Title Page
-
Site
-
Document No.
-
Job Number
-
Client
-
Date
-
Cable number
-
Item description (Charger 1, Paymate, etc.)
-
Cable Type and Size
- 4 x 150mm consumer mains
- 4 x 120mm + 35mm earth
- 6mm 2C&E Orange circ
- 2.5mm 2C&E Orange circ
- 10mm 2C&E Orange circ
- 120mm earth
- 50mm earth
- 35mm earth
-
Source
-
Destination
-
Prepared by
Test & Verification
Visual Inspection pre energisation
-
Inspect plant for damage. Is it in good condition?
-
Please describe issue. Add photos
-
Are all circuit breakers and switches in the off position?
-
Check all connections where practicable. All tight?
-
Please describe issue. Add photos
-
Is the item of plant fit for energisation?
-
Please describe issue. Add photos.
Voltage and phase rotation checks where applicable. Energize relevant circuit braker and conduct tests at field terminals.
-
Meter used
Voltage Tests. If single phase, answer questions for Red and Neutral only
-
Neutral - Earth
-
Red - Earth
-
Red - Neutral
-
Red - White
-
Red - Blue
-
White - Earth
-
White - Neutral
-
White - Blue
-
Blue - Earth
-
Blue - Neutral
Phase rotation test.
-
Phase rotation correct?
-
Please describe issue. Add photos
Earth Fault Loop Impedence Tests
-
Meter used
-
Red fault loop impedence
-
Red Prospective Short Circuit Current
-
White fault loop impedence
-
White Prospective Short Circuit Current
-
Blue fault loop impedence
-
Blue Prospective Short Circuit Current
Functional Tests
-
Turn on the main switch/plug in device. Does the device start up?
-
Please describe issue. Add photos
-
Turn on subsequent CBs/switches and verify power up.
-
Please describe issue. Add photos
-
If applicable, check lights on comms ports. Lights should be blinking if basic communications have been established.
-
Please describe issue. Add photos
Close out
-
Is the device ready for commissioning?
-
Comments (tagged, locked out, etc)
-
Electrical Licence Number
-
Sign off