Mr. Electric Aluminium Wiring Inspection Report Name:
-
Client Name:
-
Report Number
-
Audit Title
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Personnel
Aluminium Wiring Inspection
Kitchen
-
Add media
-
10% of kitchen receptacles inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of kitchen light switches inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of kitchen light fixtures inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
Dining Room
-
Add media
-
10% of dinning room receptacles inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of dining room light switches inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of dinning room light fixtures inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
Living Room
-
Add media
-
10% of living room receptacles inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of living room light switches inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of living room light fixtures inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
Master Bed Room
-
Add media
-
10% of master bed room receptacles inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of master bed room light switches inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of master bed room light fixtures inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
Bed Room #1
-
Add media
-
10% of bed room #1 receptacles inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of bed room #1 light switches inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of bed room #1 light fixtures inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
All Other Bedrooms
-
Add media
-
10% of all other bed room receptacles inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of all other bed room light switches inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of all other bed room light fixtures inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
Hallways/Foyers/Common Areas
-
Add media
-
10% of hallways/foyer/common area receptacles inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of hallways/foyer/common area light switches inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of hallways/foyer/common area light fixtures inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
Basement
-
Add media
-
10% of basement receptacles inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of basement light switches inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of basement light fixtures inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
Electrical Panel(s)
-
Add media
-
10% of the breakers inspected. Inspection include removing device and visually check for: 1. Non-Aluminum rated devices 2. Discoloured wiring, caused by overheating 3. Discoloured insulation, caused by overheating 4. Loose connections, (torque test) 5. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
-
10% of the neutral connection points inspected. Inspection include removing device and visually check for: 1. Discoloured wiring, caused by overheating 2. Discoloured insulation, caused by overheating 3. Loose connections, (torque test) 4. Aluminium rated wire connectors
- No indication of aluminium wiring issues exist
- Non-Aluminium rated device connected to aluminium wiring
- Evidence of overheating
- Loose connections
- Improper wire nuts used
- N/A
Conclusion
-
Albumin wiring info and links to outside sources
Recommend and aluminium wiring repair
Stats on aluminum wiring fires. -
I understand that this Aluminium Wiring Inspection is performed with the intent to expose all electrical challenges but by no means carries any guarantee. Neither Mr. Electric nor any representative associated with Mr. Electric, nor the Service Professional performing the Safety Check-up shall be liable for any damages which may arise from the Aluminium Wiring Inspection but shall be sole responsibility of the property owner.
-