Title Page

  • I.D.I. Job Number

  • Job Site Name

  • Conducted on

  • I.D.I. QAQC Inspector

  • Job Site Area of QAQC Inspection

  • Confirm for updated drawings, RFI's, plans & specs

  • Confirm mineral wool and spray, per approved submittals, are on site

  • Confirm drywall is down from substrate 1" or per manufacturer's requirements if different

  • Confirm speed plugs are installed in flutes above top track and speed strips installed above drywall below speed plug and below valley of flute at proper compression per manufacturer's requirements

  • Confirm mineral wool at beam is packed tight around beams and flush with drywall per manufacturer's requirements

  • Confirm there are no gaps between compressed speed plug and decking

  • Confirm there are no gaps between the ends of speed strips in all areas

  • Confirm fire taping is complete prior to spray application

  • Confirm drywall screw inspection was done

  • Confirm mineral wool has been inspected prior to spray

  • Confirm fire taping is complete prior to fire spray application

  • Confirm cleanup of our cartons and scrap materials

  • Comments

  • Sign Off

  • I.D.I. QAQC Inspector

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.