Information
-
Audit Title
-
Document No.
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Personnel
Exterior
-
Photo taken from entrance of compound looking in.
-
Photo of Hydro meter and pole markings.
-
Photo of Tower and close up of pinwheel.
-
Photo of Tower bases.
-
Photo of Tower Guys taken from base of Tower
-
Photo of inside Rear cabinet.
-
Compound: must be clean and free of debris.
-
Fences & Gates: functional without damage or deficiencies.
-
Locks & Mechanisms: all locks and mechanisms present and functional.
-
Shelter or Enclosure: exterior of shelter or enclosure without damage or deficiencies.
-
Identification & Labelling: all exterior labelling and identification present. Engineering # on door (other identifications vary by province).
-
Tower and Shelter Lighting: exterior shelter and lighting functional.
-
Surrounding Environment: surrounding area should be free of potentially dangerous or damaging objects. Example: trees, branches, etc...
-
Rear access panel is locked with Abloy lock
-
Rear access panel boots installed and any openings sealed.
-
Polyphasors in Rear access panel is grounded and tight. All electrical connections tight.
Grounding
-
Photo of poor grounding (if necessary).
-
Ground Cables: all exterior grounding cables must be solid, properly attached without damage and not missing.
-
Ground Resistance Meter: All ground connections must be checked with Ground Resistance Meter.
-
Enter ground readings
Generator
-
Check spigot ground and spigot clear of obstructions
-
Environmental: environmental kit present if required. Environmental sticker on door?
Interior
-
Take picture looking into shelter from front door and each piece of equipment inside the shelter.
-
Shelter Clean: interior of shelter or enclosure must be free of unnecessary debris, garbage kept to a minimum, floor and environment clean.
-
All devices have their IP labelled.
-
Label site engineering number and name on Argus door Electrical breaker box
-
Labelling: all interior labelling and identification present (AC breaker panel, site ID plaque, etc...).
-
Hardware Fixed: all items mounted or attached to walls or ceiling must be safe and solid (example: cable trays, electrical boxes, shelving, etc...).
-
Airtightness: interior must be airtight and waterproof. No holes should be present in floor, walls or antenna entry ports to prevent water or vermin migration.
-
HVAC: A/C and ventilation functional.
-
Interior Accessories: table, chair, step ladder (rooftop sites), garbage can, broom, dustpan, floor mat and fire extinguisher (valid) all present if area permits. Broom dustpan and fire extinguisher mounted on wall
-
Proper temperature settings are programmed into the environmental panel.
RF Hardware
-
All frames must be solidly attached and properly grounded.
-
All RF hardware and equipment must be properly and safely installed and grounded.
-
Noran Tel check GMT fuses values and label. Juniper 5A, HSPA BBU 15A, MPR 10A
-
All electrical connections must be safe and solid.
-
All RF connections must be safe and properly torqued.
-
All cabling secured with tie wraps on frames and cable trays.
-
Building temperature sensor moved the side of Argus if sensor was installed by door.
-
Outside receptacle turn off.
-
Battery capacity testing performed.
-
Inventory performed.
-
Door code changed to proper NWZ code.
Juniper, Argus, Microwave and BBU
-
Juniper Check remote access and check for active alarms.
-
Argus power plant label breakers and check Smoke Detector is 0.5 amp.
-
Argus power plant number batteries and check for loose connections.
-
Argus power plant check temperature probes are on the top bank of batteries.
-
Argus power plant check door hinges not broken.
-
Argus power plant check configuration, dynamic text has been pushed.
-
Argus power plant check battery inventory and capacity updated.
-
Argus power plant check site name and location is correct.
-
Argus power plant check AC mains, temp probes calibrated and data logging in enabled
-
Argus power check remote access and download a copy of the configuration file.
-
BBU check for remote/local access and no active alarms.
-
BBU environmental alarms enabled and tested to NOCC.
-
BBU check device status, topography status and version of software for the WBBP, WMPT cards.
-
BBU and RRU RX Fiber levels are at least 2500.
-
Microwave Check remote/local access to and check for active alarms.
-
Microwave check settings and RSLs. Screen shots of vital settings and MIB backup.
-
Microwave: All RF connections must be safe and properly torqued.
-
Check all screws tight on BBU and Microwave cards
-
All unused slots have covers
Documentation & Site Information
-
Log books present at site and populated.
-
Acceptance tests, work orders and antenna sweeps present on site (or on FMLS).
-
NRM information precise and up-to-date.