Electrical Switchroom Checklist
-
Before you open the door of the substation or switchroom ensure that any Fire Protection Gas Suppression systems have been properly isolated by a competent person and secured.
- Yes - proceed to acces
- No - isolate before proceeding
- No extinguishant installed- proceed to access
-
When you first open the door and before proceeding into the substation or switch room use your senses to check for:
- Gas - do not proceed
- Pungent rotten egg smells which would indicate the presence of decomposed SF6 gas - do not proceed
- Crackling sounds and smells of Ozone which would indicate the presence of electrical arcs
- Evidence of oil leaks or ingress of water
- If you detect any of these conditions do not enter, secure the door, report your findings to your management and await further instructions.
- No smells - proceed to access
-
Is there a copy of the electricity at works regulations 1989 posted in the switchroom
- Yes - no action required
- Request Supervisor / Manager to purchase
-
Is there a copy of the first aid signage posted in the switchroom
- Yes - no action required
- Request Supervisor / Manager to purchase
-
Is lighting adequate ?
- Yes - no action required
- No - advise Supervisor / Manager
-
Ensure all floor areas are clean, rubbish removed and disposed
-
Are Entry locks secure and working correctly ?
-
Are sprinkler heads free of obstruction ?
-
Are smoke & heat detectors free of obstruction ?
-
Are all fire barriers and penetrations in place and undisturbed ?
-
Check all circuit breakers are in their normal operating positions
-
Are all battery tripping units are healthy ?
-
If applicable check all power factor correction units are indicating normal healthy conditions
-
Check all protection relays are indicating normal healthy conditions
-
Check for any signs of compound leaks from cable termination chambers
-
Check that all safety equipment and tools are available and free from defect
- Yes - proceed to acces
- No - isolate before proceeding
- No extinguishant installed- proceed to access
-
Check all heating and ventilation systems are operating normally
-
If applicable check the basement de-watering pumps are operating normally
- Yes - proceed to acces
- No - isolate before proceeding
- No extinguishant installed- proceed to access
-
Check for roof leaks or ingress of water
-
Please take a photo and record plantroom condition
-
Ensure lighting is turned "OFF" when exiting the plantroom
-
Reinstate extinguishant system if required