Title Page

  • GeoOP job number

  • Client / Site

  • Conducted on

  • Prepared by

  • Location
  • PV module manufacturer and model number

  • Number of modules in series in a string

  • Number of strings in parallel in PV array

  • Inverter manufacturer and model number

  • Number of inverters

  • Number of MPPTs

  • PV array tilt and orientation

  • Array frame is certified to AS1170.2 for installation location

  • Array frame is installed to to manufacturers instructions

  • No galvanically dissimilar metals are in contact with the array frames or supports

  • Roof penetrations are suitably sealed and weatherproofed

  • PV wiring losses are less than 3% at the maximum current output of the array

  • Where PV array comprises multiple strings, string protection has been provided

  • Wiring is protected from mechanical damage and is appropriately supported

  • Weatherproof PV isolator mounted adjacent to array

  • All low voltage wiring has been installed by a licensed electrical tradesperson

  • All wiring has been tested and approved by a qualified electrical tradesperson

  • PV array isolator mounted adjacent to the inverter

  • Isolator is mounted on output of inverter

  • Lockable AC circuit breaker is mounted within the switchboard to act as the inverter main switch for the PV/inverter

  • Inverter is installed to manufacturers specification

  • Inverter ceases supplying power within 2 seconds of a loss of mains power

  • Inverter does not resume supplying power until mains have been present for more than 60 seconds

Continuity check

  • Continuity of all string, sub-array and array cables

  • Continuity of all earth connections (including module frame)

Insulation resistance measurements

  • Array positive to earth M ohm

  • Array negative to earth M ohm

System check

  • String 1 voltage

  • String 1 short circuit current

  • String 1 operating current

  • String 1 polarity

  • String 2 voltage

  • String 2 short circuit current

  • String 2 operating current

  • String 2 polarity

  • String 3 voltage

  • String 3 short circuit current

  • String 3 operating current

  • String 3 polarity

  • String 4 voltage

  • String 4 short circuit current

  • String 4 operating current

  • String 4 polarity

  • CEC installers name

  • CEC installers signature

  • CEC accreditation number

  • CEC designers name

  • CEC designers signature

  • Electricians license number

  • Electricians signature

The following safety/warning labels have been attached

  • "Warning" Dual Supply -Isolate both normal and solar supplies before working on this switchboard. (On switchboard that inverter is directly connected)

  • "Normal supply" main switch (is permanently fixed at the main switch)

  • "Solar supply" main switch (is permanently fixed at the solar main switch)

  • "Warning" Dual supply - isolate solar supply at Distribution Board (where the inverter connects to a DB)

  • Inverter location (where the inverter is not located adjacent to the main switchboard)

  • "Warning" hazardous DC voltage (Permanently fixed on array junction boxes)

  • "Solar array on roof" and "PV" labels (permanently fixed on MSB and/or meter box)

  • "PV array DC isolator" (DC isolator a clearly identified)

  • "Warning - multiple DC sources" (Placed adjacent to inverter when multiple isolator are used and not ganged together)

  • "Solar" (Labels placed on exterior of wiring enclosures)

  • "Shut down procedure" (permanently fixed at inverter and/or main switchboard)

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.