Information

  • Document No.

  • Audit Title

  • Date of Inspection

  • Inspector(s)

  • Competency

Equipment information

  • Area Classification

  • Area Equipment is installed

  • Equipment type

  • Equipment

  • Manufacturer

  • Serial Number / Part Number

  • Photograph the equipment (Optional)

  • Cable ID

  • Tag Number

  • Ex Protection

  • Ex Cert Number

  • IP Rating

  • Grade of inspection

  • Protection type

Equipment Schedule

  • Equipment

  • Code

  • Equipment

  • Code

  • Equipment

  • Code

  • Equipment

  • Code

  • Equipment

  • Code

  • Equipment

  • Code

  • Equipment

  • Code

  • Equipment

  • Code

  • Equipment

  • Code

  • Equipment

  • Code

  • Equipment

  • Code

  • Equipment

  • Code

Apparatus

  • Apparatus and/or circuit is appropriate to area classification (V,C,D)

  • There are no visible unauthorised modifications

  • Safety barrier units, relays and other energy limiting devices are of the approved type, installed in accordance with the certification requirements and are securely earthed when required

Installation

  • There is no any obvious damage to cables

  • Sealing of trunking, ducts, pipes, and/or conduits is satisfactory

  • Earth connections maintain integrity of type of protection

  • Cables not in use are terminated correctly

Environment

  • Apparatus is adequately protected against corrosion, weather, dusts, vibration and any other adverse factors

  • No undue accumulation of dust and dirt is present

  • Type of equipment to be installed to comply with zone

Apparatus

  • Apparatus is appropriate to area classification (V,C,D)

  • Apparatus circuit identification is available

  • Enclosures glass parts & glass to metal, sealing gaskets and/or compounds are satisfactory

  • There are no visible unauthorised modifications

  • Bolts, cable entry devices (direct and indirect) & blanking elements are of the correct type and are complete and tight Physical check

Installation

  • There is no any obvious damage to cables

  • Sealing of trunking, ducts, pipes, and/or conduits is satisfactory

  • Earthing connections, including any supplementary earthing bonding connections are satisfactory (e.g. connections are tight and conductors are of sufficient cross section) Physical check

Environment

  • Apparatus is adequately protected against corrosion, weather, dusts, vibration and any other adverse factors

  • No undue accumulation of dust and dirt is present

Apparatus

  • Apparatus is appropriate to area classification (V,C,D)

  • Apparatus circuit identification is available

  • Enclosures glass parts & glass to metal, sealing gaskets and/or compounds are satisfactory

  • There are no visible unauthorised modifications

  • Bolts, cable entry devices (direct and indirect) & blanking elements are of the correct type and are complete and tight Physical check

Installation

  • There is no any obvious damage to cables

  • Sealing of trunking, ducts, pipes, and/or conduits is satisfactory

  • Earthing connections, including any supplementary earthing bonding connections are satisfactory (e.g. connections are tight and conductors are of sufficient cross section) Physical check

Environment

  • Apparatus is adequately protected against corrosion, weather, dusts, vibration and any other adverse factors

  • No undue accumulation of dust and dirt is present

Apparatus

  • Apparatus is appropriate to area classification (V,C,D)

  • Apparatus circuit identification is available

  • Enclosures glass parts & glass to metal, sealing gaskets and/or compounds are satisfactory

  • There are no visible unauthorised modifications

  • Bolts, cable entry devices (direct and indirect) & blanking elements are of the correct type and are complete and tight Physical check

Installation

  • There is no any obvious damage to cables

  • Sealing of trunking, ducts, pipes, and/or conduits is satisfactory

  • Earthing connections, including any supplementary earthing bonding connections are satisfactory (e.g. connections are tight and conductors are of sufficient cross section) Physical check

  • Obstructions adjacent to flameproof flanged joints are in accordance with IEC 79-14

Environment

  • Apparatus is adequately protected against corrosion, weather, dusts, vibration and any other adverse factors

  • No undue accumulation of dust and dirt is present

  • Protection type

Apparatus

  • Apparatus and/or circuit is appropriate to area classification (V,C,D)

  • Apparatus installed is that specified in documentation

  • Apparatus temperature class is correct

  • Apparatus and/or circuit category and group is correct

  • Installation is clearly labelled

  • There are no visible unauthorised modifications

  • Safety barrier units, relays and other energy limiting devices are of the approved type, installed in accordance with the certification requirements and are securely earthed when required

Installation

  • There is no any obvious damage to cables

  • Sealing of trunking, ducts, pipes, and/or conduits is satisfactory

  • Earth connections maintain integrity of type of protection

  • Cables not in use are terminated correctly

Environment

  • Apparatus is adequately protected against corrosion, weather, dusts, vibration and any other adverse factors

  • No undue accumulation of dust and dirt is present

  • Type of equipment to be installed to comply with zone

Apparatus

  • Apparatus is appropriate to area classification (V,C,D)

  • Apparatus group is correct

  • Apparatus temperature class is correct

  • Apparatus circuit identification is available

  • Enclosures glass parts & glass to metal, sealing gaskets and/or compounds are satisfactory

  • There are no visible unauthorised modifications

  • Bolts, cable entry devices (direct and indirect) & blanking elements are of the correct type and are complete and tight Physical check

  • Breathing and draining devices are satisfactory

Installation

  • There is no any obvious damage to cables

  • Sealing of trunking, ducts, pipes, and/or conduits is satisfactory

  • Earthing connections, including any supplementary earthing bonding connections are satisfactory (e.g. connections are tight and conductors are of sufficient cross section) Physical check

  • Variable voltage/frequency installation in accordance with documentation

Environment

  • Apparatus is adequately protected against corrosion, weather, dusts, vibration and any other adverse factors

  • No undue accumulation of dust and dirt is present

Apparatus

  • Apparatus is appropriate to area classification (V,C,D)

  • Apparatus group is correct

  • Apparatus temperature class is correct

  • Apparatus circuit identification is available

  • Enclosures glass parts & glass to metal, sealing gaskets and/or compounds are satisfactory

  • There are no visible unauthorised modifications

  • Bolts, cable entry devices (direct and indirect) & blanking elements are of the correct type and are complete and tight Physical check

  • Breathing and draining devices are satisfactory

Installation

  • There is no any obvious damage to cables

  • Sealing of trunking, ducts, pipes, and/or conduits is satisfactory

  • Earthing connections, including any supplementary earthing bonding connections are satisfactory (e.g. connections are tight and conductors are of sufficient cross section) Physical check

  • Variable voltage/frequency installation in accordance with documentation

Environment

  • Apparatus is adequately protected against corrosion, weather, dusts, vibration and any other adverse factors

  • No undue accumulation of dust and dirt is present

Apparatus

  • Apparatus is appropriate to area classification (V,C,D)

  • Apparatus group is correct

  • Apparatus temperature class is correct

  • Apparatus circuit identification is available

  • Enclosures glass parts & glass to metal, sealing gaskets and/or compounds are satisfactory

  • There are no visible unauthorised modifications

  • Flange dimensions are within max permitted values

  • Bolts, cable entry devices (direct and indirect) & blanking elements are of the correct type and are complete and tight Physical check

  • Breathing and draining devices are satisfactory

Installation

  • There is no any obvious damage to cables

  • Sealing of trunking, ducts, pipes, and/or conduits is satisfactory

  • Earthing connections, including any supplementary earthing bonding connections are satisfactory (e.g. connections are tight and conductors are of sufficient cross section) Physical check

  • Obstructions adjacent to flameproof flanged joints are in accordance with IEC 79-14

  • Variable voltage/frequency installation in accordance with documentation

Environment

  • Apparatus is adequately protected against corrosion, weather, dusts, vibration and any other adverse factors

  • No undue accumulation of dust and dirt is present

  • Protection type

Apparatus

  • Apparatus and/or circuit is appropriate to area classification (V,C,D)

  • Apparatus installed is that specified in documentation

  • Apparatus temperature class is correct

  • Apparatus and/or circuit category and group is correct

  • Installation is clearly labelled

  • There are no unauthorised modifications

  • There are no visible unauthorised modifications

  • Safety barrier units, relays and other energy limiting devices are of the approved type, installed in accordance with the certification requirements and are securely earthed when required

  • Electrical connections are tight

  • Printed circuit boards are clean and undamaged

Installation

  • There is no any obvious damage to cables

  • Cables installed in accordance with documentation

  • Cable screens are earthed in accordance with the documentation

  • Sealing of trunking, ducts, pipes, and/or conduits is satisfactory

  • Point to point connections are tight

  • Earth continuity is satisfactory

  • Earth connections maintain integrity of type of protection

  • Intrinsically safe circuit is isolated from Earth or earthed only one point

  • Separation is maintained between I.s and non I.s circuits in common distribution boxes or relay cubicles

  • As applicable short circuit protection of the power supply is in accordance with the documentation

  • Cables not in use are terminated correctly

  • Special conditions of use(if applicable) are complied with

Environment

  • Apparatus is adequately protected against corrosion, weather, dusts, vibration and any other adverse factors

  • No undue accumulation of dust and dirt is present

  • Type of equipment to be installed to comply with zone

Apparatus

  • Apparatus is appropriate to area classification (V,C,D)

  • Apparatus group is correct

  • Apparatus temperature class is correct

  • Apparatus circuit identification is correct

  • Apparatus circuit identification is available

  • Enclosures glass parts & glass to metal, sealing gaskets and/or compounds are satisfactory

  • There are no unauthorised modifications

  • Lamp rating, type and position are correct

  • Electrical connections are tight

  • Condition of enclosure gaskets is satisfactory

  • Enclosed-break and hermetically sealed devices are undamaged

  • Bolts, cable entry devices (direct and indirect) & blanking elements are of the correct type and are complete and tight Physical check

  • Motor fans have sufficient clearance to enclosure and/or covers

  • Breathing and draining devices are satisfactory

  • Restricted breathing enclosures are satisfactory (Exn only)

Installation

  • There is no any obvious damage to cables

  • Type of cable is appropriate

  • Integrity of conduit systems and interface with mixed systems is maintained

  • Sealing of trunking, ducts, pipes, and/or conduits is satisfactory

  • Fault loop impedance(TN systems) or earth resistance (IT systems) is satisfactory

  • Insulation resistance is satisfactory

  • Automatic electrical protective devices operate within permitted limits

  • Automatic electrical protective devices are set correctly (auto reset not possible in Zone 1)

  • Earthing connections, including any supplementary earthing bonding connections are satisfactory (e.g. connections are tight and conductors are of sufficient cross section) Physical check

  • Cables not in use are correctly terminated

  • Variable voltage/frequency installation in accordance with documentation

  • Special conditions of use(if applicable) are complied with

Environment

  • Apparatus is adequately protected against corrosion, weather, dusts, vibration and any other adverse factors

  • No undue accumulation of dust and dirt is present

  • Electrical insulation is clean and dry

Apparatus

  • Apparatus is appropriate to area classification (V,C,D)

  • Apparatus group is correct

  • Apparatus temperature class is correct

  • Apparatus circuit identification is correct

  • Apparatus circuit identification is available

  • Enclosures glass parts & glass to metal, sealing gaskets and/or compounds are satisfactory

  • There are no unauthorised modifications

  • Lamp rating, type and position are correct

  • Electrical connections are tight

  • Condition of enclosure gaskets is satisfactory

  • Bolts, cable entry devices (direct and indirect) & blanking elements are of the correct type and are complete and tight Physical check

  • Motor fans have sufficient clearance to enclosure and/or covers

  • Breathing and draining devices are satisfactory

Installation

  • There is no any obvious damage to cables

  • Type of cable is appropriate

  • Integrity of conduit systems and interface with mixed systems is maintained

  • Sealing of trunking, ducts, pipes, and/or conduits is satisfactory

  • Fault loop impedance(TN systems) or earth resistance (IT systems) is satisfactory

  • Insulation resistance is satisfactory

  • Automatic electrical protective devices operate within permitted limits

  • Automatic electrical protective devices are set correctly (auto reset not possible in Zone 1)

  • Earthing connections, including any supplementary earthing bonding connections are satisfactory (e.g. connections are tight and conductors are of sufficient cross section) Physical check

  • Cables not in use are correctly terminated

  • Variable voltage/frequency installation in accordance with documentation

  • Special conditions of use(if applicable) are complied with

Environment

  • Apparatus is adequately protected against corrosion, weather, dusts, vibration and any other adverse factors

  • No undue accumulation of dust and dirt is present

  • Electrical insulation is clean and dry

Apparatus

  • Apparatus is appropriate to area classification (V,C,D)

  • Apparatus group is correct

  • Apparatus temperature class is correct

  • Apparatus circuit identification is correct

  • Apparatus circuit identification is available

  • Enclosures glass parts & glass to metal, sealing gaskets and/or compounds are satisfactory

  • There are no unauthorised modifications

  • Flange faces are clean and undamaged and gaskets, if any, are satisfactory

  • Flange dimensions are within max permitted values

  • Lamp rating, type and position are correct

  • Bolts, cable entry devices (direct and indirect) & blanking elements are of the correct type and are complete and tight Physical check

  • Motor fans have sufficient clearance to enclosure and/or covers

  • Breathing and draining devices are satisfactory

Installation

  • There is no any obvious damage to cables

  • Type of cable is appropriate

  • Stopper boxes and cable boxes are correctly fitted

  • Integrity of conduit systems and interface with mixed systems is maintained

  • Sealing of trunking, ducts, pipes, and/or conduits is satisfactory

  • Fault loop impedance(TN systems) or earth resistance (IT systems) is satisfactory

  • Insulation resistance is satisfactory

  • Automatic electrical protective devices operate within permitted limits

  • Automatic electrical protective devices are set correctly (auto reset not possible in Zone 1)

  • Earthing connections, including any supplementary earthing bonding connections are satisfactory (e.g. connections are tight and conductors are of sufficient cross section) Physical check

  • Cables not in use are correctly terminated

  • Obstructions adjacent to flameproof flanged joints are in accordance with IEC 79-14

  • Variable voltage/frequency installation in accordance with documentation

  • Special conditions of use(if applicable) are complied with

Environment

  • Apparatus is adequately protected against corrosion, weather, dusts, vibration and any other adverse factors

  • No undue accumulation of dust and dirt is present

  • Did you answer no or unsafe to any of the above questions?

  • Please sign to close out inspection as compliant

  • Does the apparatus and/or circuit require to be shutdown until a repair can be carried out

  • Please enter the isolation certificate number

  • Please provide a picture of the isolation certificate

Completed Inspection

Completed Inspection

  • Completion Date

  • Compex EX01-04 inspector name and signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.