Title Page
-
GeoOP job number
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
PV module manufacturer and model number
- Sapphire Gem 250 watt
- Solar Juice Opal 250 watt
- Trina Honey 250 watt
-
Number of modules in series in a string
-
Number of strings in parallel in PV array
-
Inverter manufacturer and model number
-
Number of inverters
-
Number of MPPTs
-
PV array tilt and orientation
-
Array frame is certified to AS1170.2 for installation location
-
Array frame is installed to to manufacturers instructions
-
No galvanically dissimilar metals are in contact with the array frames or supports
-
Roof penetrations are suitably sealed and weatherproofed
-
PV wiring losses are less than 3% at the maximum current output of the array
-
Where PV array comprises multiple strings, string protection has been provided
-
Wiring is protected from mechanical damage and is appropriately supported
-
Weatherproof PV isolator mounted adjacent to array
- ZJ BENY 1000V 32A
-
All low voltage wiring has been installed by a licensed electrical tradesperson
-
All wiring has been tested and approved by a qualified electrical tradesperson
-
PV array isolator mounted adjacent to the inverter
- Yes
- No
- N/A
-
Isolator is mounted on output of inverter
-
Lockable AC circuit breaker is mounted within the switchboard to act as the inverter main switch for the PV/inverter
- 16 Amp
- 20 Amp
- 25 Amp
- 32 Amp
-
Inverter is installed to manufacturers specification
-
Inverter ceases supplying power within 2 seconds of a loss of mains power
-
Inverter does not resume supplying power until mains have been present for more than 60 seconds
Continuity check
-
Continuity of all string, sub-array and array cables
-
Continuity of all earth connections (including module frame)
Insulation resistance measurements
-
Array positive to earth M ohm
-
Array negative to earth M ohm
System check
-
String 1 voltage
-
String 1 short circuit current
-
String 1 operating current
-
String 1 polarity
-
String 2 voltage
-
String 2 short circuit current
-
String 2 operating current
-
String 2 polarity
-
String 3 voltage
-
String 3 short circuit current
-
String 3 operating current
-
String 3 polarity
-
String 4 voltage
-
String 4 short circuit current
-
String 4 operating current
-
String 4 polarity
-
CEC installers name
- Cameron Walker
- Christopher van Zanten
- Mark Doolan
-
CEC installers signature
-
CEC accreditation number
- A9975582
- A1575465
- Other
-
CEC designers name
- Cameron Walker
- Christopher van Zanten
- Other
-
CEC designers signature
-
Electricians license number
- E37355 - 209363C
- A45153 - 58259S
- A50178 - 68022S
-
Electricians signature
The following safety/warning labels have been attached
-
"Warning" Dual Supply -Isolate both normal and solar supplies before working on this switchboard. (On switchboard that inverter is directly connected)
-
"Normal supply" main switch (is permanently fixed at the main switch)
-
"Solar supply" main switch (is permanently fixed at the solar main switch)
-
"Warning" Dual supply - isolate solar supply at Distribution Board (where the inverter connects to a DB)
-
Inverter location (where the inverter is not located adjacent to the main switchboard)
-
"Warning" hazardous DC voltage (Permanently fixed on array junction boxes)
-
"Solar array on roof" and "PV" labels (permanently fixed on MSB and/or meter box)
-
"PV array DC isolator" (DC isolator a clearly identified)
-
"Warning - multiple DC sources" (Placed adjacent to inverter when multiple isolator are used and not ganged together)
-
"Solar" (Labels placed on exterior of wiring enclosures)
-
"Shut down procedure" (permanently fixed at inverter and/or main switchboard)