Field Junction Box Checklist
General
-
Time
-
ITP Inspection
-
Inspection Type
- Installation Inspection
- General
- Punchlist Signoff
- Compliance
- Post Delivery
- Final Handover
- Damage Report
- Reinspection
-
Basic Location
- Access Roads
- EPCM
- Overland Conveyor
- ROM Reclaim
- ROM Transfer Pad
- MIA
- Raw Coal Stockpiles
- CV-045
- TS-044
- CV-008
- General Surface Aress
- MSF
- M&M Drift
- Mainteck Offsite Yard
- CV Drift
- SK041 RCS Stacker
- RE041 RCS Reclaimer
- Substation MP-SU-444
- Substation MP-SU-422
- Substation G1-SS-H01
- Substation G1-SS-A01
- CHPP
-
Specific Location/s
-
Attendees
- Mark Sanders
- Bruce Johnston
- Patrick Doody
- Wylie Pearson
- Grant Porter
- Dave Middleton
- Phil Adlam
- Tony Pereria
- David Seaver
- Andrew Marriott
- Michael Ross
- CJ Riley
- Deon Cordie
- Shaun Smith
-
Other Attendees
1. FAT Documentation
-
Documentation available?
-
Add notes
-
Add photos
2. Name Plate Fitted
-
-
Add notes
-
Add photos
3. Enclosure Built Fit for Purpose
-
All enclosures shall have generous dimensions to accommodate all electrical and control equipment without overcrowding and to minimise excessive heat buildup within the enclosure. Marshalling boxes shall have 20% spare space and terminals.
-
Add notes
-
Add photos
4. Outdoor IP 66
-
Constructed from grade 316 stainless steel
-
Add notes
-
Add photos
5. 22.5° Roof Pitch
-
The roof shall overhang the front of the enclosure by at least 50mm.
-
Add notes
-
Add photos
6. Indoor IP 54
-
Enclosure shall be painted mild steel. Naturally ventilated only.
-
Add notes
-
Add photos
7. Bottom Entry Gland Plate
-
All enclosures shall be fitted with removable 6mm thick brass bottom entry gland plates, suitable for removal of the entire gland plate with cables still attached. Gland plates shall have a minimum 20% spare capacity. Gland plates shall be bolted to the enclosure and fitted with a suitable gasket to maintain the IP rating. It shall be solidly bonded to the enclosure earth bar via a suitable flexible braided earth conductor and purpose stud mounted on the gland plate.
-
Add notes
-
Add photos
8. Floor Mounted Enclosures
-
Floor mounted enclosures shall be fitted with a 100mm hot dip galvanised plinth.
-
Add notes
-
Add photos
9. Doors
-
Double return edges and be able to open to angle of 135°. T-type handles shall be provided, except where low voltage equipment is located within the enclosure and the door locks then requiring a special tool to be opened. A double return shall be provided on the body of the enclosure.
-
Add notes
-
Add photos
10. Door Stay
-
To ensure that the doors open to the required angle and retain them in the open position.
-
Add notes
-
Add photos
11. Doors Earthed
-
The hinged door shall be connected to the earth bar via a suitable flexible earth conductor.
-
Add notes
-
Add photos
12. Document Pocket
-
All panels shall have a document pocket inside the door. Document holders shall be welded channel suitable to accept A4 documents.
-
Add notes
-
Add photos
13. Door Stiffening
-
Doors shall be suitably stiffened to prevent distortion. In any case, no door shall be more than 850mm wide.
-
Add notes
-
Add photos
14. Hinges x 2
-
Enclosures with doors <900mm high shall incorporate a minimum of two hinges. Hinges shall be chrome plated with stainless steel pins, and one pin longer than the others.
-
Add notes
-
Add photos
15. Hinges x 3
-
Enclosures with doors >900mm high shall have a minimum of three hinges and shall be suitably stiffened.
-
Add notes
-
Add photos
16. Centre Mullion
-
Enclosures with clear openings larger than 800mm, shall have doors that close on a centre mullion.
-
Add notes
-
Add photos
17. 8mm Square Locks
-
Individual 8ram square key door locks shall be fitted to all field mounted electrical enclosures. Three point door locking mechanisms are not acceptable.
-
Add notes
-
Add photos
18. HD Neoprene Gasket Seal
-
Seals shall be glued and held in place by continuous retaining strips.
-
Add notes
-
Add photos
19. Coating
-
Refer: GROS-TSTD-MS-003
-
Add notes
-
Add photos
20. Gear Tray
-
All internally mounted equipment such as relays, remote I/O, etc shall be mounted on the equipment gear plate only. Side mounting of equipment is not acceptable.
-
Add notes
-
Add photos
21. Segregation
-
Terminal strips and ducting segregated by voltage: 240Vac power wiring (shroud and warning label), 4-20mA analogue signals (IS signals in separate enclosure in field), 24Vdc digital signsls (IS signals in separate enclosure in field), instrument or control system communications. All voltages above extra low voltage shall be suitably shrouded with minimum IP2XB.
-
Add notes
-
Add photos
22. Intrinsically Safe
-
Intrinsically safe circuits and hazardous area enclosures shall be designed and installed in accordance with requirements of AS/NZS 3000, AS/NZS 60079.
-
Add notes
-
Add photos
23. Terminals
-
35mm DIN rail mounted, screw type terminals. Minimum terminal size 2.5mm2 wiring, power terminals sized for application. Terminate all cores with 20% spare. Standard stoppers, dividers, barriers tier labels and bridging links to IP2XB.
-
Add notes
-
Add photos
24. Internal Wiring
-
Terminals mounted vertically, split PVC ducts on either side. There shall be adequate clearance to read wire numbers in full and readily insert and extract wires. (Min 50mm), Use labeled shrouds on all above ELV.
-
Add notes
-
Add photos
25. Labels
-
All equipment shall be identified by a label attached to a non-detachable part. Refer to the specification.
-
Add notes
-
Add photos
26. Instrument Earth
-
The earth rod system shall be connected together and tied back to an independent instrument earth bar labeled "Instrument Earth Bar". GROS-TSTD-EL-010-V2
-
Add notes
-
Add photos
27. Cable Colors
-
Refer Specification.
-
Add notes
-
Add photos
28. Remote I/O
-
Refer specification.
-
Add notes
-
Add photos
Inspector
-
Inspector
-
Signature