory?
-
Backlit clock with 12 and 24 hour display?
-
Sound suppression to offset ARFF and aircraft sound levels?
-
Alarm - Are chimes / alert tones provided throughout the station and satellite stations?
-
Alarm - Is an audible alarm provided when auxiliary firefighters supplement emergency response personnel?
-
Alarm - Are all watch / alarm room controls easily accessible and with in reach of all operators?
-
Observer's Comments:
ARFF STATION MEDICAL DECON ROOM (AC 150/5210-15)
-
Is a room dedicated for medical clean-up and decontamination of ARFF personnel?
-
I the room equipped with a double sink, a shower, and drying area?
-
Is the space a minimum of 150 square feet?
-
Observer's Comments:
ARFF STATION GEAR WASHING / DRYING ROOM (AC 150/5210-15)
-
Is the room equipped with a commercial extractor washer and a heated drying rack?
-
Is the space a minimum of 200 square feet?
-
Observer's Comments:
ARFF STATION FIRST AID AND MEDICAL STORAGE (AC 150/5210-15)
-
Is a room dedicated for medical treatment or personnel seeking medical treatment?
-
Is the room lockable and equipped with a sink and cabinets for medical storage?
-
Is the space a minimum of 120 square feet?
-
Observer's Comments:
ARFF STATION COMPLIMENTARY AGENT STORAGE (AC 150/5210-15)
-
Is a storage room dedicated for the storage of Dry Chemical, Halon, Powder Fire Fighting Agents, and Nitrogen Cylinders?
-
Are doors of sufficient width to accommodate a forklift for their delivery of 4X4 pallets?
-
Is the space a minimum of 225 - 350 square feet?
-
Observer's Comments:
ARFF STATION SCBA AND FIRE EXTINGUISHER ROOM (AC 150/5210-15)
-
Is a room dedicated for the servicing and repair of SCBA and Fire Extinguishers?
-
Is the room provided with storage cabinets and a workbench to perform tasks and store materials and parts?
-
Is the space a minimum of 200 square feet?
-
Is an air filtration system available for re-servicing of SCBA?
-
Is an air compressor provided?
-
Is a cascade system used?
-
Are all components properly marked with labels / placards or signs that identify nomenclatures?
-
Are tags and warning labels affixed to equipment for safety operations?
-
Observer's Comments:
ARFF STATION HOSE DRYING FACILITIES (AC 150/5210-15)
-
Is the space a minimum of 150 square feet?
-
Is a drying rack required?
-
Is a mechanical drying machine required?
-
Are hose storage rack provided?
-
Observer's Comments:
ARFF STATION VEHICLE FUELING AREA (AC 150/5210-15)
-
Is an area adjacent to the apron provided for re-fueling?
-
Are fuel pumps adequately protected from physical damage?
-
Raised platform?
-
Bollards?
-
Are automatic / remote shut offs provided? Are distinct signs provided?
-
Do fuel storage tanks meets all standard requirements?
-
Observer's Comments:
ARFF STATION DAY ROOM (AC 150/5210-15)
-
Is a minimum of 20 square feet per person provided?
-
Is it furnished to provide a relaxing atmosphere?
-
Does it include furnishings, television, radio, tables, and other amenities for relaxtion?
-
Speakers for alarm notification announcements?
-
Observer's Comments:
ARFF STATION SLEEPING ROOMS (AC 150/5210-15)
-
Is the space a minimum of 140 square feet per firefighter?
-
Bedding / Mattress / Box spring / Framing / Headboard / Footboard
-
Nightstand and lamp?
-
Small desk and chair?
-
Lockable storage unit?
-
Speakers for alarm notification announcements?
-
Observer's Comments:
ARFF STATION LOCKER ROOMS (AC 150/5210-15)
-
Does the location provide for 15 square feet of space per firefighter, to include the space used by the locker itself?
-
Is locker space a minimum of 18 inches by 24 inches by 78 inches?
-
Is a locker provided for each individual firefighter?
-
Speakers for alarm notification announcements?
-
Observer's Comments:
ARFF STATION LAVATORIES (AC 150/5210-15)
-
Toilets, urinals, sinks, showers as appropriate based on local building codes?
-
Individual shower stalls - minimum of 9 square feet?
-
Clothing hooks, towels bars, soap dishes?
-
Ground Fault Interrupter (GFI) Outlets?
-
Ceiling and walls of water resistant materials?
-
Flooring that is slip resistant materials?
-
Vanity Mirrors of sufficient size for 3 personnel to use simultaneously?
-
Speakers for alarm notification announcements?
-
Observer's Comments:
ARFF STATION KITCHEN / DINING ROOM (AC 150/5210-15)
-
Is the space a minimum of 400 square feet?
-
Is the kitchen area of sufficient size to accommodate a commercial range, griddle, refrigerator / freezer (for each shift), microwave, food preparation area, storage and shelving for cooking utensils, a double sink with garbage disposal, commercial ice-maker, and commercial dishwasher?
-
Is an exit available that leads directly to the outside?
-
Do cooking appliances have a "manual shut-off" button to kill power or gas supply to the cooking devices when firefighters are dispatched?
-
Speakers for alarm notification announcements?
-
Observer's Comments:
ARFF STATION TRAINING ROOM (AC 150/5210-15)
-
Is the space a minimum of 48 square feet per firefighter?
-
Is secure storage space provided?
-
Are desk provided / or classroom seating provided?
-
Speakers for alarm notification announcements?
-
Observer's Comments:
ARFF STATION EMERGENCY GENERATOR ROOM (AC 150/5210-15)
-
Is a separate room provided for an emergency generator?
-
Is the generator of sufficient size to support all essential services?
-
Is the room equipped with an exterior access for maintenance and repair work?
-
Is the fuel supply sufficient to operate the generator under maximum load for a minimum 7 day period?
-
Is the room enclosed by fire rated walls and ceiling?
-
Speakers for alarm notification announcements?
-
Observer's Comments:
ARFF STATION PARKING AREA (AC 150/5210-15)
-
Is one space per on-duty firefighter provided?
-
Is access to parking controlled?
-
Is visitor parking provided?
-
Is Handicap parking provided?
-
Is access to parking designed to comply with ADA requirements?
MISCELLANEOUS OBSERVATION(S) & PHOTO(S)
-
Miscellaneous Observation(s)
-
Miscellaneous Photo(s)
SIGNATURE OF OBSERVER & COMMENTS
-
Observer"s Comments
-
Name & Signature of Observer
-
Date & Time of Observation
-
Date Reviewed By AIR - L thru AIR - LF